Bryant R-22 service manual Crankcase Heater, Cycle Protector, Time-Delay Relay

Page 13

Use following formula to calculate capacitance:

Capacitance (mfd)= (2650 X amps)/volts

3.Remove any capacitor that shows signs of bulging, dents, or leaking. Do not apply power to a defective capacitor as it may explode.

Sometimes under adverse conditions, a standard run capacitor in a system is inadequate to start compressor. In these instances, a start assist device is used to provide an extra starting boost to compressor motor. This device is called a positive temperature coefficient (PTC) or start thermistor. It is a resistor wired in parallel with the run capacitor. As current flows through the PTC at start-up, it heats up. As PTC heats up, its resistance increases greatly until it effectively lowers the current through itself to an extremely low value. This, in effect, removes the PTC from the circuit.

After system shutdown, resistor cools and resistance value returns to normal until next time system starts. Thermistor device is adequate for most conditions, however, in systems where off cycle is short, device cannot fully cool and becomes less effective as a start device. It is an easy device to troubleshoot. Shut off all power to system.

Check thermistor with ohmmeter as described below. Shut off all

With high-voltage power off, attach voltmeter leads across T1 and T3, and set thermostat so that Y terminal is energized. Make sure all protective devices in series with Y terminal are closed. Voltmeter should read 24v across T1 and T3. With 24v still applied, move voltmeter leads to T2 and T3. After 5 ± 2 minutes, voltmeter should read 24v, indicating control is functioning normally. If no time delay is encountered or device never times out, change control.

Crankcase Heater

Crankcase heater is a device for keeping compressor oil warm. By keeping oil warm, refrigerant does not migrate to and condense in compressor shell when the compressor is off. This prevents flooded starts which can damage compressor.

On units that have a single-pole contactor, the crankcase heater is wired in parallel with contactor contacts and in series with compressor. (See Fig. 7.) When contacts open, a circuit is completed from line side of contactor, through crankcase heater, through run windings of compressor, and to other side of line. When contacts are closed, there is no circuit through crankcase heater because both leads are connected to same side of line. This allows heater to operate when system is not calling for cooling. The heater does not operate when system is calling for cooling.

power to unit. Remove PTC from unit. Wait at least 10 minutes for PTC to cool to ambient temperature.

Measure resistance of PTC with ohmmeter.

The cold resistance (RT) of any PTC device should be approximately 100-180 percent of device ohm rating.

12.5-ohm PTC = 12.5-22.5 ohm resistance (beige color)

If PTC resistance is appreciably less than rating or more than 200

CRANKCASE HTR

BLKBLK

11

TEMP SWITCH

BLKBLK

21

A97586

percent higher than rating, device is defective.

A94006

Fig. 6 – Capacitors

Cycle Protector

Bryant thermostats have anti-cycle protection built in to protect the compressor. Should a non-Bryant stat be utilized, it is recommended to add a cycle protector to the system. Solid-state cycle protector protects unit compressor by preventing short cycling. After a system shutdown, cycle protector provides for a 5

±2-minute delay before compressor restarts. On normal start-up, a

5-minute delay occurs before thermostat closes. After thermostat closes, cycle protector device provides a 3-sec delay.

Cycle protector is simple to troubleshoot. Only a voltmeter capable of reading 24v is needed. Device is in control circuit, therefore, troubleshooting is safe with control power (24v) on and high-voltage power off.

Fig. 7 – Wiring for Single-Pole Contactor

The crankcase heater is powered by high-voltage power of unit. Use extreme caution troubleshooting this device with power on. The easiest method of troubleshooting is to apply voltmeter across crankcase heater leads to see if heater has power. Do not touch heater. Carefully feel area around crankcase heater. If warm, crankcase heater is probably functioning. Do not rely on this method as absolute evidence heater is functioning. If compressor has been running, the area will still be warm.

With power off and heater leads disconnected, check across leads with ohmmeter. Do not look for a specific resistance reading. Check for resistance or an open circuit. Change heater if an open circuit is detected.

Time-Delay Relay

The TDR is a solid-state control, recycle delay timer which keeps indoor blower operating for 90 sec after thermostat is satisfied. This delay enables blower to remove residual cooling in coil after compression shutdown, thereby improving efficiency of system. The sequence of operation is that on closure of wall thermostat and at end of a fixed on delay of 1 sec, fan relay is energized. When thermostat is satisfied, an off delay is initiated. When fixed delay of 90 ± 20 sec is completed, fan relay is de-energized and fan motor stops. If wall thermostat closes during this delay, TDR is reset and fan relay remains energized. TDR is a 24v device that operates within a range of 15v to 30v and draws about 0.5 amps. If the blower runs continuously instead of cycling off when the fan switch is set to AUTO, the TDR is probably defective and must be replaced.

