Function Mode
| Code | Function name |
| L300P Setting range | Initial data | N o t e | |||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
| C070 | Data command |
|
|
| 02(operator)/03(RS485)/04(option1)/05(option2) | 02 |
| |
ation | C071 | Communicating |
|
|
| 04 |
| ||
| transmission speed |
|
| 05(9600bps)/06(19200bps) |
| ||||
|
|
|
|
|
| ||||
Communic function | C072 | Communication code |
| 1. - 32. | 1. |
| |||
C073 | Communication bit |
|
| 7(7bit)/8(8bit) | 7 |
| |||
|
|
|
| ||||||
| C074 | Communication parity |
| 00(no parity name)/01(even parity)/02(odd parity) | 00 |
| |||
| C075 | Communication stop bit | 1(bit)/2(bit) | 1 |
| ||||
| C078 | Communication waiting |
| 0. |
| ||||
| time |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
setting | C082 | OI adjustment |
|
|
| Setting on |
| ||
|
|
| forwarding |
| |||||
| C081 | O adjustment |
|
|
| forwarding |
| ||
|
|
|
|
|
|
|
| Setting on |
|
|
|
|
|
|
|
|
|
|
|
meter | C083 | O2 adjustment |
|
|
|
| Setting on |
| |
|
|
| forwarding |
| |||||
|
|
|
|
|
|
|
| ||
C085 | Thermistor adjustment |
| 0.0 - 1000. | 105.0 |
| ||||
Analog | C088 | AMI offset adjustment |
| 0. - 20.0( mA) | 4.0 |
| |||
| C086 | AM offset adjustment |
| 0.0 - 10.0(V) | 0.0 |
| |||
| C087 | AMI adjustment |
|
|
| 0. - 255 . | 80 |
| |
|
|
|
|
|
| ||||
| b034 | RUN time/Power ON time | 0. |
| |||||
| level |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
| b035 | Operation direction restrict | 00(Reverse is valid)/01(Only forward)/02(Only reverse) | 00 |
| ||||
| b036 | Start reduced voltage |
| 00(Start reduced voltage time small) | 06 |
| |||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
| b037 | Display selection |
|
| 00(all display)/01(each function display)/ | 00 |
| ||
|
|
| 02(User setting / main setting) |
| |||||
|
|
|
|
|
|
|
|
| |
| b080 | AM adjustment |
|
|
| 0. - 255. | 180 |
| |
| b081 | FM adjustment |
|
|
| 0. - 255. | 60 |
| |
| b082 | Start frequency adjustment | 0.50 |
| |||||
| b083 | Carrier frequency setting | 3.0 |
| |||||
| b084 | Initialize mode |
|
|
| 00(Trip history clear)/01(Data initialization)/ | 00 |
| |
|
|
|
| 02(Trip history clear + data initialization) |
| ||||
|
|
|
|
|
|
|
|
| |
| b085 | Country code for |
|
| 00(Interior)/01(EC)/02(USA) | 01/02/00 |
| ||
| initialization |
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
| b086 | Frequency scalar |
|
| 1.0 |
| |||
| conversion factor |
|
|
| |||||
|
|
|
|
|
|
| |||
| b087 | STOP key enable |
|
| 00(valid)/01(invalid) | 00 |
| ||
| b088 | Resume on FRS |
|
| 00(0Hz start)/01(Start | 00 |
| ||
| cancellation mode |
|
|
| |||||
|
|
|
|
|
|
| |||
| b090 | BRD usage ratio |
|
| 0.0 |
| |||
| b091 | Stop mode selection |
| 00(deceleration | 00 |
| |||
| b092 | Cooling fan control |
|
| 00(Always ON)/01(ON during run, After power ON, then for 5 minutes | 00 |
| ||
|
|
| on stop is implied.) |
| |||||
|
|
|
|
|
|
|
|
| |
| b095 | BRD selection |
|
|
| 00(invalid)/01(valid<invalid during stop>)/ | 00 |
| |
|
|
|
| 02(valid<valid during stop>) |
| ||||
|
|
|
|
|
|
|
|
| |
| b096 | BRD ON level |
|
|
| 360/720 |
| ||
| b098 | Thermistor selection |
| 00(invalid)/01(Positive temperature coefficient enable)/ | 00 |
| |||
|
| 02 (NTC enable) |
| ||||||
|
|
|
|
|
|
|
|
| |
| b099 | Thermistor error level |
| 0. – 9999. ( ohm) | 3000. |
| |||
| C061 | Thermal warning level |
| 0. – 100. ( %) | 80 |
| |||
| C091 | Debug mode selection |
| 00(No display)/01(Display) | 00 |
| |||
| C101 | UP/DWN selection |
|
| 00(No frequency data)/01(Keep frequency data) | 00 |
| ||
others | C102 | Reset f frequency matching | 00(Trip cancel during ON)/01(Trip cancel during OFF)/ | 00 |
| ||||
| Reset selection |
|
|
| 02(Valid only during trip<Cancel during ON>) |
| |||
The | C103 | selection |
|
|
| 00(0H z start)/01(Start | 00 |
| |
|
|
|
|
|
|
| |||
C121 | O zero adjustment |
|
| Set on |
| ||||
|
|
| forwarding |
| |||||
|
|
|
|
|
|
|
|
| |
| C122 | OI zero adjustment |
|
| Set on |
| |||
|
|
| forwarding |
| |||||
|
|
|
|
|
|
|
|
| |
| C123 | O2 zero adjustment |
| Set on |
| ||||
|
| forwarding |
| ||||||
|
|
|
|
|
|
|
|
| |
| H003 | 1s t allowable motor |
|
| Set on |
| |||
| selection |
|
|
| forwarding |
| |||
|
|
|
|
|
|
| |||
| H203 | 2nd allowable motor |
|
| Set on |
| |||
| selection |
|
|
| forwarding |
| |||
|
|
|
|
|
|
| |||
| H004 | 1s t motor pole selection | 2/4/6/8(pole) | 4 |
| ||||
| H204 | 2nd motor pole selection | 2/4/6/8(pole) | 4 |
| ||||
| H006 | 1s t stabilized factor |
|
| 0. - 255. | 100. |
| ||
| H206 | 2nd stabilized factor |
|
| 0. - 255. | 100. |
| ||
| P001 | Option1 operation selection | 00(TRP)/01(RUN) | 00 |
| ||||
| on error |
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
| P002 | Option2 operation selection | 00(TRP)/01(RUN) | 00 |
| ||||
| on error |
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
| P031 | Digital | input option | input | 00(operation)/01(option1)/02(option2) | 00 |
| ||
| mode selection(Acc/Dec) |
| |||||||
|
|
|
|
| |||||
| P044 | DeviceNet running order of | 1.00 |
| |||||
| monitoring timer setting |
| |||||||
|
|
|
|
| |||||
| P045 | Setting | in | action | of | 00(trip)/01(trip after deceleration stop)/02(invalid)/ | 0. |
| |
| abnormal communication |
| |||||||
|
|
|
| ||||||
| P046 | Output | assemble | instance | 20,21,100 | 21 |
| ||
| Number setting |
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
| P047 | Input | assemble | instance | 70,71,101 | 71 |
| ||
| Number setting |
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
| P048 | Detect | of idol | mode | for | 00(trip)/01(trip after deceleration stop)/02(invalid)/ | 01 |
| |
| motion setting |
|
|
|
| ||||
|
|
|
|
|
|
| |||
| P049 | Pole setting | of | rotation | 0 |
| |||
| speed |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
(Note) < > indicate the setting range of 90 to 132kW (Note1)
1- 14