Bryant R-22 service manual 286B Models Compressor Thermal Cutout, 289B Compressor Thermal Cutout

Page 63

230v Brown-Out Protection Defeated

The brownout feature can be defeated if needed for severe noisy power conditions. This defeat should always be a last resort to solving the problem. Defeat is available on the User Interface setup screen (available with SYSTXBBUID01-C UI) or can be initiated through the forced defrost pins for non-communicating systems as follows:

The brownout toggle is accomplished by shorting the defrost pins from power up with the OAT and OCT sensor connector removed. After 3 seconds, the status of the force defrost short and the OAT/OCT as open will be checked. If correct, then the brownout will be toggled.

SStatus code 6 shows the brownout is disabled. S Status code 5 shows the brownout is active.

After the brownout defeat is set, power down and reinstall the OAT/OCT sensor and remove the short from the forced defrost pins. As long as the short on the forced defrost remains, the OAT and OCT faults will not be cleared. The code will continue to be flashed.

The control is shipped with the brownout active. The change in status is remembered until toggled to a new status. A power down/power up sequence will not reset the status. It may be necessary to do the toggle twice to cycle to the desired state of the defeat.

230V Line (Power Disconnect) Detection

If there is no 230v at the compressor contactor(s) when the indoor unit is powered and cooling or heating demand exists, the appropriate fault code is displayed. Verify the disconnect is closed and 230v wiring is connected to the unit.

Compressor Voltage Sensing

The control board input terminals labeled VS, VR and L2 on 286B/187B models and VS and L2 on 289B/180B models (see Fig. 45) are used to detect compressor voltage status and alert the user of potential problems. The control continuously monitors the high voltage on the run capacitor of the compressor motor. Voltage should be present any time the compressor contactor is energized and voltage should not be present when the contactor is de-energized.

Contactor Shorted Detection

If there is compressor voltage sensed when there is no demand for compressor operation, the contactor may be stuck closed or there may be a wiring error. The control will flash the appropriate fault code.

286B Models - Compressor Thermal Cutout

The control senses the compressor voltage at VR and VS. When starting or running, a phase difference of the voltages on the inputs will indicate the thermal protector is closed. If the phase difference is 5_ or less for 10 seconds, the internal protector is open. The control de-energizes the appropriate compressor contactor for 15 minutes, but continues to operate the outdoor fan. The control Status LED will flash the appropriate code shown in Table 21. After 15 minutes, with a call for low or high stage cooling or heating, the appropriate compressor contactor is energized. If the thermal protector has not re-set, the outdoor fan is turned off. If the call for cooling or heating continues, the control will energize the compressor contactor every 15 minutes. If the thermal protector closes, (at the next 15 minute interval check) the unit will resume operation.

If the thermal cutout trips for three consecutive cycles, then unit operation is locked out for 4 hours and the appropriate fault code is displayed.

289B Compressor Thermal Cutout

If the control senses the compressor voltage after start-up and is then absent for 10 consecutive seconds while cooling or heating demand exists, the thermal protector is open. The control de-energizes the compressor contactor for 15 minutes, but continues to operate the outdoor fan. The control Status LED will flash the appropriate code shown in Table 21. After 15 minutes, with a call for low or high stage cooling or heating, the compressor contactor is energized. If the thermal protector has not re-set, the outdoor fan is turned off. If the call for cooling or heating continues, the control will energize the compressor contactor every 15 minutes. If the thermal protector closes, (at the next 15 minute interval check) the unit will resume operation.

If the thermal cutout trips for three consecutive cycles, then unit operation is locked out for 4 hours and the appropriate fault code is displayed.

Low or High Contactor Open (286B models) / No 230V at Compressor Contractor (289B models)

If the compressor voltage is not sensed when the compressor should be starting, the appropriate contactor may be stuck open or there is a wiring error. The control will flash the appropriate fault code. Check the contactor and control box wiring.

Troubleshooting 289B/286B units for proper switching between low & high stages

Check the suction pressures at the service valves. Suction pressure should be reduced by 3-10% when switching from low to high capacity.

NOTE: The liquid pressures are very similar between low and high stage operation, so liquid pressure should not be used for troubleshooting.

Compressor current should increase 20-45% when switching from low to high stage. The compressor solenoid when energized in high stage, should measure 24vac.

When the compressor is operating in low stage the 24v DC compressor solenoid coil is de-energized. When the compressor is operating in high stage, the 24v DC solenoid coil is energized. The solenoid plug harness that is connected to the compressor HAS an internal rectifier that converts the 24v DC signal to 24v AC. DO

NOT INSTALL A PLUG WITHOUT AN INTERNAL RECTIFIER.

Unloader Test Procedure

The unloader is the compressor internal mechanism, controlled by the DC solenoid, that modulates between high and low stage. If it is suspected that the unloader is not working, the following methods may be used to verify operation.

1.Operate the system and measure compressor amperage. Cycle the unloader on and off at 30 second plus intervals at the UI (from low to high stage and back to low stage). Wait 5 seconds after staging to high before taking a reading. The compressor amperage should go up or down at least 20 percent.

2.If the expected result is not achieved, remove the solenoid plug from the compressor and with the unit running and the UI calling for high stage, test the voltage output at the plug with a DC voltmeter. The reading should be 4 to 18 volts.

3.If the correct DC voltage is at the control circuit molded plug, measure the compressor unloader coil resistance. The resistance should be 32 to 60 ohms depending on compressor temperature. If the coil resistance is infinity, much lower than 32 ohms, or is grounded, the compressor must be replaced.

