Bryant R-22 service manual Troubleshooting with Superheat, Basic Diagnostics

Page 34

TROUBLESHOOTING WITH SUPERHEAT

This troubleshooting routine was developed to diagnose cooling problems using superheat in TXV systems. It is effective on heat pumps in cooling mode as well as air conditioners. The system must utilize a TXV as the expansion device in cooling mode.

Basic Diagnostics

NOTE: When checking refrigerant charge and troubleshooting operating systems, the indoor airflow has significant effect on the determination. If you are at this stage, it is assumed you have already checked the subcooling once and believe the charge is correct. From this point, the airflow must be verified prior to proceeding, hence step 1 below.

1.Check or verify proper indoor airflow S Indoor air filter

S Duct dampers and supply registers are open S Indoor coil for debris

2.Check subcooling at OD unit liquid service valve S Outdoor airflow (debris on coil, etc.)

SSet the subcooling at value listed on rating plate if standard lineset

SSet the subcooling at the maximum of 10°F or value listed on rating plate if a long line application

3.Check superheat at OD unit vapor service valve.

SIf low (< 2°F), proceed to Low SuperHeat section.

SIf between 2 and 20°F/11_C valve is probably operating properly.

SIf greater than 20°F/11_C, perform Pseudo Evaporator SuperHeat Instructions check as follows:

Check refrigerant pressure at vapor service valve and refrigerant temperature at outlet of evaporator.

Use suction line geometry (diameter and equivalent length), unit capacity and Tables 7 and 8 to determine suction pressure drop.

SFor standard lineset diameters (vapor service valve diameters and larger) and lengths (less than 80 ft), generally no pressure adjustment (per Table 6 or Table 7) is required.

SFor longer (greater than 80 ft) and small diameter . linesets (less than service valve size), correct pressure (add to gauge pressure reading) per Table 6 and Table 7.

SIf Pseudo Superheat is greater than 15, proceed to High SuperHeat section.

SIf Pseudo Evaporator Superheat is between 2 and 15, TXV appears to be functioning properly.

SIf operation erratic (hunting), proceed to Hunting Superheat °F Superheat in repetition section.

NOTE: Hunting is when the valve superheat swings more than 10_.

Low Superheat with Normal or Low Suction Pressure

NOTE: Normal or low suction pressure is considered for

R-22: < 80 psig, Puron: < 135 psig

1.Re-check airflow and then check sensing bulb tightness, orientation on vapor tube and is properly wrapped.

SLow Superheat with Normal or Low Suction Pressure If OK proceed to Step 2

2. Check superheat at Vapor Service Valve

and

Pseudo

Evaporator Superheat.

 

 

SIf both are less than 2°F, TXV likely not controlling properly, i.e. stuck open -> REPLACE VALVE

SIf superheat is higher than 15°F, proceed to Step 3

3.Perform TXV function check.

SWith system running, place sensing bulb in ice bath for 1 minute -> superheat should increase.

If no response, Replace Valve

If OK proceed to Step 4

4.Check for even temperature distribution at outlet of each circuit of evaporator

SIf greater than 15°F between circuits, distributor or coil has a restriction.

SIf OK proceed to Step 5

Low Superheat with High Suction Pressure

NOTE: High suction pressure is considered for R-22: > 80 psig,

Puron: > 135 psig. An application issue or other system component failure typically causes this condition.

5.R-22 Systems: Check that proper valve used (not an R-410A valve)

SIf OK proceed to Step 6

6.Check airflow, sensing bulb tightness, orientation on vapor tube and ensure bulb is properly wrapped.

SIf OK proceed to Step 7

7.Check that compressor is pumping properly

NOTE: Loose Rules of Thumb: Is discharge saturated 20°F higher than ambient temperature? Is discharge superheat between 15 and 50?

SIf OK proceed to Step 8

8.Recheck Airflow and Subcooling.

SIf OK proceed to Replace Valve

High Superheat with Normal or Low Pressure

NOTE: Normal or low suction pressure is considered: R-22 < 80 psig, Puron < 135 psig.

9.Check for restriction in liquid line (kinked line, filter drier restricted, etc.)

SIf OK proceed to Step 10

10.Check for restriction in suction line (kink, restricted suction filter drier etc.))

