Bryant R-22 service manual Refrigeration System, Refrigerant, Compressor Oil

Page 22

Ground Circuit

To determine if a wire has broken or come in direct contact with shell, causing a direct short to ground, follow these steps:

1.Allow crankcase heaters to remain on for several hours before checking motor to ensure windings are not saturated with refrigerant.

2.Using an ohmmeter on R X 10,000 ohm scale or megohmmeter (follow manufacturer’s instructions).

3.Be sure all power is off.

4.Discharge all capacitors.

5.Remove wires from terminals C, S, and R.

6.Place one meter probe on ground or on compressor shell. Make a good metal-to-metal contact. Place other probe on terminals C, S, and R in sequence.

7.Note meter scale.

8.If reading of 0 or low resistance is obtained, motor is grounded. Replace compressor.

Compressor resistance to ground should not be less than 1000 ohms per volt of operating voltage.

Example:

230 volts X 1000 ohms/volt = 230,000 ohms minimum.

Short Circuit

To determine if any wires within windings have broken through their insulation and made contact with other wires, thereby shorting all or part of the winding(s), be sure the following conditions are met.

1.Correct motor winding resistances must be known before testing, either from previous readings or from manufacturer’s specifications.

2.Temperature of windings must be as specified, usually about 70_F.

3.Resistance measuring instrument must have an accuracy within ± 5-10 percent. This requires an accurate ohmmeter such as a Wheatstone bridge or null balance-type instrument.

4.Motor must be dry or free from direct contact with liquid refrigerant.

Make This Critical Test

(Not advisable unless above conditions are met)

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals C, S, and R.

4.Place instrument probes together and determine probe and lead wire resistance.

5.Check resistance readings from C-R, C-S, and R-S.

6.Subtract instrument probe and lead resistance from each reading.

If any reading is within ±20 percent of known resistance, motor is probably normal. Usually a considerable difference in reading is noted if a turn-to-turn short is present.

REFRIGERATION SYSTEM

Refrigerant

!WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal injury or equipment damage.

Puronr refrigerant which has higher pressures than R-22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puronr. If you are unsure consult the equipment manufacturer.

In an air conditioning and heat pump system, refrigerant transfers heat from one replace to another. The condenser is the outdoor coil in the cooling mode and the evaporator is the indoor coil.

In a heat pump, the condenser is the indoor coil in the heating mode and the evaporator is the outdoor coil.

In the typical air conditioning mode, compressed hot gas leaves the compressor and enters the condensing coil. As gas passes through the condenser coil, it rejects heat and condenses into liquid. The liquid leaves condensing unit through liquid line and enters metering device at evaporator coil. As it passes through metering device, it becomes a gas-liquid mixture. As it passes through indoor coil, it absorbs heat and the refrigerant moves to the compressor and is again compressed to hot gas, and cycle repeats.

Compressor Oil

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

The compressor in a Puronr system uses a polyol ester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere. (See Table 4.)

