Bryant R-22 service manual High Superheat with Normal or High Suction Pressure, Hunting Superheat

Page 35

High Superheat with Normal or High Suction Pressure

NOTE: Normal to High suction pressure is considered

for R-22: > 65 psig, Puron: > 110 psig. An application issue or other system component failure typically causes this condition.

15.Check airflow, sensing bulb tightness, orientation on vapor tube and ensure bulb is properly wrapped.

SIf OK proceed to Step 16

16.R-410A Systems: Make sure proper valve is used (Not R-22)

SIf OK proceed to Step 17

17.Check for even temperature distribution at outlet of each circuit of evaporator

SIf OK proceed to Step 18

18.Check for high evaporator load: Return Air Leaks, high indoor wet bulb and/or dry bulb temp, undersized system, etc.

SIf OK proceed to Step 19

19.Check that compressor is pumping properly

SLoose Rule of Thumb: Is discharge saturated 20°F higher than ambient temperature? Is discharge superheat between 15_F and 50_F?

Hunting Superheat

NOTE: Hunting is when the valve superheat swings more than 10°F Superheat in repetition. This is typically an application issue.

20.Check for obvious kinked or pinched distributor (capillary) tubes causing imbalance to the circuiting.

SIf OK proceed to Step 21

21.Check that proper size valve is used per Product Literature.

SIf OK proceed to Step 22

22.Check airflow, sensing bulb tightness, orientation on vapor tube and ensure bulb is properly wrapped.

SIf OK proceed to Step 23

23.Check for even temperature distribution (±5° difference) at outlet of each circuit of evaporator and for even air distribution over all evaporator slabs

SIf OK proceed to Step 24.

24.Move sensing bulb further down suction line.

SIf problem not corrected, replace valve

Pseudo Evaporator Superheat Instructions

The Pseudo Evaporator Superheat calculates the superheat at the outlet of the evaporator with known and available information. Because there generally is not a pressure port on the vapor line at the indoor coil, this procedure allows the service personnel to evaluate the evaporator superheat with the vapor pressure port at the outdoor unit.

The method requires the following information:

SSuction line temperature at the outlet of the evaporator (°F).

SSuction line pressure at the outdoor unit (psig). S Outdoor nominal unit size (btuh).

S Suction line equivalent line length (ft).

SSuction line pressure drop from tables (Table 6 and Table 7).

SPressure-Temperature relationship for refrigerant used (P-T Chart).

If system uses a vapor line the same size as vapor service valve fitting or larger AND the line set equivalent length is 80 feet or less, the pressure drop in vapor line of line set can be ignored.

1.Take suction line temperature at outlet of evaporator at indoor unit.

2.Take suction service valve pressure at OD unit.

3.Determine lineset vapor line equivalent length and tube diameter.

4.Determine suction line pressure drop from Table 6 (Puron) or Table 7 (R-22).

5.Calculate Pseudo Evaporator Superheat.

SAdd the suction line pressure drop to the pressure reading obtained at suction service valve.

NOTE: For nominal and larger diameter vapor lines with standard length linesets (vapor line same size as service valve fitting size and larger with equivalent length less than 80 ft) the pressure drop can be ignored – use vapor service valve pressure and evaporator outlet temperature to calculate superheat

SDetermine saturated evaporator temperature from a refrigerant pressure temperature relationship chart (PT chart).

SSubtract saturated evaporator from evaporator suction line temperature to obtain evaporator superheat.

 

90° STD

 

 

 

90° LONG RAD

45° STD

 

 

 

 

 

A01058

 

Fig. 32 – Tube Fitting Geometry

 

 

Table 5—Fitting Losses in Equivalent Feet

 

 

 

 

 

 

TUBE SIZE OD

90° STD (A)

 

90° LONG RAD (B)

45° STD (C)

(IN.)

 

 

 

 

 

1/2

1.2

 

0.8

0.6

5/8

1.6

 

1.0

0.8

3/4

1.8

 

1.2

0.9

7/8

2.0

 

1.4

1.0

1---1/8

2.6

 

