Bard I42H1D, I36H1D, I30H1, I60H1D Mounting the Unit, Wiring Main Power, Component Location

Page 21

INSTALLATION INSTRUCTIONS

MOUNTING THE UNIT

The wall sleeve is attached to the I-TEC unit from the outside of the building. See Figures 11A & 11B. Refer to wall sleeve Manual 2100-562 supplied with sleeve.

Following are the steps for attaching the I-TEC to the wall sleeve.

1.Lift the unit into place making sure that it is aligned side to side.

2.Push the unit back until the rear panel touches the sleeve gasket.

3.This unit must be level from side to side and from front to back. If adjustments are necessary, shim up under the base rails with sheets of metal or any substance not affected by moisture.

4.Attach the sleeve to the unit using the ten (10) ¾" long self-tapping screws supplied with the sleeve.

5.The exhaust sleeve has three (3) ¾" long screw slots in each side flange. Line these up with the screw engagement holes in the fan panel. Attach using six

(6)¾" long pointed sheet metal screws supplied with the sleeve. Extend the sleeve out until it is flush with the louver grill attachment angles.

6.Lock the sleeve in place using two (2) ½" long pointed sheet metal screws on each side by shooting through the slot into a pre-punched hole.

7.A bottom trim piece is shipped loose for installation beneath the doors. Attach the trim piece to the unit with screws provided.

8.The compressor is secured to the base with two

(2)bolts for shipping. Both bolts are identified with a tag. Remove shipping bolts (Figure 5).

WIRING – MAIN POWER

Refer to the unit rating plate and/or Table 2 for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only suitable for at least

75°C”. THESE INSTRUCTIONS MUST BE ADHERED TO. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection, and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

See “START UP” section for information on three phase scroll compressor start-ups.

The field wiring conduit connections are located on the top right-hand corner of the unit with a wire raceway to feed the wires down to the circuit breaker(s). See Figure 12.

 

 

 

 

 

 

 

FIGURE 12

 

 

 

 

COMPONENT LOCATION

ELECTRIC HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE RACEWAY

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVAPORATOR COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL PANEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT PORT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT OPTION

Manual

2100-549G

Page

21 of 59

Image 21
Contents TEC Series Packaged Heat Pump Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsAnsi Z535.5 Definitions GeneralIndoor Blower Performance Factory BUILT-IN Electric Heat TableElectrical Specifications Unit Dimensions Unit Specification SheetShipping Damage Unit Removal from SkidHandling Unit After Removal from Skid Minimum Installation Height Seismic ConsiderationsWall Mounting Bracket Location Bracket Wall Section View Center of Gravity Center of GravityRequired Clearances & Recommended Access Removal of AIR Duct Compressor Shipping BoltsDucted Application Basic Unit 3 Riser Application 6 Riser Application Filters Duct WorkSupply Duct Connections Filter LocationCondensate Drain With Energy Recovery VentilatorWith no Vent Option With Commercial Room Ventilator16 3/4 NON-TAPPING 16 1/2 NON-TAPPING Unit MountingTEC Unit Wiring Main Power Mounting the UnitComponent Location LOW Voltage Connections Wiring LOW Voltage WiringOperating Voltage Range Wall ThermostatsSC SC SC Basic Heat Pump with no Ventilation PackageHeat Pump with CRV, Without CO2 Control Y2 B/W1 W2 W3 CRV Wiring HarnessTo function Heat Pump with CRV and CO2 ControlHeat Pump with ERV, Without CO2 Control ERV Wiring HarnessHeat Pump with ERV and CO2 Control ON/OFF Cycling Heat Pump with ERV and CO2 Control Fully Modulating ERV Wiring Harness Bard #8403-067Heat Pump with Combination CRV and DB Economizer N Vent Code Topping OFF System Charge Safety PracticesPhase Monitor Important Installer NoteThree Phase Scroll Compressor Start UP Information Service HintsPressure Service Ports Sequence of OperationSound Defrost Cycle Defrost CycleSetting the Ventilation CFM Levels Control WiringTeccommercial Room Ventilator System General Description Recommended Control SequencesVent Option INTAKE/EXHAUST Speeds CRV Motor SPEED/CFM ConfigurationCRV Speed Change Terminal Access Control Wiring Economizer Control Circuit TECECON. Sequence of OperationHeating Mode Operation Ventilation ModeMotor SPEED/CFM Configuration Tecenergy Recovery Ventilator System General Description Changing to Fully Modulating Mode Changing Ventilation CFM Rates in Manual ModeWinter Heating Performance Indoor Design Conditions 70F DB Performance and Application DataERV Modulating Mode Jumper PIN on P Terminal ERV Manual Mode Jumper PIN on M TerminalIndoor Air Supply Air Outdoor Air Ventilation Airflow DiagramERV Access Control Board CONFIGURATION/SETTING SpecificationsAccessing Menu Parameters WiringMounting Selection of Voltage OutputsMenu Descriptions Cleanability and Performance Energy Recovery Ventilator Maintenance General InformationMaintenance Procedures Quarterly Maintenance FrequencyAnnual Maintenance Solid State Heat Pump Control Troubleshooting Procedure TroubleshootingCodes Function Temperature F VS Resistance R of Temperature Sensor Checking Temperature SensorTroubleshooting ECM 142R Outdoor FAN Motor Cooling Mode Troubleshooting ECM 142R Outdoor FAN MotorHeat Pump Mode Replacing the MotorTroubleshooting Indoor ECM Blower Motors Troubleshooting Indoor ECM Blower Motors Cont’d Control Connector Motor Half FAN Blade Setting DimensionsPower Connector Motor Half Refrigerant ChargeFull Load Heating PRESSURE/TEMPERATURE Full Load Cooling PRESSURE/TEMPERATUREPart Load Heating PRESSURE/TEMPERATURE Part Load Cooling PRESSURE/TEMPERATURE