Hitachi L300P Series service manual Trouble Shooting, Inverter trip contents, remedy, advice

Page 19

2. TROUBLE SHOOTING

2.1 Inverter trip contents, remedy, advice

Trip

contents

Digital operator display

Remedy, advice

 

 

 

 

It’s

one of

INV

failure

by locked

While

constant

Load changed rapidly.

 

 

 

 

motor,

fast

ACC/DEC because big

 

 

 

 

Short circuit or earth contact (ground

 

 

 

 

current will be flown.

 

 

 

 

 

 

 

 

 

 

 

speed

 

 

fault) in the motor or the motor cable.

 

 

 

 

By over current detection, INV will

 

 

 

 

 

 

 

 

 

 

 

 

 

shut the output by the hardware.

 

 

 

 

 

 

 

 

This detection will be done by AC

While

 

 

If fast deceleration is happening

Over

current

detection

at

CT.

 

 

 

 

 

 

 

deceleration

 

preset Decel time longer

Over current will be detected about

 

If fast acceleration is happening

output stage

 

 

 

 

 

 

 

200% of rated level on SJ300.

 

While

 

 

preset Accel time longer

 

 

 

 

 

 

 

 

 

 

 

Over current will be detected about

acceleration

 

Any motor locked, check the wires

 

 

 

 

150% of rated level on L300P.

 

 

High preset torque boost, reduce the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

others

 

 

Is the preset DC injection brake level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

high

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Any CT malfunction, any noise

 

 

 

 

INV is monitoring the output current, if the connected

 

 

 

 

 

motor

was overload conditions,

INV will detect

the

 

 

 

 

 

overload, if the level was exceeded preset level, INV

 

 

 

 

 

will shut the output.

 

 

 

 

 

 

 

 

 

 

(E-thermal characteristic has deleting characteristic by

Too heavy load

Over

load

detection

at

the output freq. If the freq. Is less than 5Hz, it has more

Thermal level proper ?

chance to have the trip.

 

 

 

 

 

Perform above adjustment referring

output stage(with motor)

 

 

 

 

 

 

 

Over current will be detected about 200% of rated level

to d104, to reduce the electronic

 

 

 

 

on SJ300.

 

 

 

 

 

 

 

 

thermal level.

 

 

 

 

If the load has big inertia moment, while ACC, there is a

 

 

 

 

 

possibility to disturb the ACC by the detection.

 

 

 

 

 

 

 

In this case, adjust torque boost if v/f control is

 

 

 

 

 

selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

This

detection

is

over

voltage

detection,

but

the

Any fast decel

 

 

 

 

condition is different from the normal over voltage trip.

Over

voltage detection

Busy running cycle

The

difference

is

below. If the

preset BRD %ED

Preset BRD%ED proper ? low ?

after BRD %ED was run

level(d090) was run out, BRD circuit can not work and if

Perform above adjustment referring

out

 

 

 

DC bus voltage will detect the over voltage level, INV

to d103, to reduce the BRD usage

 

 

 

will shut the output.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ratio.

 

 

 

 

If DC bus voltage is exceeded specific level by

Any fast decel

 

 

 

 

generating energy from the connected motor, high

Earth contact (ground fault) in the

Over voltage detection (DC

incoming AC voltage, INV will shut the output.

 

 

motor or the motor cable.

The DC bus voltage level is

 

 

 

 

Any back energy from the load

bus voltage)

 

 

 

 

 

 

 

 

About 400VDC (200V class)

 

 

 

 

Perform above adjustment referring

 

 

 

 

About 800VDC (400V class)

 

 

 

 

to d102, so that the DC bus voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

does not exceed the trip level.

 

 

 

 

INV uses EEPROM to preset parameters, if the

 

 

 

 

 

EEPROM

was

affected

by external

noise,

abnormal

Any big noise near the INV

EEPROM (contradiction)

 

heat, micro processor will detect the contradiction such

 

Ambient temp. is too high.

 

 

 

 

as sum check , INV will shut the output.

 

 

 

 

 

 

 

If DC bus voltage is low, INV can’t work properly

Any incoming AC V drop

Under

voltage(DC bus

especially control circuit, in this case,

INV will shut the

Sufficient power capacity

output.

