Bard I30H1D, I60H1 Shipping Damage, Unit Removal from Skid, Handling Unit After Removal from Skid

Page 8

SHIPPING DAMAGE

Upon receipt of equipment, the unit should be checked for external signs of shipping damage. The skid must remain attached until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

UNIT REMOVAL FROM SKID

WARNING

This unit is heavy and requires more than one person to handle during installation and removal from the skid. Extreme caution must be taken to prevent injury to personnel and damage to the unit. Use appropriate safety equipment, including gloves when handling. Failure to do so may result in serious injury.

A forklift or a lift rated for the load (Figure 2A) is required to lift the unit off from the skid. This unit is top heavy and should never be tipped while moving it.

The I-TEC is designed to be lifted off the skid from the front or rear of the unit without having to remove any doors or side panels. See Figure 1 for fork openings. The shipping brackets on front and rear of the unit must be removed and discarded. The unit can now be lifted straight up and the skid can be slid out from underneath.

Tip unit from left side only.

Failure to do so may result in injury due to unit

top-heaviness or compressor damage!

FIGURE 2A — UNIT ON LIFT

HANDLING UNIT AFTER REMOVAL FROM SKID

If a wide and tall enough opening exists, the I-TEC can be moved as a complete assembled unit. If not, it is designed to break down into two sections to allow it to pass through a 36 inch wide door.

1.Depress & release both top & bottom door latches and open doors.

2.Remove the doors by lifting straight up and off from the hinge pins.

3.Remove cabinet sides by first removing the four (4) sheet metal screws from the front (leading edge) of the side panel. The panel will not fall off. Swing the panel away from the chassis 20 to 30 degrees & then pull forward from the two (2) tabs supporting the rear edge.

4.On each side of the unit is a tie plate that secures the top and bottom sections with four (4) cap bolts. Using a ½ inch wrench or socket, remove these screws from both plates and set aside.

5.If the unit is equipped with a CRV or ERV, you must unplug the wire harness on the left-hand side of the control box.

6.A forklift or a lift rated for the load is required to lift the top section off from the bottom base. Do not attempt to do this manually. Failure to do so could result in the unit tipping over & causing bodily injury and/or damage to the unit.

7.The top section can be forked from either the RH or LH side. See Figure 1 for fork openings.

8.Carefully lift the top section straight up avoiding tipping.

9.Move the top section through the doorway and place on flat surface free of debris.

10.The bottom base can now be moved through the doorway the same way.

11.Reassemble the unit by reversing this procedure.

FIGURE 2B UNIT SIDE

É

ERV/CRV

HARNESS CONNECTION

 

(4) CAP BOLTS

FORK OPENING

É

(Visible after

 

removing tie plate)

É

 

É

TIE PLATE

(Covers entire width; shortened for illustration purposes to show Fork Openings)

Manual

2100-549G

Page

8 of 59

Image 8
Contents TEC Series Packaged Heat Pump Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersGeneral Ansi Z535.5 DefinitionsFactory BUILT-IN Electric Heat Table Indoor Blower PerformanceElectrical Specifications Unit Specification Sheet Unit DimensionsHandling Unit After Removal from Skid Shipping DamageUnit Removal from Skid Wall Mounting Bracket Location Minimum Installation HeightSeismic Considerations Bracket Wall Section View Center of Gravity Center of GravityRequired Clearances & Recommended Access Compressor Shipping Bolts Removal of AIR DuctDucted Application Basic Unit 3 Riser Application 6 Riser Application Duct Work FiltersSupply Duct Connections Filter LocationWith Energy Recovery Ventilator Condensate DrainWith no Vent Option With Commercial Room VentilatorUnit Mounting 16 3/4 NON-TAPPING 16 1/2 NON-TAPPINGTEC Unit Component Location Wiring Main PowerMounting the Unit Wiring LOW Voltage Wiring LOW Voltage ConnectionsOperating Voltage Range Wall ThermostatsBasic Heat Pump with no Ventilation Package SC SC SCY2 B/W1 W2 W3 CRV Wiring Harness Heat Pump with CRV, Without CO2 ControlHeat Pump with CRV and CO2 Control To functionERV Wiring Harness Heat Pump with ERV, Without CO2 ControlHeat Pump with ERV and CO2 Control ON/OFF Cycling ERV Wiring Harness Bard #8403-067 Heat Pump with ERV and CO2 Control Fully ModulatingHeat Pump with Combination CRV and DB Economizer N Vent Code Safety Practices Topping OFF System ChargeImportant Installer Note Phase MonitorThree Phase Scroll Compressor Start UP Information Service HintsSound Pressure Service PortsSequence of Operation Defrost Cycle Defrost CycleControl Wiring Setting the Ventilation CFM LevelsTeccommercial Room Ventilator System General Description Recommended Control SequencesCRV Motor SPEED/CFM Configuration Vent Option INTAKE/EXHAUST SpeedsCRV Speed Change Terminal Access Control Wiring TECECON. Sequence of Operation Economizer Control CircuitMotor SPEED/CFM Configuration Heating Mode OperationVentilation Mode Tecenergy Recovery Ventilator System General Description Changing Ventilation CFM Rates in Manual Mode Changing to Fully Modulating ModePerformance and Application Data Winter Heating Performance Indoor Design Conditions 70F DBERV Manual Mode Jumper PIN on M Terminal ERV Modulating Mode Jumper PIN on P TerminalVentilation Airflow Diagram Indoor Air Supply Air Outdoor AirERV Access Specifications Control Board CONFIGURATION/SETTINGWiring Accessing Menu ParametersMounting Selection of Voltage OutputsMenu Descriptions Energy Recovery Ventilator Maintenance General Information Cleanability and PerformanceMaintenance Procedures Quarterly Maintenance FrequencyAnnual Maintenance Codes Function Solid State Heat Pump Control Troubleshooting ProcedureTroubleshooting Checking Temperature Sensor Temperature F VS Resistance R of Temperature SensorTroubleshooting ECM 142R Outdoor FAN Motor Troubleshooting ECM 142R Outdoor FAN Motor Cooling ModeHeat Pump Mode Replacing the MotorTroubleshooting Indoor ECM Blower Motors Troubleshooting Indoor ECM Blower Motors Cont’d FAN Blade Setting Dimensions Control Connector Motor HalfPower Connector Motor Half Refrigerant ChargeFull Load Cooling PRESSURE/TEMPERATURE Full Load Heating PRESSURE/TEMPERATUREPart Load Cooling PRESSURE/TEMPERATURE Part Load Heating PRESSURE/TEMPERATURE