Bard I30H1D, I60H1 Full Load Cooling PRESSURE/TEMPERATURE, Full Load Heating PRESSURE/TEMPERATURE

Page 58

TABLE 10A

FULL LOAD COOLING PRESSURE/TEMPERATURE

 

RETURN

 

 

 

 

AIR TEMPERATURE ENTERING OUTDOOR COIL °F

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

MODEL

TEMP.

PRESSURE

 

75 DB

Low Side

117

118

120

121

123

124

126

128

129

130

132

133

135

136

137

 

62 WB

High Side

202

224

246

267

289

310

332

354

375

399

423

448

472

496

520

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I30H1

80 DB

Low Side

130

131

133

134

136

139

140

141

142

144

145

147

148

150

151

67 WB

High Side

201

225

248

271

294

315

345

362

386

411

436

461

486

510

535

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

145

146

148

149

151

152

154

156

157

159

160

162

164

165

167

 

72 WB

High Side

210

233

256

278

301

323

346

369

391

416

442

467

492

517

542

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

126

127

129

130

131

132

134

135

136

137

138

139

141

142

143

 

62 WB

High Side

209

231

252

274

295

317

338

360

381

405

429

452

476

500

524

I36H1

80 DB

Low Side

139

140

142

143

144

146

147

148

149

150

152

153

154

155

157

67 WB

High Side

208

231

254

277

300

327

358

370

392

417

441

466

490

515

539

 

 

85 DB

Low Side

154

155

157

158

159

160

162

163

164

165

167

168

170

171

172

 

72 WB

High Side

217

240

262

285

307

330

352

375

397

422

447

471

496

521

540

 

75 DB

Low Side

122

123

125

127

128

130

131

133

134

135

136

137

138

139

140

 

62 WB

High Side

218

238

258

279

299

319

339

360

380

404

428

452

476

500

524

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I42H1

80 DB

Low Side

134

136

138

139

141

142

144

146

147

148

149

150

151

152

153

67 WB

High Side

217

239

260

282

304

326

355

369

391

416

440

465

490

514

539

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

139

140

142

143

144

145

147

148

149

150

151

152

153

154

155

 

72 WB

High Side

226

247

269

290

311

332

353

375

396

421

446

471

496

521

546

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

125

126

127

128

129

129

130

131

132

134

135

136

138

139

140

 

62 WB

High Side

203

225

248

271

293

316

339

361

384

411

437

464

491

517

544

I48H1

80 DB

Low Side

136

138

139

140

141

143

144

145

147

148

150

151

153

154

156

67 WB

High Side

208

231

254

276

299

321

351

367

390

417

444

471

498

526

553

 

 

85 DB

Low Side

148

149

151

153

154

156

158

159

161

162

164

166

167

169

171

 

72 WB

High Side

215

238

261

284

307

331

354

377

400

428

456

484

512

539

567

 

75 DB

Low Side

123

124

124

125

126

127

128

129

129

131

132

133

134

135

136

 

62 WB

High Side

218

241

265

289

312

336

360

383

407

434

462

489

516

544

571

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I60H1

80 DB

Low Side

134

135

137

138

139

140

141

142

143

145

146

147

148

150

151

67 WB

High Side

224

248

271

295

319

341

373

389

413

441

469

497

524

552

580

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

146

147

148

150

151

153

154

156

157

159

160

161

163

164

166

 

72 WB

High Side

231

255

279

303

327

352

376

400

424

453

481

510

538

567

595

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 10B

FULL LOAD HEATING PRESSURE/TEMPERATURE

 

RETURN

 

 

 

 

AIR TEMPERATURE ENTERING OUTDOOR COIL °F

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

MODEL

TEMP.