SIf OK proceed to Step 11

11.Check power element cap tube is not broken

SIf OK proceed to Step 12

12.Check that equalizer tube is not kinked or plugged

SIf OK proceed to Step 13

13.Check that inlet screen (R-22 systems) is not restricted

SIf OK proceed to Step 14

14.Replace Valve

34

Image 34
Contents Table of Contents Application GuidelineAIR Conditioner and Heat Pump Model Number Nomenclature Table of Contents TWO Stage NON-COMMUNICATINGTWO Stage Communicating Serial Number NomenclatureInstallation Guideline Safety ConsiderationsIntroduction Required Field-Installed Accessories for Air Conditioners AccessoriesRequired Field-Installed Accessories for Heat Pumps Accessory Descriptions Base / Mid-Tier / Deluxe 4-sided Baffle Assembly LOW-AMBIENT Cooling GuidelineDeluxe 3-sided Baffle Assembly and Dimensions Long Line Guideline Cabinet AssemblyBasic Cabinet Designs Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Labeling Figure LabelsContactor Aluminum WireElectrical CapacitorCrankcase Heater Time-Delay RelayCycle Protector Pressure Switches Personal Injury HazardDefrost Thermostat Defrost Control BoardIf defrost thermostat is stuck closed Troubleshooting HK32EA001 If outdoor unit will not runDefrost Speedup If defrost thermostat is stuck openCooling Five-Minute Compressor DelayQuiet Shift HeatingCompressor Plug Troubleshooting HK32EA003Fan Motor Low-Voltage TerminalsLocked Rotor Compressor FailuresMechanical Failures Runs, Does Not PumpNoisy Compressor Split Post Grommet part number KA75UG100Electrical Failures Single-Phase MotorsUnit Personal Injury Hazard Refrigerant Refrigeration SystemCompressor Oil Brazing Synthetic Roof Precautionary ProcedureServicing Systems on Roofs With Synthetic Materials Oil ChargingPumpdown Procedure Service Valves and PumpdownPersonal Injury and Unit Damage Hazard Heating Piston AccuRaterr Heat Pumps Only AccuRaterr Components Used in R-22 Heat PumpsReversing Valve Reversing Valve Heating Mode, Solenoid De-EnergizedLiquid Line Filter Drier Install Liquid-line Filter Drier Indoor ACSuction Line Filter Drier Accumulator AccumulatorTXV Operation Install TXVThermostatic Expansion Valve TXV Unit Operation HazardReplacing TXV on Indoor Coil post-2006 Make Piping ConnectionsReplacing TXV on an Indoor Coil pre-2006 Personal Injury and Environmental Hazard Coil Removal Refrigeration System Repair Leak Detection Fire HazardCompressor Removal and Replacement System Clean-Up After BurnoutEvacuation Check ChargeDeep Vacuum Method Low Superheat with Normal or Low Suction Pressure Troubleshooting with SuperheatBasic Diagnostics Low Superheat with High Suction PressureHunting Superheat High Superheat with Normal or High Suction PressurePseudo Evaporator Superheat Instructions Puron System Suction Pressure Drop Example22 System Suction Pressure Drop PuronrRefrigerant Pressure Temperature Chart Psig22 Refrigerant Pressure Temperature Relationship PsigPuron Subcooling Chart Liquid Line Temperature F Liq Press Subcooling F PsigPuron Superheat Chart Superheat F Psig22 Subcooling Chart Liquid Line Temperature F PT F Subcooling F Pres Psig22 Superheat Chart Model Plug TWO-STAGEApplication Guidelines Model Plug InformationDefrost General InformationLow Ambient Cooling Airflow Selection for 315AAV/355AAV FurnacesForced Defrost Liquid-Line Solenoid AccessoryDefrost Hold All 286A units must be charged in high stage onlyUtility Interface With Evolution Control One Minute Stage Change Time Delay on 286ANA/187ANA ModelsCooling and Heating Operation Compressor Operation on 286ANA/187ANA ModelsECM Fan Motor Troubleshooting Outdoor Fan Motor OperationMuffler, Accumulator, Reversing Valve RVS Time DelaysThermistors Control BOX Troubleshooting Compressor Voltage Sensing 230V Line Power Disconnect Detection230v Brown-Out Protection Defeated Contactor Shorted DetectionFailed Thermistor Default Operation Unloader Test ProcedureTemperature Thermistors Thermistor Sensor ComparisonTroubleshooting Status CodesEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information Heating Check Chart Procedure All 286B units must be charged in high stage onlyCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Control Box Incoming PowerTroubleshooting 187B & 286B Start Circuit Contactor And CapacitorTroubleshooting HK38EA015 circuit board 286B Models Compressor Thermal Cutout 289B Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner Airflow Selections ECM Furnaces TWO Stage NON-COMMUNICATING 127A/226AOperating Ambient Airflow Selection for FV4C Fan Coils non-communicatingCompressor Operation System Function and Sequence of OperationDefrost Speedup Check Charge Airflow Selections for ECM Furnaces non communicating TWO Stage Communicating 167A/266AIndoor Thermostat Control Options Evolution Controlled Low Ambient Cooling Defrost HoldMajor Components Outdoor Fan Motor Operation Communication and Status Function LightsFor Evolution Control only, Green communications Comm Light 2230V Brown-Out Protection Defeated No 230V at Compressor Contactor Thermistor CurveOutdoor Coil Thermistor OCT Attachment 167A / 266A Troubleshooting Status CodesCare and Maintenance Final Check-Out Puronr R-410A Refrigerant Quick Reference GuideAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle TWO-STAGE 286A/288A 180A/187A Index of TablesDescription Table # TWO-STAGE 286B/288B 180B/187BCatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb