Bard I30H1, I60H1, I42H1D, I36H1D Factory BUILT-IN Electric Heat Table, Indoor Blower Performance

Page 5

I-TEC Series General Information

I-TEC MODEL NOMENCLATURE

I 36 H

1 D A 0Z

R

P

4

X X

2

 

 

 

 

 

 

MODEL

SYSTEM TYPE:

SERIES

HEAT PUMP

NOMINAL

 

REVISION

CAPACITY

 

 

 

30

= 30,000 BTUH

SPECIAL UNITS

36

=

36,000

 

(–) = Standard

42

= 42,000

 

D = Dehum.

48

=

48,000

 

 

60

=

60,000

 

 

VOLTS & PHASE

A= 230/208, 60-1

B= 230/208, 60-3

C= 460-60-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLS

 

 

 

 

 

 

COLOR OPTIONS

 

 

 

 

ELECTRIC HEAT

 

 

X - Beige paint

 

 

 

 

X = 24V Terminal Block Only w/o

0Z = No heat w/breaker

 

 

 

 

 

1

- White paint

 

 

 

 

CompleteStat

04

= 4KW

1-Phase

 

 

 

 

4

- Gray paint

 

 

 

 

1 = CompleteStat THO (Temp,

05

= 5KW

1-Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity & Occupancy)

06

= 6KW

3-Phase

 

 

 

 

 

 

 

 

 

2 = CompleteStat THO w/CO2

09

= 9KW

3-Phase

FILTER OPTIONS

 

 

 

 

3 = CompleteStat THO w/Ethernet

10

= 10KW 1-Phase

P = 2" Pleated MERV 8

 

 

 

 

4 = CompleteStat THO w/CO2 &

15

= 15KW 1 & 3-Phase

M = 2" Pleated MERV 11

 

 

 

Ethernet

18

= 18KW 3-Phase

N = 2" Pleated MERV 13

 

 

 

 

 

 

 

 

Note: CompleteStat must be field

20

= 20KW 1-Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

installed & wired. All units have

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24V terminal block.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTILATION OPTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COIL TREATMENT

 

B = Blank-Off Plate

 

 

 

 

 

 

M = Multi-Speed CRV

 

 

 

 

 

X - Std. Hydrophilic Fin Evap. &

 

N = Comb. CRV & DB Economizer

 

 

 

 

Uncoated Alum. Cond. Coil

 

R = ERV

 

 

 

 

 

 

 

1 - Phenolic Coated ID Coil

 

 

 

 

 

RESERVED

2 - Phenolic Coated OD Coil

 

 

 

 

 

3 - Phenolic Coated ID & OD Coil

 

 

 

 

 

 

 

 

 

 

TABLE 1

FACTORY BUILT-IN ELECTRIC HEAT TABLE

Models

I30H1-A

I30H1-B

I30H1-C

I36H1-A

I36H1-B

I36H1-C

I48H1-A

I48H1-B

I48H1-C

I60H1-A

I42H1-A

I42H1-B

I42H1-C

I60H1-B

I60H1-C

 

 

 

 

 

 

 

 

 

 

KW

240V-1

208V-1

240V-3

208V-3

460V-3

240V-1

208V-1

240V-3

208V-3

460V-3

240V-1

208V-1

240V-3

208V-3

460V-3

240V-1

208V-1

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

BTUH

 

4.0

 

 

 

 

 

 

 

 

 

 

13,652

10,239

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

17,065

12,799

 

 

 

17,065

12,799

 

 

 

17,065

12,799

 

 

 

17,065

12,799

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.0

 

 

20,478

15,359

20,478

 

 

20,478

15,359

20,478

 

 

20,478

15,359

20,478

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.0

 

 

30,717

23,038

30,717

 

 

30,717

23,038

30,717

 

 

30,717

23,038

30,717

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.0

34,130

25,598

 

 

 

34,130

25,598

 

 

 

34,130

25,598

 

 

 

34,130

25,598

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15.0

 

 

 

 

 

51,195

38,396

51,195

38,396

51,195

51,195

38,396

51,195

38,396

51,195

51,195

38,396

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18.0

 

 

 

 

 

 

 

 

 

 

 

 

61,434

46,076

61,434

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20.0

 

 

 

 

 

 

 

 

 

 

68,260

51,195

 

 

 

68,260

51,195

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 1A

INDOOR BLOWER PERFORMANCE 1

 

 

 

2

 

 

3

4

 

 

 

Continuous

Rated 2nd

Rated 1st

5 - 9 KW

13.5 - 18

Model

Rated ESP

Max. ESP

CFM

Stage CFM

Stage CFM

CFM

KW CFM

I30H1

.15

0.50

500

900

650

700

1400

 

 

 

 

 

 

 

 

I36H1

.15

0.50

600

1150

850

700

1400

 

 

 

 

 

 

 

 

I42H1

.20

0.50

650

1300

950

700

1400

 

 

 

 

 

 

 

 

I48H1

.20

0.50

725

1500

1050

700

1400

 

 

 

 

 

 

 

 

I60H1

.20

0.50

850

1700

1200

700

1400

 

 

 

 

 

 

 

 

1Motor will deliver consistent CFM through voltage supply range with no deterioration.

2 Continuous fan CFM is the total air being circulated during continuous fan mode.

3 Will operate at rated Full Load Airflow when operating with Heat Pump.

4Will occur automatically with a call for "W3" or "Emergency Heat" signal from the thermostat (Heat Pump Operation is terminated at this condition).

Manual

2100-549G

Page

5 of 59

Image 5
Contents TEC Series Packaged Heat Pump Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsAnsi Z535.5 Definitions GeneralIndoor Blower Performance Factory BUILT-IN Electric Heat TableElectrical Specifications Unit Dimensions Unit Specification SheetHandling Unit After Removal from Skid Shipping DamageUnit Removal from Skid Wall Mounting Bracket Location Minimum Installation HeightSeismic Considerations Bracket Wall Section View Center of Gravity Center of GravityRequired Clearances & Recommended Access Removal of AIR Duct Compressor Shipping BoltsDucted Application Basic Unit 3 Riser Application 6 Riser Application Filters Duct WorkSupply Duct Connections Filter LocationCondensate Drain With Energy Recovery VentilatorWith no Vent Option With Commercial Room Ventilator16 3/4 NON-TAPPING 16 1/2 NON-TAPPING Unit MountingTEC Unit Component Location Wiring Main PowerMounting the Unit LOW Voltage Connections Wiring LOW Voltage WiringOperating Voltage Range Wall ThermostatsSC SC SC Basic Heat Pump with no Ventilation PackageHeat Pump with CRV, Without CO2 Control Y2 B/W1 W2 W3 CRV Wiring HarnessTo function Heat Pump with CRV and CO2 ControlHeat Pump with ERV, Without CO2 Control ERV Wiring HarnessHeat Pump with ERV and CO2 Control ON/OFF Cycling Heat Pump with ERV and CO2 Control Fully Modulating ERV Wiring Harness Bard #8403-067Heat Pump with Combination CRV and DB Economizer N Vent Code Topping OFF System Charge Safety PracticesPhase Monitor Important Installer NoteThree Phase Scroll Compressor Start UP Information Service HintsSound Pressure Service PortsSequence of Operation Defrost Cycle Defrost CycleSetting the Ventilation CFM Levels Control WiringTeccommercial Room Ventilator System General Description Recommended Control SequencesVent Option INTAKE/EXHAUST Speeds CRV Motor SPEED/CFM ConfigurationCRV Speed Change Terminal Access Control Wiring Economizer Control Circuit TECECON. Sequence of OperationMotor SPEED/CFM Configuration Heating Mode OperationVentilation Mode Tecenergy Recovery Ventilator System General Description Changing to Fully Modulating Mode Changing Ventilation CFM Rates in Manual ModeWinter Heating Performance Indoor Design Conditions 70F DB Performance and Application DataERV Modulating Mode Jumper PIN on P Terminal ERV Manual Mode Jumper PIN on M TerminalIndoor Air Supply Air Outdoor Air Ventilation Airflow DiagramERV Access Control Board CONFIGURATION/SETTING SpecificationsAccessing Menu Parameters WiringMounting Selection of Voltage OutputsMenu Descriptions Cleanability and Performance Energy Recovery Ventilator Maintenance General InformationMaintenance Procedures Quarterly Maintenance FrequencyAnnual Maintenance Codes Function Solid State Heat Pump Control Troubleshooting ProcedureTroubleshooting Temperature F VS Resistance R of Temperature Sensor Checking Temperature SensorTroubleshooting ECM 142R Outdoor FAN Motor Cooling Mode Troubleshooting ECM 142R Outdoor FAN MotorHeat Pump Mode Replacing the MotorTroubleshooting Indoor ECM Blower Motors Troubleshooting Indoor ECM Blower Motors Cont’d Control Connector Motor Half FAN Blade Setting DimensionsPower Connector Motor Half Refrigerant ChargeFull Load Heating PRESSURE/TEMPERATURE Full Load Cooling PRESSURE/TEMPERATUREPart Load Heating PRESSURE/TEMPERATURE Part Load Cooling PRESSURE/TEMPERATURE