Hitachi L300P Series service manual Fe/-Fu/-Fr

Page 14

Function Mode

 

Code

Function name

L300P Setting range

Initial data

N o t e

 

-FE/-FU/-FR

 

 

 

 

 

 

 

 

A001

Frequency setting selection

00(VR)/01(terminal)/02(operator)/03(RS485)/

01/01/00

 

 

 

04(option1)/05(option2)

 

 

 

 

 

 

 

setting

 

A002

Operation setting selection

01(terminal)/02(operator)/03(RS485)/04(option1)/05(option2)

01/01/02

 

 

A003

Base frequency

30. - Maximum. frequency(Hz)

50./60./60.

 

 

 

 

Base

 

A203

Base frequency, 2nd motor

30. - 2nd M aximum. frequency (Hz)

50./60./60.

 

 

A004

Maximum frequency

30. - 400. (Hz)

50./60./60.

 

 

 

 

 

 

A204

Maximum frequency, 2nd

30. - 400. (Hz)

50./60./60.

 

 

 

motor

 

 

 

 

 

 

 

 

 

A005

AT terminal selection

00( Changing of O and OI with AT terminal)/01(Changing of O and O2

00

 

 

 

with AT terminal)

 

setting

 

 

 

 

 

 

 

 

/02(auxiliary speed of O, OI [reversible]

 

 

 

 

A006

02 selection

00(single)/01(auxiliary speed of O, OI) [no reversible]

00

 

 

 

 

 

input

 

 

 

 

 

 

 

A011

0 start

0.00-99.99/100.0-400.0 (Hz)

0.00

 

 

 

 

Analog

 

A012

0 end

0.00-99.99/100.0-400.0 (Hz)

0.00

 

 

A013

0 start rate

0.-100.0 (%)

0.

 

 

 

 

 

 

A014

0 end rate

0.-100.0(%)

100.

 

 

 

A015

0 start selection

00 (external starting frequency)/01( OHz)

01

 

 

 

A016

O, OI, O2 sampling

1.-30.(times)

8.

 

 

 

A019

Multi-speed selection

00(binary : range is to 16 stage speed with 4 terminals)/01(bit : range

00

 

 

 

is to 6 stage speed with 5 terminals)

 

 

 

 

 

 

 

 

 

A020

Multi-speed 0

0.00, starting frequency-maximum. frequency(Hz)

0.00

 

 

 

A220

Multi-speed 0, 2 nd motor

0.00, starting frequency-2ndmaximum frequency(Hz)

0.00

 

 

 

A021

Multi-speed1

0.00, starting frequency-maximum frequency(Hz)

0.00

 

setting

 

A022

Multi-speed2

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

A024

Multi-speed4

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A023

Multi-speed3

0.00, starting frequency-maximum frequency(Hz)

0.00

 

frequency

 

 

 

 

 

 

 

A025

Multi-speed5

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A026

Multi-speed6

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A027

Multi-speed7

0.00, starting frequency-maximum frequency(Hz)

0.00

 

speed,jogging

 

A028

Multi-speed8

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

A032

Multi-speed12

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A029

Multi-speed9

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A030

Multi-speed10

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A031

Multi-speed11

0.00, starting frequency-maximum frequency(Hz)

0.00

 

Multistage

 

 

 

 

 

 

 

A033

Multi-speed13

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

 

 

 

A034

Multi-speed14

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A035

Multi-speed15

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A038

Jogging frequency

0.00, starting frequency-9.99(Hz)

1.00

 

 

 

 

 

00(free-run on JG stop / invalid on running) / 01(stop decelerating on

 

 

 

 

 

 

JG stop / invalid on running) / 02(DC braking on JG stop/invalid on

 

 

 

 

A039

Jogging selection

running) / 03(free-run on JG stop/valid on running[JG after stop

00

 

 

 

 

 

decelerating]) / 04 (stop decelerating on JG stop/valid on running) /

 

 

 

 

 

 

05 (DC braking on JG stop/valid on operating)

 

 

 

 

