Bryant R-22 service manual Evolution Controlled Low Ambient Cooling, Defrost Hold

Page 71

GENERAL INFORMATION

Evolution Controlled Low Ambient Cooling

This unit is capable of low ambient cooling down to 0°F (-17.8°C) without a kit ONLY when using an Evolution Control. A low ambient kit is not required for Evolution controlled low ambient operation. The Evolution Control provides an automatic evaporator freeze thermostat. Low ambient cooling must be enabled in the User Interface setup. Fan may not begin to cycle until about 40°F (4.4°C) OAT. Fan will cycle based on coil and outdoor air temperature.

Evolution controlled low ambient mode operates as follows:

S Fan is OFF when outdoor coil temperature is less than outdoor air temperature (+ 3 _F/1.7_C) or outdoor fan has been ON for 30 minutes. (Fan is turned off to allow refrigerant system to stabilize.)

S Fan is ON when outdoor coil temperature is less than outdoor air temperature (+25_F/13.9_C) or outdoor coil temperature is more than 80 _F (26.7 _C) or if outdoor fan has been OFF for 30 minutes. (Fan is turned on to allow refrigerant system to stabilize.)

S Low pressure switch is ignored for first 3 minutes during low ambient start up. After 3 minutes, if LPS trips, then outdoor fan motor is turned off for 10 minutes, with the compressor running. If LPS closes within 10 minutes then cooling continues with the outdoor fan cycling per the coil temperature routine listed above for the remainder of the cooling cycle. If the LPS does not close within 10 minutes, then the normal LPS trip response (shut down cooling operation and generate LPS trip error) will occur.

Defrost

This control offers 5 possible defrost interval times: 30, 60, 90, 120 minutes, or AUTO.

Defrost intervals are selected by dip switches on the unit control board or by the Evolution Control User Interface. The Evolution Control selection overrides the control board dip switch settings.

Defrost interval times: 30, 60, 90, and 120 minutes or AUTO are selected by the Evolution Control User Interface (the dip switches are not used.)

AUTO defrost adjusts the defrost interval time based on the last defrost time as follows:

S When defrost time <3 minutes, the next defrost interval=120 minutes.

SWhen defrost time 3-5 minutes, the next defrost interval=90

minutes.

SWhen defrost time 5-7 minutes, the next defrost interval=60

minutes.

S When defrost time >7 minutes, the next defrost interval=30 minutes.

The control board accumulates compressor run time. As the accumulated run time approaches the selected defrost interval time, the control board monitors the coil temperature sensor for a defrost demand. If a defrost demand exists, a defrost cycle will be initiated at the end of the selected time interval. A defrost demand exists when the coil temperature is at or below 32_F (0_C) for 4 minutes during the interval.

The defrost cycle is terminated when the coil temperature reaches 65_F (18.33_C)or 10 minutes has passed. When OAT is > 25°F (-3.9°C), defrost will occur in low or high stage as demanded by the thermostat or User Interface.

If OAT is 25°F (3.9_C), defrost will occur in high stage only, regardless of thermostat or User Interface demand, and will terminate at 50_F (10_C) coil temperature with a minimum of 2.5 minutes in defrost.

If the coil temperature does not reach 32_F (0_C) within the interval, the interval timer will be reset and start over.

S Upon initial power up the first defrost interval is defaulted to 30 minutes. Remaining intervals are at selected times.

S Defrost is only allowed to occur below 50_F (10_C) outdoor ambient temperature.

The outdoor fan output (ODF) will remain off for 20 seconds after termination. This delay will allow time for the system to capture the heat from the outdoor coil and reduce the “steam cloud” effect that may occur on transition from defrost to heating cycle. The outdoor fan output OFF delay of 20 seconds may be defeated to enable the fan to energize immediately at the time of termination and 12 seconds prior to the reversing valve de-energizing through the User Interface setup screen (available with SYSTXCCUID01-C), or forced defrost pins as follows:

The ODF fan delay defeat can be toggled by shorting the forced defrost pins for >15 seconds while in the standby mode (status LED on solid). The LED will start to flash when the toggle has taken place.

Status code 4 shows the fan delay defeat is active (no delay). Status code 3 shows that it is not active (20 second delay).

The code will continue to be displayed until after the short is removed. There is a 5 second wait before the code is cancelled once the short is removed. the code that is flashing will finish before going back to solid LED. The control is shipped with the ODF fan delay defeat NOT active.

The change in status is remembered until toggled to a new status. A power down/power up sequence will not reset the status. It may be necessary to do the toggle twice to cycle to the desired state of the defeat.

Defrost Hold

On a non-communicating system, if the thermostat becomes satisfied (Y1 or Y1 and Y2) before the defrost cycle is terminated, the control will “hold” in defrost mode and finish the defrost cycle on the next call for heat.

On models with communicating Evolution Control, defrost hold is not needed because the User Interface will complete the defrost cycle before shutting down the system.

Forced Defrost

On a system with non-communicating (non-Evolution) control, forced defrost can be initiated by manually shorting the 2-pin header labeled FORCED DEFROST (see Fig 6) on the control board for 5 seconds then releasing.

On a system with communicating (Evolution) control, forced defrost is initiated with the User Interface.

On all models, during a Forced Defrost:

SIf coil temperature is at defrost temperature of 32_F (0_C), and

outdoor air temperature is below 50_F (10_C), a full defrost sequence will occur.

S If coil temperature or outdoor air temperature does not meet the above requirements, an abbreviated 30 second defrost will occur.

