Hitachi L300P Series service manual How to remove cooling fan for steel case

Page 35

(How to remove cooling fan for steel case)

Remove terminal cover and front cover.

Reconfirm that the charge lamp is turned OFF.

ƒRemove the all screws of the cooling fan case and pull out like following figure. Remove the connector for fan connection.

(How to fix cooling fan for steel case)

Pay attention to the direction of the cooling fan.

Connect the fan connector to J21 or J22 or J23 or J24 (depends on the model) on the power PCB. ƒ Fix the cooling fan case to the inverter main body.

Fix the front cover and terminal cover.

(2) DC bus capacitor

Big capacitance of electrolytic capacitors are used in a DC bus line of the inverter as a smoothing circuit. Due to the chemical reaction inside the capacitor, its lifetime highly depends on the ambient temperature and usage condition. Replacement is recommended to be done in 5 years under normal usage condition. Also, it should be anyway replaced with new ones when there is any abnormality is found or its capacity becomes less than 85% of its rated capacitance.

(How to remove DC bus capacitor for mold case)

Remove terminal cover.

Reconfirm that the charge lamp is turned OFF. ƒ Remove blind cover.

Remove all the screws connecting capacitor PCB and power PCB. Pull the capacitor PCB downwards.

5- 6

Image 35
Contents Hitachi Inverter Revision History Table Inverter specification Investigation of the inverter 1 SJ300 Inverter specificationFunction Mode Code 2nd motor Signal output mode Others Allowable motor selection 20-75.0kW 160kW User 2 L300P FE/-FU/-FR PID Terminal Meter C083 O2 adjustment 9999./1000-655310000-65530 U006 User6 selection Inverter trip contents, remedy, advice Trouble ShootingIgbt Device- Net option board SJ-DN Option error Feed-back board SJ-FBDigital-input option board SJ-DG Check of the trip monitor contents Check of the warning monitor contents Return to an initialization setup Factory-shipment state Monitor mode Debug ModeUSA Function modeInitial cofiguration completion check procedure Setup of an inverterSetting procedure Model selection code C198 Code SJ300 L300P Control signal Control power supplyMaintenance and Inspection Daily and annual maintenance Megger test How to check inverter & converter portion Parts replacement How to remove cooling fan for steel case How to fix DC bus capacitors for mold case Unit replacement English Internal block diagram SJ300-004-007LF Circuit Diagram SJ300-015 055LF Circuit Diagram SJ300-075-110LF , L300P-110-150LFR Circuit Diagram SJ300-150 220LF , L300P-185 300LFR Circuit Diagram SJ300-300LF, L300P-370LFR Circuit Diagram SJ300-370-450LF, L300P-450-550LFR Circuit Diagram SJ300-550LF,L300P-750LFR Circuit Diagram SJ300-007HF Circuit Diagram SJ300-015-055HF Circuit Diagram SJ300-075-110HF , L300P-110-150HFR Circuit Diagram SJ300-150 220HF , L300P-185 300HFR Circuit Diagram SJ300-300HF , L300P-370HFR Circuit Diagram SJ300-370- 550HF,L300P-450-750HFR Circuit Diagram DM Board SJ300-750-1320HF , L300P-900-1320HFR Circuit Diagram Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page SJ300/L300P Series Spare Parts List SJ3 CT PCB DM PCB NGMB25