A041

Torque boost selection

00 (manual torque boost) / 01 (automatic torque boost)

00

 

 

 

A241

Torque boost selection, 2nd

00 (manual torque boost) / 01 (automatic torque boost)

00

 

 

 

motor

 

characteristic

 

 

 

 

 

 

A042

Manual torque boost point, 2nd

0.0-20.0(%)

1.0

 

 

 

Manual torque boost

 

 

 

A242

Manual torque boost, 2nd motor

0.0-20.0(%)

1.0

 

 

 

A043

Manual torque boost point

0.0-50.0(%)

5.0

 

V/f

 

A243

motor

0.0-50.0(%)

5.0

 

 

 

 

 

 

 

 

A044

1s t control

00/(VC)/01(VP1.7power)/02(free V/f setting)

00

 

 

 

A244

2nd control

00/(VC)/01(VP1.7power)/02(free V/f setting)

00

 

 

 

A045

Output voltage gain

20. - 100. (%)

100.

 

 

 

A051

DC braking selection

00(invalid)/01(valid)

00

 

 

 

A052

DC braking frequency

0.00-60.00(Hz)

0.50

 

braking

 

A053

DC braking wait time

0.0 - 5.0(s)

0.0

 

 

 

A054

DC braking power

0. - 70. (%)

0.

 

current

 

A055

DC braking time

0.0 - 60.0(s)

0.0

 

 

A056

DC braking edge/level

00(edge action)/01(level action)

01

 

 

 

 

 

 

selection

 

 

 

 

 

 

 

Direct

 

A057

DC braking power

0. - 70. (%)

0.

 

 

(starting time)

 

 

 

 

 

 

 

 

 

 

 

 

A058

DC braking time

0.00-60.0(s)

0.0

 

 

 

(starting time)

 

 

 

 

 

 

 

 

 

A059

DC carrier frequency

0.5-12(kHz) Derating <0.5-8(kHz)>

3.0

 

(Note) < > indicate the setting range of 90 to 132kW

1- 11

Image 14
Contents Hitachi Inverter Revision History Table Inverter specification Investigation of the inverter Inverter specification 1 SJ300Function Mode Code 2nd motor Signal output mode Others Allowable motor selection 20-75.0kW 160kW User 2 L300P FE/-FU/-FR PID Terminal Meter C083 O2 adjustment 9999./1000-655310000-65530 U006 User6 selection Trouble Shooting Inverter trip contents, remedy, adviceIgbt Device- Net option board SJ-DN Option error Feed-back board SJ-FBDigital-input option board SJ-DG Check of the trip monitor contents Check of the warning monitor contents Return to an initialization setup Factory-shipment state Debug Mode Monitor modeFunction mode USAInitial cofiguration completion check procedure Setup of an inverterSetting procedure Model selection code C198 Code SJ300 L300P Control power supply Control signalMaintenance and Inspection Daily and annual maintenance Megger test How to check inverter & converter portion Parts replacement How to remove cooling fan for steel case How to fix DC bus capacitors for mold case Unit replacement English Internal block diagram SJ300-004-007LF Circuit Diagram SJ300-015 055LF Circuit Diagram SJ300-075-110LF , L300P-110-150LFR Circuit Diagram SJ300-150 220LF , L300P-185 300LFR Circuit Diagram SJ300-300LF, L300P-370LFR Circuit Diagram SJ300-370-450LF, L300P-450-550LFR Circuit Diagram SJ300-550LF,L300P-750LFR Circuit Diagram SJ300-007HF Circuit Diagram SJ300-015-055HF Circuit Diagram SJ300-075-110HF , L300P-110-150HFR Circuit Diagram SJ300-150 220HF , L300P-185 300HFR Circuit Diagram SJ300-300HF , L300P-370HFR Circuit Diagram SJ300-370- 550HF,L300P-450-750HFR Circuit Diagram DM Board SJ300-750-1320HF , L300P-900-1320HFR Circuit Diagram Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page SJ300/L300P Series Spare Parts List SJ3 CT PCB DM PCB NGMB25