Bryant R-22 service manual Refrigeration System Repair, Leak Detection, Coil Removal, Fire Hazard

Page 31

REFRIGERATION SYSTEM REPAIR

Leak Detection

New installations should be checked for leaks prior to complete charging. If a system has lost all or most of its charge, system must be pressurized again to approximately 150 psi minimum and 375 psi maximum. This can be done by adding refrigerant using normal charging procedures or by pressurizing system with nitrogen (less expensive than refrigerant). Nitrogen also leaks faster than refrigerants. Nitrogen cannot, however, be detected by an electronic leak detector. (See Fig. 27.)

BEEP

BEEP

A95422

Fig. 27 – Electronic Leak Detection

!WARNING

PERSONAL INJURY AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal injury or death.

Due to the high pressure of nitrogen, it should never be used without a pressure regulator on the tank.

Assuming that a system is pressurized with either all refrigerant or a mixture of nitrogen and refrigerant, leaks in the system can be found with an electronic leak detector that is capable of detecting specific refrigerants.

If system has been operating for some time, first check for a leak visually. Since refrigerant carries a small quantity of oil, traces of oil at any joint or connection is an indication that refrigerant is leaking at that point.

A simple and inexpensive method of testing for leaks is to use soap bubbles. (See Fig. 28.) Any solution of water and soap may be used. Soap solution is applied to all joints and connections in system. A small pinhole leak is located by tracing bubbles in soap solution around leak. If the leak is very small, several minutes may pass before a bubble will form. Popular commercial leak detection solutions give better, longer-lasting bubbles and more accurate results than plain soapy water. The bubble solution must be removed from the tubing and fittings after checking for leaks as some solutions may corrode the metal.

LEAK

DETECTOR

SOLUTION

A95423

Fig. 29 – Bubble Leak Detection

You may use an electronic leak detector designed for specific refrigerant to check for leaks. (See Fig. 27.) This unquestionably is the most efficient and easiest method for checking leaks. There are various types of electronic leak detectors. Check with manufacturer of equipment for suitability. Generally speaking, they are portable, lightweight, and consist of a box with several switches and a probe or sniffer. Detector is turned on and probe is passed around all fittings and connections in system. Leak is detected by either the movement of a pointer on detector dial, a buzzing sound, or a light.

In all instances when a leak is found, system charge must be recovered and leak repaired before final charging and operation. After leak testing or leak is repaired, replace liquid line filter drier, evacuate system, and recharge with correct refrigerant quantity.

Coil Removal

Coils are easy to remove if required for compressor removal, or to replace coil.

1.Shut off all power to unit.

2.Recover refrigerant from system through service valves.

3.Break vacuum with nitrogen.

4.Remove top cover. (See Remove Top Cover in Cabinet section of the manual.)

5.Remove screws in base pan to coil grille.

6.Remove coil grille from unit.

7.Remove screws on corner post holding coil tube sheet.

!WARNING

FIRE HAZARD

Failure to follow this warning could result in personal injury or equipment damage.

Cut tubing to reduce possibility of personal injury and fire.

8.Use midget tubing cutter to cut liquid and vapor lines at both sides of coil. Cut in convenient location for easy reassembly with copper slip couplings.

9.Lift coil vertically from basepan and carefully place aside.

10.Reverse procedure to reinstall coil.

11.Replace filter drier, evacuate system, recharge, and check for normal systems operation.

