2. TROUBLE SHOOTING
2.1 Inverter trip contents, remedy, advice
Trip
contents
Digital operator display
Remedy, advice
|
|
|
| It’s | one of | INV | failure | by locked | While | constant | Load changed rapidly. | |||||
|
|
|
| motor, | fast | ACC/DEC because big | ||||||||||
|
|
|
| Short circuit or earth contact (ground | ||||||||||||
|
|
|
| current will be flown. |
|
|
|
|
| |||||||
|
|
|
|
|
| speed |
|
| fault) in the motor or the motor cable. | |||||||
|
|
|
| By over current detection, INV will |
|
| ||||||||||
|
|
|
|
|
|
| ||||||||||
|
|
|
| shut the output by the hardware. |
|
|
|
| ||||||||
|
|
|
| This detection will be done by AC | While |
|
| If fast deceleration is happening | ||||||||
Over | current | detection | at | CT. |
|
|
|
|
|
|
| deceleration |
| preset Decel time longer | ||
Over current will be detected about |
| If fast acceleration is happening | ||||||||||||||
output stage |
|
|
|
|
| |||||||||||
|
| 200% of rated level on SJ300. |
| While |
|
| preset Accel time longer | |||||||||
|
|
|
|
|
|
| ||||||||||
|
|
|
| Over current will be detected about | acceleration |
| Any motor locked, check the wires | |||||||||
|
|
|
| 150% of rated level on L300P. |
|
| High preset torque boost, reduce the | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| value | |
|
|
|
|
|
|
|
|
|
|
|
| others |
|
| Is the preset DC injection brake level | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| high | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Any CT malfunction, any noise | |
|
|
|
| INV is monitoring the output current, if the connected |
| |||||||||||
|
|
|
| motor | was overload conditions, | INV will detect | the |
| ||||||||
|
|
|
| overload, if the level was exceeded preset level, INV |
| |||||||||||
|
|
|
| will shut the output. |
|
|
|
|
|
| ||||||
|
|
|
| Too heavy load | ||||||||||||
Over | load | detection | at | the output freq. If the freq. Is less than 5Hz, it has more | Thermal level proper ? | |||||||||||
chance to have the trip. |
|
|
|
|
| Perform above adjustment referring | ||||||||||
output stage(with motor) |
|
|
|
|
|
| ||||||||||
| Over current will be detected about 200% of rated level | to d104, to reduce the electronic | ||||||||||||||
|
|
|
| on SJ300. |
|
|
|
|
|
|
|
| thermal level. | |||
|
|
|
| If the load has big inertia moment, while ACC, there is a |
| |||||||||||
|
|
|
| possibility to disturb the ACC by the detection. |
|
|
| |||||||||
|
|
|
| In this case, adjust torque boost if v/f control is |
| |||||||||||
|
|
|
| selected. |
|
|
|
|
|
|
|
|
| |||
|
|
|
| This | detection | is | over | voltage | detection, | but | the | Any fast decel | ||||
|
|
|
| condition is different from the normal over voltage trip. | ||||||||||||
Over | voltage detection | Busy running cycle | ||||||||||||||
The | difference | is | below. If the | preset BRD %ED | ||||||||||||
Preset BRD%ED proper ? low ? | ||||||||||||||||
after BRD %ED was run | level(d090) was run out, BRD circuit can not work and if | |||||||||||||||
Perform above adjustment referring | ||||||||||||||||
out |
|
|
| DC bus voltage will detect the over voltage level, INV | to d103, to reduce the BRD usage | |||||||||||
|
|
| will shut the output. |
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ratio. | |
|
|
|
| If DC bus voltage is exceeded specific level by | Any fast decel | |||||||||||
|
|
|
| generating energy from the connected motor, high | Earth contact (ground fault) in the | |||||||||||
Over voltage detection (DC | incoming AC voltage, INV will shut the output. |
|
| motor or the motor cable. | ||||||||||||
The DC bus voltage level is |
|
|
|
| Any back energy from the load | |||||||||||
bus voltage) |
|
|
|
|
|
| ||||||||||
|
| About 400VDC (200V class) |
|
|
|
| Perform above adjustment referring | |||||||||
|
|
|
| About 800VDC (400V class) |
|
|
|
| to d102, so that the DC bus voltage | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| does not exceed the trip level. | |
|
|
|
| INV uses EEPROM to preset parameters, if the |
| |||||||||||
|
|
|
| EEPROM | was | affected | by external | noise, | abnormal | Any big noise near the INV | ||||||
EEPROM (contradiction) |
| heat, micro processor will detect the contradiction such | ||||||||||||||
| Ambient temp. is too high. | |||||||||||||||
|
|
|
| as sum check , INV will shut the output. |
|
|
| |||||||||
|
|
|
| If DC bus voltage is low, INV can’t work properly | Any incoming AC V drop | |||||||||||
Under | voltage(DC bus | especially control circuit, in this case, | INV will shut the | Sufficient power capacity | ||||||||||||
output. |
|
|
|
|
|
|
|
|
| Any thyristor failure | ||||||
voltage) |
|
| The DC bus voltage level is |
|
|
|
| Perform above adjustment referring | ||||||||
|
| About 200VDC or less(200V class) |
|
|
|
| to d102, so that the DC bus voltage | |||||||||
|
|
|
|
|
|
|
| |||||||||
|
|
|
| About 400VDC or less(400V class) |
|
|
|
| does not exceed the trip level. | |||||||
|
|
|
| INV uses CT to detect motor current, if the CT outputs |
| |||||||||||
CT offset |
|
| unusual offset level while INV stop, INV will shut the | Any high offset signal of the CT | ||||||||||||
|
| output. |
|
|
|
|
|
|
|
|
|
The voltage level is about 0.6V or more.
CPU(micro processor mis- | If built in Micro processor works improper, if it detects | Any big noise near the INV |
| |||||
failure, INV will shut the output. |
| |||||||
operation) |
|
| Micro processor failure |
| ||||
|
|
|
| |||||
|
| If the intelligent terminal detects the input signal from |
|
|
|
| ||
External(customer’s |
|
|
|
|
| |||
| external devices, INV will shut the output. This | Check | the | configuration, | signal, | |||
selection) |
|
| function/trip is customer ’s selection. If EXT function is | wiring, conditions |
| |||
|
| not selected, there is no chance to have the trip. |
|
|
|
| ||
|
|
|
|
|
|
| ||
USP(US version default or | If INV is ready to start at power on, INV will shut the |
|
|
|
| |||
output. This function/trip is customer’s selection. If USP | Check the configuration,signal, wiring, | |||||||
customer’s selection) | function is not selected, there is no chance to have the | conditions |
|
| ||||
trip. |
|
|
|
| ||||
|
|
|
|
|
|
| ||
Ground default at power on | Only at power on, INV will detect ground fault between | Earth | contact | (ground fault) | in the | |||
INV and the connected motor, INV will shut the output. If | ||||||||
motor or the motor cable. , | IGBT | |||||||
at output stage |
| the motor remaining voltage exists, this detection | ||||||
| failure |
|
|
| ||||
|
|
| doesn’t work. |
|
|
|
| |
|
|
| If DC bus voltage is continuously exceeding specific | Any high incoming voltage | except | |||
Incoming | over | voltage | level more than 30 sec, INV will shut the output. | |||||
The DC bus voltage level is | deceleration |
|
| |||||
detection |
|
|
|
| ||||
|
| About 380VDC or above (200V class) | implement input ACL |
|
About 760VDC or above (400V class)
2- 1