63

Image 63
Contents Application Guideline Table of ContentsSerial Number Nomenclature Table of Contents TWO Stage NON-COMMUNICATINGTWO Stage Communicating AIR Conditioner and Heat Pump Model Number NomenclatureSafety Considerations Installation GuidelineIntroduction Accessories Required Field-Installed Accessories for Air ConditionersRequired Field-Installed Accessories for Heat Pumps Accessory Descriptions LOW-AMBIENT Cooling Guideline Base / Mid-Tier / Deluxe 4-sided Baffle AssemblyDeluxe 3-sided Baffle Assembly and Dimensions Cabinet Assembly Long Line GuidelineBasic Cabinet Designs Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Figure Labels LabelingCapacitor Aluminum WireElectrical ContactorTime-Delay Relay Crankcase HeaterCycle Protector Personal Injury Hazard Pressure SwitchesDefrost Control Board Defrost ThermostatIf defrost thermostat is stuck open Troubleshooting HK32EA001 If outdoor unit will not runDefrost Speedup If defrost thermostat is stuck closedHeating Five-Minute Compressor DelayQuiet Shift CoolingLow-Voltage Terminals Troubleshooting HK32EA003Fan Motor Compressor PlugRuns, Does Not Pump Compressor FailuresMechanical Failures Locked RotorSplit Post Grommet part number KA75UG100 Noisy CompressorSingle-Phase Motors Electrical FailuresUnit Personal Injury Hazard Refrigeration System RefrigerantCompressor Oil Oil Charging Synthetic Roof Precautionary ProcedureServicing Systems on Roofs With Synthetic Materials BrazingService Valves and Pumpdown Pumpdown ProcedurePersonal Injury and Unit Damage Hazard AccuRaterr Components Used in R-22 Heat Pumps Heating Piston AccuRaterr Heat Pumps OnlyReversing Valve Heating Mode, Solenoid De-Energized Reversing ValveInstall Liquid-line Filter Drier Indoor AC Liquid Line Filter DrierSuction Line Filter Drier Accumulator AccumulatorUnit Operation Hazard Install TXVThermostatic Expansion Valve TXV TXV OperationPersonal Injury and Environmental Hazard Make Piping ConnectionsReplacing TXV on an Indoor Coil pre-2006 Replacing TXV on Indoor Coil post-2006Fire Hazard Refrigeration System RepairLeak Detection Coil RemovalSystem Clean-Up After Burnout Compressor Removal and ReplacementCheck Charge EvacuationDeep Vacuum Method Low Superheat with High Suction Pressure Troubleshooting with SuperheatBasic Diagnostics Low Superheat with Normal or Low Suction PressureHigh Superheat with Normal or High Suction Pressure Hunting SuperheatPseudo Evaporator Superheat Instructions Example Puron System Suction Pressure Drop22 System Suction Pressure Drop Psig PuronrRefrigerant Pressure Temperature ChartPsig 22 Refrigerant Pressure Temperature RelationshipLiquid Line Temperature F Liq Press Subcooling F Psig Puron Subcooling ChartSuperheat F Psig Puron Superheat ChartLiquid Line Temperature F PT F Subcooling F Pres Psig 22 Subcooling Chart22 Superheat Chart Model Plug Information TWO-STAGEApplication Guidelines Model PlugAirflow Selection for 315AAV/355AAV Furnaces General InformationLow Ambient Cooling DefrostAll 286A units must be charged in high stage only Liquid-Line Solenoid AccessoryDefrost Hold Forced DefrostCompressor Operation on 286ANA/187ANA Models One Minute Stage Change Time Delay on 286ANA/187ANA ModelsCooling and Heating Operation Utility Interface With Evolution ControlOutdoor Fan Motor Operation ECM Fan Motor TroubleshootingTime Delays Muffler, Accumulator, Reversing Valve RVSThermistors Control BOX Troubleshooting Contactor Shorted Detection 230V Line Power Disconnect Detection230v Brown-Out Protection Defeated Compressor Voltage SensingThermistor Sensor Comparison Unloader Test ProcedureTemperature Thermistors Failed Thermistor Default OperationStatus Codes TroubleshootingEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information All 286B units must be charged in high stage only Heating Check Chart ProcedureCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Contactor And Capacitor Incoming PowerTroubleshooting 187B & 286B Start Circuit Control BoxTroubleshooting HK38EA015 circuit board 289B Compressor Thermal Cutout 286B Models Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner Airflow Selection for FV4C Fan Coils non-communicating TWO Stage NON-COMMUNICATING 127A/226AOperating Ambient Airflow Selections ECM FurnacesSystem Function and Sequence of Operation Compressor OperationDefrost Speedup Check Charge TWO Stage Communicating 167A/266A Airflow Selections for ECM Furnaces non communicatingIndoor Thermostat Control Options Defrost Hold Evolution Controlled Low Ambient CoolingMajor Components Communication and Status Function Lights Outdoor Fan Motor OperationFor Evolution Control only, Green communications Comm Light 2230V Brown-Out Protection Defeated Thermistor Curve No 230V at Compressor ContactorOutdoor Coil Thermistor OCT Attachment Status Codes 167A / 266A TroubleshootingCare and Maintenance Puronr R-410A Refrigerant Quick Reference Guide Final Check-OutAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle TWO-STAGE 286B/288B 180B/187B Index of TablesDescription Table # TWO-STAGE 286A/288A 180A/187ACatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.