13

Image 13
Contents Application Guideline Table of ContentsTWO Stage Communicating Table of Contents TWO Stage NON-COMMUNICATINGAIR Conditioner and Heat Pump Model Number Nomenclature Serial Number NomenclatureInstallation Guideline Safety ConsiderationsIntroduction Required Field-Installed Accessories for Air Conditioners AccessoriesRequired Field-Installed Accessories for Heat Pumps Accessory Descriptions LOW-AMBIENT Cooling Guideline Base / Mid-Tier / Deluxe 4-sided Baffle AssemblyDeluxe 3-sided Baffle Assembly and Dimensions Long Line Guideline Cabinet AssemblyBasic Cabinet Designs Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Figure Labels LabelingElectrical Aluminum WireContactor CapacitorCrankcase Heater Time-Delay RelayCycle Protector Personal Injury Hazard Pressure SwitchesDefrost Control Board Defrost ThermostatDefrost Speedup Troubleshooting HK32EA001 If outdoor unit will not runIf defrost thermostat is stuck closed If defrost thermostat is stuck openQuiet Shift Five-Minute Compressor DelayCooling HeatingFan Motor Troubleshooting HK32EA003Compressor Plug Low-Voltage TerminalsMechanical Failures Compressor FailuresLocked Rotor Runs, Does Not PumpSplit Post Grommet part number KA75UG100 Noisy CompressorElectrical Failures Single-Phase MotorsUnit Personal Injury Hazard Refrigerant Refrigeration SystemCompressor Oil Servicing Systems on Roofs With Synthetic Materials Synthetic Roof Precautionary ProcedureBrazing Oil ChargingPumpdown Procedure Service Valves and PumpdownPersonal Injury and Unit Damage Hazard AccuRaterr Components Used in R-22 Heat Pumps Heating Piston AccuRaterr Heat Pumps OnlyReversing Valve Heating Mode, Solenoid De-Energized Reversing ValveLiquid Line Filter Drier Install Liquid-line Filter Drier Indoor ACSuction Line Filter Drier Accumulator AccumulatorThermostatic Expansion Valve TXV Install TXVTXV Operation Unit Operation HazardReplacing TXV on an Indoor Coil pre-2006 Make Piping ConnectionsReplacing TXV on Indoor Coil post-2006 Personal Injury and Environmental HazardLeak Detection Refrigeration System RepairCoil Removal Fire HazardSystem Clean-Up After Burnout Compressor Removal and ReplacementEvacuation Check ChargeDeep Vacuum Method Basic Diagnostics Troubleshooting with SuperheatLow Superheat with Normal or Low Suction Pressure Low Superheat with High Suction PressureHunting Superheat High Superheat with Normal or High Suction PressurePseudo Evaporator Superheat Instructions Example Puron System Suction Pressure Drop22 System Suction Pressure Drop Psig PuronrRefrigerant Pressure Temperature ChartPsig 22 Refrigerant Pressure Temperature RelationshipLiquid Line Temperature F Liq Press Subcooling F Psig Puron Subcooling ChartSuperheat F Psig Puron Superheat ChartLiquid Line Temperature F PT F Subcooling F Pres Psig 22 Subcooling Chart22 Superheat Chart Application Guidelines TWO-STAGEModel Plug Model Plug InformationLow Ambient Cooling General InformationDefrost Airflow Selection for 315AAV/355AAV FurnacesDefrost Hold Liquid-Line Solenoid AccessoryForced Defrost All 286A units must be charged in high stage onlyCooling and Heating Operation One Minute Stage Change Time Delay on 286ANA/187ANA ModelsUtility Interface With Evolution Control Compressor Operation on 286ANA/187ANA ModelsOutdoor Fan Motor Operation ECM Fan Motor TroubleshootingMuffler, Accumulator, Reversing Valve RVS Time DelaysThermistors Control BOX Troubleshooting 230v Brown-Out Protection Defeated 230V Line Power Disconnect DetectionCompressor Voltage Sensing Contactor Shorted DetectionTemperature Thermistors Unloader Test ProcedureFailed Thermistor Default Operation Thermistor Sensor ComparisonStatus Codes TroubleshootingEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information All 286B units must be charged in high stage only Heating Check Chart ProcedureCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Troubleshooting 187B & 286B Start Circuit Incoming PowerControl Box Contactor And CapacitorTroubleshooting HK38EA015 circuit board 289B Compressor Thermal Cutout 286B Models Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner Operating Ambient TWO Stage NON-COMMUNICATING 127A/226AAirflow Selections ECM Furnaces Airflow Selection for FV4C Fan Coils non-communicatingCompressor Operation System Function and Sequence of OperationDefrost Speedup Check Charge Airflow Selections for ECM Furnaces non communicating TWO Stage Communicating 167A/266AIndoor Thermostat Control Options Defrost Hold Evolution Controlled Low Ambient CoolingMajor Components Outdoor Fan Motor Operation Communication and Status Function LightsFor Evolution Control only, Green communications Comm Light 2230V Brown-Out Protection Defeated Thermistor Curve No 230V at Compressor ContactorOutdoor Coil Thermistor OCT Attachment Status Codes 167A / 266A TroubleshootingCare and Maintenance Puronr R-410A Refrigerant Quick Reference Guide Final Check-OutAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle Description Table # Index of TablesTWO-STAGE 286A/288A 180A/187A TWO-STAGE 286B/288B 180B/187BCatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.