22

Image 22
Contents Table of Contents Application GuidelineAIR Conditioner and Heat Pump Model Number Nomenclature Table of Contents TWO Stage NON-COMMUNICATINGTWO Stage Communicating Serial Number NomenclatureInstallation Guideline Safety ConsiderationsIntroduction Required Field-Installed Accessories for Air Conditioners AccessoriesRequired Field-Installed Accessories for Heat Pumps Accessory Descriptions Base / Mid-Tier / Deluxe 4-sided Baffle Assembly LOW-AMBIENT Cooling GuidelineDeluxe 3-sided Baffle Assembly and Dimensions Long Line Guideline Cabinet AssemblyBasic Cabinet Designs Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Labeling Figure LabelsContactor Aluminum WireElectrical CapacitorCrankcase Heater Time-Delay RelayCycle Protector Pressure Switches Personal Injury HazardDefrost Thermostat Defrost Control BoardIf defrost thermostat is stuck closed Troubleshooting HK32EA001 If outdoor unit will not runDefrost Speedup If defrost thermostat is stuck openCooling Five-Minute Compressor DelayQuiet Shift HeatingCompressor Plug Troubleshooting HK32EA003Fan Motor Low-Voltage TerminalsLocked Rotor Compressor FailuresMechanical Failures Runs, Does Not PumpNoisy Compressor Split Post Grommet part number KA75UG100Electrical Failures Single-Phase MotorsUnit Personal Injury Hazard Refrigerant Refrigeration SystemCompressor Oil Brazing Synthetic Roof Precautionary ProcedureServicing Systems on Roofs With Synthetic Materials Oil ChargingPumpdown Procedure Service Valves and PumpdownPersonal Injury and Unit Damage Hazard Heating Piston AccuRaterr Heat Pumps Only AccuRaterr Components Used in R-22 Heat PumpsReversing Valve Reversing Valve Heating Mode, Solenoid De-EnergizedLiquid Line Filter Drier Install Liquid-line Filter Drier Indoor ACSuction Line Filter Drier Accumulator AccumulatorTXV Operation Install TXVThermostatic Expansion Valve TXV Unit Operation HazardReplacing TXV on Indoor Coil post-2006 Make Piping ConnectionsReplacing TXV on an Indoor Coil pre-2006 Personal Injury and Environmental HazardCoil Removal Refrigeration System RepairLeak Detection Fire HazardCompressor Removal and Replacement System Clean-Up After BurnoutEvacuation Check ChargeDeep Vacuum Method Low Superheat with Normal or Low Suction Pressure Troubleshooting with SuperheatBasic Diagnostics Low Superheat with High Suction PressureHunting Superheat High Superheat with Normal or High Suction PressurePseudo Evaporator Superheat Instructions Puron System Suction Pressure Drop Example22 System Suction Pressure Drop PuronrRefrigerant Pressure Temperature Chart Psig22 Refrigerant Pressure Temperature Relationship PsigPuron Subcooling Chart Liquid Line Temperature F Liq Press Subcooling F PsigPuron Superheat Chart Superheat F Psig22 Subcooling Chart Liquid Line Temperature F PT F Subcooling F Pres Psig22 Superheat Chart Model Plug TWO-STAGEApplication Guidelines Model Plug InformationDefrost General InformationLow Ambient Cooling Airflow Selection for 315AAV/355AAV FurnacesForced Defrost Liquid-Line Solenoid AccessoryDefrost Hold All 286A units must be charged in high stage onlyUtility Interface With Evolution Control One Minute Stage Change Time Delay on 286ANA/187ANA ModelsCooling and Heating Operation Compressor Operation on 286ANA/187ANA ModelsECM Fan Motor Troubleshooting Outdoor Fan Motor OperationMuffler, Accumulator, Reversing Valve RVS Time DelaysThermistors Control BOX Troubleshooting Compressor Voltage Sensing 230V Line Power Disconnect Detection230v Brown-Out Protection Defeated Contactor Shorted DetectionFailed Thermistor Default Operation Unloader Test ProcedureTemperature Thermistors Thermistor Sensor ComparisonTroubleshooting Status CodesEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information Heating Check Chart Procedure All 286B units must be charged in high stage onlyCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Control Box Incoming PowerTroubleshooting 187B & 286B Start Circuit Contactor And CapacitorTroubleshooting HK38EA015 circuit board 286B Models Compressor Thermal Cutout 289B Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner Airflow Selections ECM Furnaces TWO Stage NON-COMMUNICATING 127A/226AOperating Ambient Airflow Selection for FV4C Fan Coils non-communicatingCompressor Operation System Function and Sequence of OperationDefrost Speedup Check Charge Airflow Selections for ECM Furnaces non communicating TWO Stage Communicating 167A/266AIndoor Thermostat Control Options Evolution Controlled Low Ambient Cooling Defrost HoldMajor Components Outdoor Fan Motor Operation Communication and Status Function LightsFor Evolution Control only, Green communications Comm Light 2230V Brown-Out Protection Defeated No 230V at Compressor Contactor Thermistor CurveOutdoor Coil Thermistor OCT Attachment 167A / 266A Troubleshooting Status CodesCare and Maintenance Final Check-Out Puronr R-410A Refrigerant Quick Reference GuideAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle TWO-STAGE 286A/288A 180A/187A Index of TablesDescription Table # TWO-STAGE 286B/288B 180B/187BCatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.