Bryant R-22 service manual Outdoor Coil Thermistor OCT Attachment

Page 76

The thermistor comparison is not performed during low ambient cooling or defrost operation.

Failed Thermistor Default Operation

Factory defaults have been provided in the event of failure of outdoor air thermistor (OAT) and/or outdoor coil thermistor (OCT).

If the OAT sensor should fail, low ambient cooling will not be allowed and the one-minute outdoor fan off delay will not occur. Defrost will be initiated based on coil temperature and time.

OAT Thermistor must be locked in place with spherical nib end facing towards the front of the control box

If the OCT sensor should fail, low ambient cooling will not be allowed. Defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.

If there is a thermistor out of range error, defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.

Count the number of short and long flashes to determine the appropriate flash code. Table 23 gives possible causes and actions related to each error.

OCT Thermistor must be secured tight on stub tube.

Fig. 57 – Outdoor Air Thermistor (OAT) Attachment

Fig. 58 – Outdoor Coil Thermistor (OCT) Attachment

76

Image 76
Contents Table of Contents Application GuidelineTable of Contents TWO Stage NON-COMMUNICATING TWO Stage CommunicatingAIR Conditioner and Heat Pump Model Number Nomenclature Serial Number NomenclatureInstallation Guideline Safety ConsiderationsIntroduction Required Field-Installed Accessories for Air Conditioners AccessoriesRequired Field-Installed Accessories for Heat Pumps Accessory Descriptions Base / Mid-Tier / Deluxe 4-sided Baffle Assembly LOW-AMBIENT Cooling GuidelineDeluxe 3-sided Baffle Assembly and Dimensions Long Line Guideline Cabinet AssemblyBasic Cabinet Designs Access Compressor Or Other Internal Cabinet Components Legacy RNC and Legacy Line Control Box Identification Labeling Figure LabelsAluminum Wire ElectricalContactor CapacitorCrankcase Heater Time-Delay RelayCycle Protector Pressure Switches Personal Injury HazardDefrost Thermostat Defrost Control BoardTroubleshooting HK32EA001 If outdoor unit will not run Defrost SpeedupIf defrost thermostat is stuck closed If defrost thermostat is stuck openFive-Minute Compressor Delay Quiet ShiftCooling HeatingTroubleshooting HK32EA003 Fan MotorCompressor Plug Low-Voltage TerminalsCompressor Failures Mechanical FailuresLocked Rotor Runs, Does Not PumpNoisy Compressor Split Post Grommet part number KA75UG100Electrical Failures Single-Phase MotorsUnit Personal Injury Hazard Refrigerant Refrigeration SystemCompressor Oil Synthetic Roof Precautionary Procedure Servicing Systems on Roofs With Synthetic MaterialsBrazing Oil ChargingPumpdown Procedure Service Valves and PumpdownPersonal Injury and Unit Damage Hazard Heating Piston AccuRaterr Heat Pumps Only AccuRaterr Components Used in R-22 Heat PumpsReversing Valve Reversing Valve Heating Mode, Solenoid De-EnergizedLiquid Line Filter Drier Install Liquid-line Filter Drier Indoor ACSuction Line Filter Drier Accumulator AccumulatorInstall TXV Thermostatic Expansion Valve TXVTXV Operation Unit Operation HazardMake Piping Connections Replacing TXV on an Indoor Coil pre-2006Replacing TXV on Indoor Coil post-2006 Personal Injury and Environmental HazardRefrigeration System Repair Leak DetectionCoil Removal Fire HazardCompressor Removal and Replacement System Clean-Up After BurnoutEvacuation Check ChargeDeep Vacuum Method Troubleshooting with Superheat Basic DiagnosticsLow Superheat with Normal or Low Suction Pressure Low Superheat with High Suction PressureHunting Superheat High Superheat with Normal or High Suction PressurePseudo Evaporator Superheat Instructions Puron System Suction Pressure Drop Example22 System Suction Pressure Drop PuronrRefrigerant Pressure Temperature Chart Psig22 Refrigerant Pressure Temperature Relationship PsigPuron Subcooling Chart Liquid Line Temperature F Liq Press Subcooling F PsigPuron Superheat Chart Superheat F Psig22 Subcooling Chart Liquid Line Temperature F PT F Subcooling F Pres Psig22 Superheat Chart TWO-STAGE Application GuidelinesModel Plug Model Plug InformationGeneral Information Low Ambient CoolingDefrost Airflow Selection for 315AAV/355AAV FurnacesLiquid-Line Solenoid Accessory Defrost HoldForced Defrost All 286A units must be charged in high stage onlyOne Minute Stage Change Time Delay on 286ANA/187ANA Models Cooling and Heating OperationUtility Interface With Evolution Control Compressor Operation on 286ANA/187ANA ModelsECM Fan Motor Troubleshooting Outdoor Fan Motor OperationMuffler, Accumulator, Reversing Valve RVS Time DelaysThermistors Control BOX Troubleshooting 230V Line Power Disconnect Detection 230v Brown-Out Protection DefeatedCompressor Voltage Sensing Contactor Shorted DetectionUnloader Test Procedure Temperature ThermistorsFailed Thermistor Default Operation Thermistor Sensor ComparisonTroubleshooting Status CodesEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 TWO-STAGE 286B/289B/180B/187B General Information Heating Check Chart Procedure All 286B units must be charged in high stage onlyCompressor Operation on 289B/180B Models Low Stage High Stage Low & High Model Incoming Power Troubleshooting 187B & 286B Start CircuitControl Box Contactor And CapacitorTroubleshooting HK38EA015 circuit board 286B Models Compressor Thermal Cutout 289B Compressor Thermal CutoutOutdoor Coil Thermistor OCT Attachment Status Codes Single Stage Furnace with 2-Stage Air Conditioner TWO Stage NON-COMMUNICATING 127A/226A Operating AmbientAirflow Selections ECM Furnaces Airflow Selection for FV4C Fan Coils non-communicatingCompressor Operation System Function and Sequence of OperationDefrost Speedup Check Charge Airflow Selections for ECM Furnaces non communicating TWO Stage Communicating 167A/266AIndoor Thermostat Control Options Evolution Controlled Low Ambient Cooling Defrost HoldMajor Components Outdoor Fan Motor Operation Communication and Status Function LightsFor Evolution Control only, Green communications Comm Light 2230V Brown-Out Protection Defeated No 230V at Compressor Contactor Thermistor CurveOutdoor Coil Thermistor OCT Attachment 167A / 266A Troubleshooting Status CodesCare and Maintenance Final Check-Out Puronr R-410A Refrigerant Quick Reference GuideAIR Conditioner Troubleshooting Chart Heat Pump Troubleshooting Heating Cycle Heat Pump Troubleshooting Cooling Cycle Index of Tables Description Table #TWO-STAGE 286A/288A 180A/187A TWO-STAGE 286B/288B 180B/187BCatalog No. SM01---6
Related manuals
Manual 52 pages 54.32 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.