 

 

 

 

 

 

 

 

 

Any thyristor failure

voltage)

 

 

The DC bus voltage level is

 

 

 

 

Perform above adjustment referring

 

 

About 200VDC or less(200V class)

 

 

 

 

to d102, so that the DC bus voltage

 

 

 

 

 

 

 

 

 

 

 

 

About 400VDC or less(400V class)

 

 

 

 

does not exceed the trip level.

 

 

 

 

INV uses CT to detect motor current, if the CT outputs

 

CT offset

 

 

unusual offset level while INV stop, INV will shut the

Any high offset signal of the CT

 

 

output.

 

 

 

 

 

 

 

 

 

The voltage level is about 0.6V or more.

CPU(micro processor mis-

If built in Micro processor works improper, if it detects

Any big noise near the INV

 

failure, INV will shut the output.

 

operation)

 

 

Micro processor failure

 

 

 

 

 

 

 

If the intelligent terminal detects the input signal from

 

 

 

 

External(customer’s

 

 

 

 

 

 

external devices, INV will shut the output. This

Check

the

configuration,

signal,

selection)

 

 

function/trip is customer ’s selection. If EXT function is

wiring, conditions

 

 

 

not selected, there is no chance to have the trip.

 

 

 

 

 

 

 

 

 

 

 

USP(US version default or

If INV is ready to start at power on, INV will shut the

 

 

 

 

output. This function/trip is customer’s selection. If USP

Check the configuration,signal, wiring,

customer’s selection)

function is not selected, there is no chance to have the

conditions

 

 

trip.

 

 

 

 

 

 

 

 

 

 

 

Ground default at power on

Only at power on, INV will detect ground fault between

Earth

contact

(ground fault)

in the

INV and the connected motor, INV will shut the output. If

motor or the motor cable. ,

IGBT

at output stage

 

the motor remaining voltage exists, this detection

 

failure

 

 

 

 

 

 

doesn’t work.

 

 

 

 

 

 

 

If DC bus voltage is continuously exceeding specific

Any high incoming voltage

except

Incoming

over

voltage

level more than 30 sec, INV will shut the output.

The DC bus voltage level is

deceleration

 

 

detection

 

 

 

 

 

 

About 380VDC or above (200V class)

implement input ACL

 

About 760VDC or above (400V class)

2- 1

Image 19
Contents Hitachi Inverter Revision History Table Inverter specification Investigation of the inverter 1 SJ300 Inverter specificationFunction Mode Code 2nd motor Signal output mode Others Allowable motor selection 20-75.0kW 160kW User 2 L300P FE/-FU/-FR PID Terminal Meter C083 O2 adjustment 9999./1000-655310000-65530 U006 User6 selection Inverter trip contents, remedy, advice Trouble ShootingIgbt Digital-input option board SJ-DG Option error Feed-back board SJ-FBDevice- Net option board SJ-DN Check of the trip monitor contents Check of the warning monitor contents Return to an initialization setup Factory-shipment state Monitor mode Debug ModeUSA Function modeSetting procedure Setup of an inverterInitial cofiguration completion check procedure Model selection code C198 Code SJ300 L300P Control signal Control power supplyMaintenance and Inspection Daily and annual maintenance Megger test How to check inverter & converter portion Parts replacement How to remove cooling fan for steel case How to fix DC bus capacitors for mold case Unit replacement English Internal block diagram SJ300-004-007LF Circuit Diagram SJ300-015 055LF Circuit Diagram SJ300-075-110LF , L300P-110-150LFR Circuit Diagram SJ300-150 220LF , L300P-185 300LFR Circuit Diagram SJ300-300LF, L300P-370LFR Circuit Diagram SJ300-370-450LF, L300P-450-550LFR Circuit Diagram SJ300-550LF,L300P-750LFR Circuit Diagram SJ300-007HF Circuit Diagram SJ300-015-055HF Circuit Diagram SJ300-075-110HF , L300P-110-150HFR Circuit Diagram SJ300-150 220HF , L300P-185 300HFR Circuit Diagram SJ300-300HF , L300P-370HFR Circuit Diagram SJ300-370- 550HF,L300P-450-750HFR Circuit Diagram DM Board SJ300-750-1320HF , L300P-900-1320HFR Circuit Diagram Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page SJ300/L300P Series Spare Parts List SJ3 CT PCB DM PCB NGMB25