71

Image 71
Contents Application Guideline Table of ContentsSerial Number Nomenclature Table of Contents TWO Stage NON-COMMUNICATINGTWO Stage Communicating AIR Conditioner and Heat Pump Model Number NomenclatureIntroduction Safety ConsiderationsInstallation Guideline Required Field-Installed Accessories for Heat Pumps AccessoriesRequired Field-Installed Accessories for Air Conditioners Accessory Descriptions LOW-AMBIENT Cooling Guideline Base / Mid-Tier / Deluxe 4-sided Baffle AssemblyDeluxe 3-sided Baffle Assembly and Dimensions Basic Cabinet Designs Cabinet AssemblyLong Line Guideline Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Figure Labels LabelingCapacitor Aluminum WireElectrical ContactorCycle Protector Time-Delay RelayCrankcase Heater Personal Injury Hazard Pressure SwitchesDefrost Control Board Defrost ThermostatIf defrost thermostat is stuck open Troubleshooting HK32EA001 If outdoor unit will not runDefrost Speedup If defrost thermostat is stuck closedHeating Five-Minute Compressor DelayQuiet Shift CoolingLow-Voltage Terminals Troubleshooting HK32EA003Fan Motor Compressor PlugRuns, Does Not Pump Compressor FailuresMechanical Failures Locked RotorSplit Post Grommet part number KA75UG100 Noisy CompressorUnit Personal Injury Hazard Single-Phase MotorsElectrical Failures Compressor Oil Refrigeration SystemRefrigerant Oil Charging Synthetic Roof Precautionary ProcedureServicing Systems on Roofs With Synthetic Materials BrazingPersonal Injury and Unit Damage Hazard Service Valves and PumpdownPumpdown Procedure AccuRaterr Components Used in R-22 Heat Pumps Heating Piston AccuRaterr Heat Pumps OnlyReversing Valve Heating Mode, Solenoid De-Energized Reversing ValveSuction Line Filter Drier Install Liquid-line Filter Drier Indoor ACLiquid Line Filter Drier Accumulator AccumulatorUnit Operation Hazard Install TXVThermostatic Expansion Valve TXV TXV OperationPersonal Injury and Environmental Hazard Make Piping ConnectionsReplacing TXV on an Indoor Coil pre-2006 Replacing TXV on Indoor Coil post-2006Fire Hazard Refrigeration System RepairLeak Detection Coil RemovalSystem Clean-Up After Burnout Compressor Removal and ReplacementDeep Vacuum Method Check ChargeEvacuation Low Superheat with High Suction Pressure Troubleshooting with SuperheatBasic Diagnostics Low Superheat with Normal or Low Suction PressurePseudo Evaporator Superheat Instructions High Superheat with Normal or High Suction PressureHunting Superheat Example Puron System Suction Pressure Drop22 System Suction Pressure Drop Psig PuronrRefrigerant Pressure Temperature ChartPsig 22 Refrigerant Pressure Temperature RelationshipLiquid Line Temperature F Liq Press Subcooling F Psig Puron Subcooling ChartSuperheat F Psig Puron Superheat ChartLiquid Line Temperature F PT F Subcooling F Pres Psig 22 Subcooling Chart22 Superheat Chart Model Plug Information TWO-STAGEApplication Guidelines Model PlugAirflow Selection for 315AAV/355AAV Furnaces General InformationLow Ambient Cooling DefrostAll 286A units must be charged in high stage only Liquid-Line Solenoid AccessoryDefrost Hold Forced DefrostCompressor Operation on 286ANA/187ANA Models One Minute Stage Change Time Delay on 286ANA/187ANA ModelsCooling and Heating Operation Utility Interface With Evolution ControlOutdoor Fan Motor Operation ECM Fan Motor TroubleshootingThermistors Time DelaysMuffler, Accumulator, Reversing Valve RVS Control BOX Troubleshooting Contactor Shorted Detection 230V Line Power Disconnect Detection230v Brown-Out Protection Defeated Compressor Voltage SensingThermistor Sensor Comparison Unloader Test ProcedureTemperature Thermistors Failed Thermistor Default OperationStatus Codes TroubleshootingEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information All 286B units must be charged in high stage only Heating Check Chart ProcedureCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Contactor And Capacitor Incoming PowerTroubleshooting 187B & 286B Start Circuit Control BoxTroubleshooting HK38EA015 circuit board 289B Compressor Thermal Cutout 286B Models Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner Airflow Selection for FV4C Fan Coils non-communicating TWO Stage NON-COMMUNICATING 127A/226AOperating Ambient Airflow Selections ECM FurnacesDefrost Speedup System Function and Sequence of OperationCompressor Operation Check Charge Indoor Thermostat Control Options TWO Stage Communicating 167A/266AAirflow Selections for ECM Furnaces non communicating Defrost Hold Evolution Controlled Low Ambient CoolingMajor Components For Evolution Control only, Green communications Comm Light Communication and Status Function LightsOutdoor Fan Motor Operation 2230V Brown-Out Protection Defeated Thermistor Curve No 230V at Compressor ContactorOutdoor Coil Thermistor OCT Attachment Status Codes 167A / 266A TroubleshootingCare and Maintenance Puronr R-410A Refrigerant Quick Reference Guide Final Check-OutAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle TWO-STAGE 286B/288B 180B/187B Index of TablesDescription Table # TWO-STAGE 286A/288A 180A/187ACatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.