31

Image 31
Contents Application Guideline Table of ContentsSerial Number Nomenclature Table of Contents TWO Stage NON-COMMUNICATINGTWO Stage Communicating AIR Conditioner and Heat Pump Model Number NomenclatureInstallation Guideline Safety ConsiderationsIntroduction Required Field-Installed Accessories for Air Conditioners AccessoriesRequired Field-Installed Accessories for Heat Pumps Accessory Descriptions LOW-AMBIENT Cooling Guideline Base / Mid-Tier / Deluxe 4-sided Baffle AssemblyDeluxe 3-sided Baffle Assembly and Dimensions Long Line Guideline Cabinet AssemblyBasic Cabinet Designs Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Figure Labels LabelingCapacitor Aluminum WireElectrical ContactorCrankcase Heater Time-Delay RelayCycle Protector Personal Injury Hazard Pressure SwitchesDefrost Control Board Defrost ThermostatIf defrost thermostat is stuck open Troubleshooting HK32EA001 If outdoor unit will not runDefrost Speedup If defrost thermostat is stuck closedHeating Five-Minute Compressor DelayQuiet Shift CoolingLow-Voltage Terminals Troubleshooting HK32EA003Fan Motor Compressor PlugRuns, Does Not Pump Compressor FailuresMechanical Failures Locked RotorSplit Post Grommet part number KA75UG100 Noisy CompressorElectrical Failures Single-Phase MotorsUnit Personal Injury Hazard Refrigerant Refrigeration SystemCompressor Oil Oil Charging Synthetic Roof Precautionary ProcedureServicing Systems on Roofs With Synthetic Materials BrazingPumpdown Procedure Service Valves and PumpdownPersonal Injury and Unit Damage Hazard AccuRaterr Components Used in R-22 Heat Pumps Heating Piston AccuRaterr Heat Pumps OnlyReversing Valve Heating Mode, Solenoid De-Energized Reversing ValveLiquid Line Filter Drier Install Liquid-line Filter Drier Indoor ACSuction Line Filter Drier Accumulator AccumulatorUnit Operation Hazard Install TXVThermostatic Expansion Valve TXV TXV OperationPersonal Injury and Environmental Hazard Make Piping ConnectionsReplacing TXV on an Indoor Coil pre-2006 Replacing TXV on Indoor Coil post-2006Fire Hazard Refrigeration System RepairLeak Detection Coil RemovalSystem Clean-Up After Burnout Compressor Removal and ReplacementEvacuation Check ChargeDeep Vacuum Method Low Superheat with High Suction Pressure Troubleshooting with SuperheatBasic Diagnostics Low Superheat with Normal or Low Suction PressureHunting Superheat High Superheat with Normal or High Suction PressurePseudo Evaporator Superheat Instructions Example Puron System Suction Pressure Drop22 System Suction Pressure Drop Psig PuronrRefrigerant Pressure Temperature ChartPsig 22 Refrigerant Pressure Temperature RelationshipLiquid Line Temperature F Liq Press Subcooling F Psig Puron Subcooling ChartSuperheat F Psig Puron Superheat ChartLiquid Line Temperature F PT F Subcooling F Pres Psig 22 Subcooling Chart22 Superheat Chart Model Plug Information TWO-STAGEApplication Guidelines Model PlugAirflow Selection for 315AAV/355AAV Furnaces General InformationLow Ambient Cooling DefrostAll 286A units must be charged in high stage only Liquid-Line Solenoid AccessoryDefrost Hold Forced DefrostCompressor Operation on 286ANA/187ANA Models One Minute Stage Change Time Delay on 286ANA/187ANA ModelsCooling and Heating Operation Utility Interface With Evolution ControlOutdoor Fan Motor Operation ECM Fan Motor TroubleshootingMuffler, Accumulator, Reversing Valve RVS Time DelaysThermistors Control BOX Troubleshooting Contactor Shorted Detection 230V Line Power Disconnect Detection230v Brown-Out Protection Defeated Compressor Voltage SensingThermistor Sensor Comparison Unloader Test ProcedureTemperature Thermistors Failed Thermistor Default OperationStatus Codes TroubleshootingEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information All 286B units must be charged in high stage only Heating Check Chart ProcedureCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Contactor And Capacitor Incoming PowerTroubleshooting 187B & 286B Start Circuit Control BoxTroubleshooting HK38EA015 circuit board 289B Compressor Thermal Cutout 286B Models Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner Airflow Selection for FV4C Fan Coils non-communicating TWO Stage NON-COMMUNICATING 127A/226AOperating Ambient Airflow Selections ECM FurnacesCompressor Operation System Function and Sequence of OperationDefrost Speedup Check Charge Airflow Selections for ECM Furnaces non communicating TWO Stage Communicating 167A/266AIndoor Thermostat Control Options Defrost Hold Evolution Controlled Low Ambient CoolingMajor Components Outdoor Fan Motor Operation Communication and Status Function LightsFor Evolution Control only, Green communications Comm Light 2230V Brown-Out Protection Defeated Thermistor Curve No 230V at Compressor ContactorOutdoor Coil Thermistor OCT Attachment Status Codes 167A / 266A TroubleshootingCare and Maintenance Puronr R-410A Refrigerant Quick Reference Guide Final Check-OutAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle TWO-STAGE 286B/288B 180B/187B Index of TablesDescription Table # TWO-STAGE 286A/288A 180A/187ACatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb