Bryant Expert Guidelines on Unloader Test Procedures and Thermistor Functions for Models

Page 53

Unloader Test Procedure

The unloader is the compressor internal mechanism, controlled by the DC solenoid, that modulates between high and low stage. If it is suspected that the unloader is not working, the following methods may be used to verify operation.

1.Operate the system and measure compressor amperage. Cycle the unloader on and off at 30 second plus intervals at the UI (from low to high stage and back to low stage). Wait 5 seconds after staging to high before taking a reading. The compressor amperage should go up or down at least 20 percent.

2.If the expected result is not achieved, remove the solenoid plug from the compressor and with the unit running and the UI calling for high stage, test the voltage output at the plug with a DC voltmeter. The reading should be 4 to 18 volts.

3.If the correct DC voltage is at the control circuit molded plug, measure the compressor unloader coil resistance. The resistance should be 32 to 60 ohms depending on compressor temperature. If the coil resistance is infinity, much lower than 32 ohms, or is grounded, the compressor must be replaced.

Temperature Thermistors

Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Thermistors are used to sense outdoor air (OAT) and coil temperature (OCT). Refer to Fig. 34 for resistance values versus temperature.

If the outdoor air or coil thermistor should fail, the control will flash the appropriate fault code. (See Table 17.)

IMPORTANT: The outdoor air thermistor and coil thermistor should be factory mounted in the final locations. Check to ensure thermistors are mounted properly per Fig. 38 and Fig. 39.

OAT Thermistor must be locked in place with spherical nib end facing to- wards the front of the control box

Fig. 38 – Outdoor Air Thermistor (OAT) Attachment

Thermistor Sensor Comparison

The control continuously monitors and compares the outdoor air temperature sensor and outdoor coil temperature sensor to ensure proper operating conditions. The comparison is:

SIn cooling if the outdoor air sensor indicates 10_F warmer than the coil sensor (or) the outdoor air sensor indicates 20_F cooler than the coil sensor, the sensors are out of range.

SIn heating if the outdoor air sensor indicates 35_F warmer than the coil sensor (or) the outdoor air sensor indicates 10_F cooler than the coil sensor, the sensors are out of range.

If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 17.

The thermistor comparison is not performed during low ambient cooling or defrost operation.

Failed Thermistor Default Operation

Factory defaults have been provided in the event of failure of outdoor air thermistor (OAT) and/or outdoor coil thermistor (OCT).

If the OAT sensor should fail, low ambient cooling will not be allowed and the one-minute outdoor fan off delay will not occur. Defrost will be initiated based on coil temperature and time.

If the OCT sensor should fail, low ambient cooling will not be allowed. Defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.

If there is a thermistor out of range error, defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.

Count the number of short and long flashes to determine the appropriate flash code. Table 17 gives possible causes and actions related to each error.

OCT Thermistor must be secured tight on stub tube.

Fig. 39 – Outdoor Coil Thermistor (OCT) Attachment

Table 16—Two-Stage Compressor Resistances

(Winding Resistance at 70_F±20_)

Winding

286ANA024

286ANA036

286ANA048

286ANA060

Start (S-C)

2.74

1.98

1.55

0.74

Run (R-C)

0.80

0.75

0.48

0.36

 

 

 

 

 

Winding

226ANA024

226ANA036

226ANA048

226ANA060

288ANA024

288ANA036

288ANA048

288ANA060

 

 

 

 

 

 

Start (S-C)

1.40

1.29

1.52

0.60

 

 

 

 

 

Run (R-C)

1.32

0.89

0.64

0.49

 

 

 

 

 

53

Image 53
Contents Application Guideline Table of ContentsTWO Stage Communicating Table of Contents TWO Stage NON-COMMUNICATINGAIR Conditioner and Heat Pump Model Number Nomenclature Serial Number NomenclatureIntroduction Safety ConsiderationsInstallation Guideline Required Field-Installed Accessories for Heat Pumps AccessoriesRequired Field-Installed Accessories for Air Conditioners Accessory Descriptions LOW-AMBIENT Cooling Guideline Base / Mid-Tier / Deluxe 4-sided Baffle AssemblyDeluxe 3-sided Baffle Assembly and Dimensions Basic Cabinet Designs Cabinet AssemblyLong Line Guideline Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Figure Labels LabelingElectrical Aluminum WireContactor CapacitorCycle Protector Time-Delay RelayCrankcase Heater Personal Injury Hazard Pressure SwitchesDefrost Control Board Defrost ThermostatDefrost Speedup Troubleshooting HK32EA001 If outdoor unit will not runIf defrost thermostat is stuck closed If defrost thermostat is stuck openQuiet Shift Five-Minute Compressor DelayCooling HeatingFan Motor Troubleshooting HK32EA003Compressor Plug Low-Voltage TerminalsMechanical Failures Compressor FailuresLocked Rotor Runs, Does Not PumpSplit Post Grommet part number KA75UG100 Noisy CompressorUnit Personal Injury Hazard Single-Phase MotorsElectrical Failures Compressor Oil Refrigeration SystemRefrigerant Servicing Systems on Roofs With Synthetic Materials Synthetic Roof Precautionary ProcedureBrazing Oil ChargingPersonal Injury and Unit Damage Hazard Service Valves and PumpdownPumpdown Procedure AccuRaterr Components Used in R-22 Heat Pumps Heating Piston AccuRaterr Heat Pumps OnlyReversing Valve Heating Mode, Solenoid De-Energized Reversing ValveSuction Line Filter Drier Install Liquid-line Filter Drier Indoor ACLiquid Line Filter Drier Accumulator AccumulatorThermostatic Expansion Valve TXV Install TXVTXV Operation Unit Operation HazardReplacing TXV on an Indoor Coil pre-2006 Make Piping ConnectionsReplacing TXV on Indoor Coil post-2006 Personal Injury and Environmental HazardLeak Detection Refrigeration System RepairCoil Removal Fire HazardSystem Clean-Up After Burnout Compressor Removal and ReplacementDeep Vacuum Method Check ChargeEvacuation Basic Diagnostics Troubleshooting with SuperheatLow Superheat with Normal or Low Suction Pressure Low Superheat with High Suction PressurePseudo Evaporator Superheat Instructions High Superheat with Normal or High Suction PressureHunting Superheat Example Puron System Suction Pressure Drop22 System Suction Pressure Drop Psig PuronrRefrigerant Pressure Temperature ChartPsig 22 Refrigerant Pressure Temperature RelationshipLiquid Line Temperature F Liq Press Subcooling F Psig Puron Subcooling ChartSuperheat F Psig Puron Superheat ChartLiquid Line Temperature F PT F Subcooling F Pres Psig 22 Subcooling Chart22 Superheat Chart Application Guidelines TWO-STAGEModel Plug Model Plug InformationLow Ambient Cooling General InformationDefrost Airflow Selection for 315AAV/355AAV FurnacesDefrost Hold Liquid-Line Solenoid AccessoryForced Defrost All 286A units must be charged in high stage onlyCooling and Heating Operation One Minute Stage Change Time Delay on 286ANA/187ANA ModelsUtility Interface With Evolution Control Compressor Operation on 286ANA/187ANA ModelsOutdoor Fan Motor Operation ECM Fan Motor TroubleshootingThermistors Time DelaysMuffler, Accumulator, Reversing Valve RVS Control BOX Troubleshooting 230v Brown-Out Protection Defeated 230V Line Power Disconnect DetectionCompressor Voltage Sensing Contactor Shorted DetectionTemperature Thermistors Unloader Test ProcedureFailed Thermistor Default Operation Thermistor Sensor ComparisonStatus Codes TroubleshootingEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information All 286B units must be charged in high stage only Heating Check Chart ProcedureCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Troubleshooting 187B & 286B Start Circuit Incoming PowerControl Box Contactor And CapacitorTroubleshooting HK38EA015 circuit board 289B Compressor Thermal Cutout 286B Models Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner Operating Ambient TWO Stage NON-COMMUNICATING 127A/226AAirflow Selections ECM Furnaces Airflow Selection for FV4C Fan Coils non-communicatingDefrost Speedup System Function and Sequence of OperationCompressor Operation Check Charge Indoor Thermostat Control Options TWO Stage Communicating 167A/266AAirflow Selections for ECM Furnaces non communicating Defrost Hold Evolution Controlled Low Ambient CoolingMajor Components For Evolution Control only, Green communications Comm Light Communication and Status Function LightsOutdoor Fan Motor Operation 2230V Brown-Out Protection Defeated Thermistor Curve No 230V at Compressor ContactorOutdoor Coil Thermistor OCT Attachment Status Codes 167A / 266A TroubleshootingCare and Maintenance Puronr R-410A Refrigerant Quick Reference Guide Final Check-OutAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle Description Table # Index of TablesTWO-STAGE 286A/288A 180A/187A TWO-STAGE 286B/288B 180B/187BCatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.