1.7

1.3

35

Image 35
Contents Application Guideline Table of ContentsSerial Number Nomenclature Table of Contents TWO Stage NON-COMMUNICATINGTWO Stage Communicating AIR Conditioner and Heat Pump Model Number NomenclatureIntroduction Safety ConsiderationsInstallation Guideline Required Field-Installed Accessories for Heat Pumps AccessoriesRequired Field-Installed Accessories for Air Conditioners Accessory Descriptions LOW-AMBIENT Cooling Guideline Base / Mid-Tier / Deluxe 4-sided Baffle AssemblyDeluxe 3-sided Baffle Assembly and Dimensions Basic Cabinet Designs Cabinet AssemblyLong Line Guideline Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Figure Labels LabelingCapacitor Aluminum WireElectrical ContactorCycle Protector Time-Delay RelayCrankcase Heater Personal Injury Hazard Pressure SwitchesDefrost Control Board Defrost ThermostatIf defrost thermostat is stuck open Troubleshooting HK32EA001 If outdoor unit will not runDefrost Speedup If defrost thermostat is stuck closedHeating Five-Minute Compressor DelayQuiet Shift CoolingLow-Voltage Terminals Troubleshooting HK32EA003Fan Motor Compressor PlugRuns, Does Not Pump Compressor FailuresMechanical Failures Locked RotorSplit Post Grommet part number KA75UG100 Noisy CompressorUnit Personal Injury Hazard Single-Phase MotorsElectrical Failures Compressor Oil Refrigeration SystemRefrigerant Oil Charging Synthetic Roof Precautionary ProcedureServicing Systems on Roofs With Synthetic Materials BrazingPersonal Injury and Unit Damage Hazard Service Valves and PumpdownPumpdown Procedure AccuRaterr Components Used in R-22 Heat Pumps Heating Piston AccuRaterr Heat Pumps OnlyReversing Valve Heating Mode, Solenoid De-Energized Reversing ValveSuction Line Filter Drier Install Liquid-line Filter Drier Indoor ACLiquid Line Filter Drier Accumulator AccumulatorUnit Operation Hazard Install TXVThermostatic Expansion Valve TXV TXV OperationPersonal Injury and Environmental Hazard Make Piping ConnectionsReplacing TXV on an Indoor Coil pre-2006 Replacing TXV on Indoor Coil post-2006Fire Hazard Refrigeration System RepairLeak Detection Coil RemovalSystem Clean-Up After Burnout Compressor Removal and ReplacementDeep Vacuum Method Check ChargeEvacuation Low Superheat with High Suction Pressure Troubleshooting with SuperheatBasic Diagnostics Low Superheat with Normal or Low Suction PressurePseudo Evaporator Superheat Instructions High Superheat with Normal or High Suction PressureHunting Superheat Example Puron System Suction Pressure Drop22 System Suction Pressure Drop Psig PuronrRefrigerant Pressure Temperature ChartPsig 22 Refrigerant Pressure Temperature RelationshipLiquid Line Temperature F Liq Press Subcooling F Psig Puron Subcooling ChartSuperheat F Psig Puron Superheat ChartLiquid Line Temperature F PT F Subcooling F Pres Psig 22 Subcooling Chart22 Superheat Chart Model Plug Information TWO-STAGEApplication Guidelines Model PlugAirflow Selection for 315AAV/355AAV Furnaces General InformationLow Ambient Cooling DefrostAll 286A units must be charged in high stage only Liquid-Line Solenoid AccessoryDefrost Hold Forced DefrostCompressor Operation on 286ANA/187ANA Models One Minute Stage Change Time Delay on 286ANA/187ANA ModelsCooling and Heating Operation Utility Interface With Evolution ControlOutdoor Fan Motor Operation ECM Fan Motor TroubleshootingThermistors Time DelaysMuffler, Accumulator, Reversing Valve RVS Control BOX Troubleshooting Contactor Shorted Detection 230V Line Power Disconnect Detection230v Brown-Out Protection Defeated Compressor Voltage SensingThermistor Sensor Comparison Unloader Test ProcedureTemperature Thermistors Failed Thermistor Default OperationStatus Codes TroubleshootingEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information All 286B units must be charged in high stage only Heating Check Chart ProcedureCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Contactor And Capacitor Incoming PowerTroubleshooting 187B & 286B Start Circuit Control BoxTroubleshooting HK38EA015 circuit board 289B Compressor Thermal Cutout 286B Models Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner Airflow Selection for FV4C Fan Coils non-communicating TWO Stage NON-COMMUNICATING 127A/226AOperating Ambient Airflow Selections ECM FurnacesDefrost Speedup System Function and Sequence of OperationCompressor Operation Check Charge Indoor Thermostat Control Options TWO Stage Communicating 167A/266AAirflow Selections for ECM Furnaces non communicating Defrost Hold Evolution Controlled Low Ambient CoolingMajor Components For Evolution Control only, Green communications Comm Light Communication and Status Function LightsOutdoor Fan Motor Operation 2230V Brown-Out Protection Defeated Thermistor Curve No 230V at Compressor ContactorOutdoor Coil Thermistor OCT Attachment Status Codes 167A / 266A TroubleshootingCare and Maintenance Puronr R-410A Refrigerant Quick Reference Guide Final Check-OutAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle TWO-STAGE 286B/288B 180B/187B Index of TablesDescription Table # TWO-STAGE 286A/288A 180A/187ACatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.