PRESSURE

I30H1

70° DB

Low Side

33

40

48

55

63

70

78

85

91

98

107

116

125

134

143

High Side

247

257

267

277

287

296

306

316

317

319

345

371

398

424

451

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I36H1

70° DB

Low Side

30

38

45

52

59

67

74

81

89

97

105

112

120

127

135

High Side

244

252

259

267

275

283

290

298

305

311

320

328

337

345

354

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I42H1

70° DB

Low Side

34

40

47

54

60

67

74

81

88

95

102

109

116

123

130

High Side

255

263

271

278

286

294

301

309

314

319

325

331

337

343

349

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I48H1

70° DB

Low Side

33

40

47

54

60

67

74

81

89

97

106

114

122

130

138

High Side

268

276

285

293

301

309

318

326

334

342

349

356

363

370

377

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I60H1

70° DB

Low Side

38

42

46

50

54

58

63

67

80

94

102

110

118

127

135

High Side

290

294

297

300

303

306

310

313

335

357

366

375

384

393

402

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

2100-549G

Page

58 of 59

Image 58
Contents TEC Series Packaged Heat Pump Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersGeneral Ansi Z535.5 DefinitionsFactory BUILT-IN Electric Heat Table Indoor Blower PerformanceElectrical Specifications Unit Specification Sheet Unit DimensionsUnit Removal from Skid Shipping DamageHandling Unit After Removal from Skid Seismic Considerations Minimum Installation HeightWall Mounting Bracket Location Bracket Wall Section View Center of Gravity Center of GravityRequired Clearances & Recommended Access Compressor Shipping Bolts Removal of AIR DuctDucted Application Basic Unit 3 Riser Application 6 Riser Application Supply Duct Connections Duct WorkFilters Filter LocationWith no Vent Option With Energy Recovery VentilatorCondensate Drain With Commercial Room VentilatorUnit Mounting 16 3/4 NON-TAPPING 16 1/2 NON-TAPPINGTEC Unit Mounting the Unit Wiring Main PowerComponent Location Operating Voltage Range Wiring LOW Voltage WiringLOW Voltage Connections Wall ThermostatsBasic Heat Pump with no Ventilation Package SC SC SCY2 B/W1 W2 W3 CRV Wiring Harness Heat Pump with CRV, Without CO2 ControlHeat Pump with CRV and CO2 Control To functionERV Wiring Harness Heat Pump with ERV, Without CO2 ControlHeat Pump with ERV and CO2 Control ON/OFF Cycling ERV Wiring Harness Bard #8403-067 Heat Pump with ERV and CO2 Control Fully ModulatingHeat Pump with Combination CRV and DB Economizer N Vent Code Safety Practices Topping OFF System ChargeThree Phase Scroll Compressor Start UP Information Important Installer NotePhase Monitor Service HintsSequence of Operation Pressure Service PortsSound Defrost Cycle Defrost CycleTeccommercial Room Ventilator System General Description Control WiringSetting the Ventilation CFM Levels Recommended Control SequencesCRV Motor SPEED/CFM Configuration Vent Option INTAKE/EXHAUST SpeedsCRV Speed Change Terminal Access Control Wiring TECECON. Sequence of Operation Economizer Control CircuitVentilation Mode Heating Mode OperationMotor SPEED/CFM Configuration Tecenergy Recovery Ventilator System General Description Changing Ventilation CFM Rates in Manual Mode Changing to Fully Modulating ModePerformance and Application Data Winter Heating Performance Indoor Design Conditions 70F DBERV Manual Mode Jumper PIN on M Terminal ERV Modulating Mode Jumper PIN on P TerminalVentilation Airflow Diagram Indoor Air Supply Air Outdoor AirERV Access Specifications Control Board CONFIGURATION/SETTINGMounting WiringAccessing Menu Parameters Selection of Voltage OutputsMenu Descriptions Maintenance Procedures Quarterly Maintenance Energy Recovery Ventilator Maintenance General InformationCleanability and Performance FrequencyAnnual Maintenance Troubleshooting Solid State Heat Pump Control Troubleshooting ProcedureCodes Function Checking Temperature Sensor Temperature F VS Resistance R of Temperature SensorTroubleshooting ECM 142R Outdoor FAN Motor Heat Pump Mode Troubleshooting ECM 142R Outdoor FAN MotorCooling Mode Replacing the MotorTroubleshooting Indoor ECM Blower Motors Troubleshooting Indoor ECM Blower Motors Cont’d Power Connector Motor Half FAN Blade Setting DimensionsControl Connector Motor Half Refrigerant ChargeFull Load Cooling PRESSURE/TEMPERATURE Full Load Heating PRESSURE/TEMPERATUREPart Load Cooling PRESSURE/TEMPERATURE Part Load Heating PRESSURE/TEMPERATURE