Bard I48H1D, I42H1D, I36H1D, I60H1D, I30H1D installation instructions Control Wiring

Page 37

I-TECCOMBINATION CRV & ECONOMIZER VENTILATION SYSTEM

DESCRIPTION

The I-TEC combination Commercial Room Ventilator (CRV) and Dry Bulb Economizer is designed to be used with all Bard I-TEC models. This ventilation package and its control provides two (2) roles:

It will provide the required ventilation by delivering fresh air to meet I.A.Q. (Indoor Air Quality) requirements through CRV portion of the device.

It will provide up to 525 CFM of free outdoor cooling CFM when the outdoor ambient temperature is below the outdoor thermostat setpoint.

Operating the I-TECCRV during unoccupied periods can result in a build up of excess moisture in the structure.

Ventilation is accomplished with (2) blower/motor assemblies for maximum ventilation at low sound levels. The intake and exhaust blowers are programmed independently and are balanced to maintain a slight positive pressurization in accordance to ASHRAE 62.1 Standard.

The Ventilation Package is also provided with filters to reduce the required service needed and to further improve the I.A.Q. The exhaust air blowers are protected by disposable filters, and the intake air blowers are protected by washable filters. Both are accessible without the need for tools.

CONTROL WIRING

Refer to Low Voltage Connection (Figure 19).

Reference Figure 23 for Control Sequence of Operation.

Open disconnect to shut all power OFF before doing this! Failure to do so could result in injury or death due to electrical shock.

SETTING THE VENTILATION CFM LEVELS

The I-TEC CRV has four (4) pre-set levels of ventilation CFM available. These are 300, 375, 450 and 525 CFM of ventilation air. This ventilation package is shipped from the factory set on the 375 CFM ventilation level while the Economizer portion is set on the 525 CFM ventilation level. To change between these four different levels of provided ventilation CFM, refer to Figure 24 to look up the corresponding CFM needed for the intake and exhaust blowers to meet the design criteria and determine which “speed/wire color” is needed.

Perform the following steps:

1.Open front swinging doors of main unit (by popping front door latches).

2.Throw main power disconnect to the “OFF” position to eliminate risk of injury or death due to electrical shock.

3.Remove six (6) screws holding front CRV door in place (see Figure 22).

4.For CRV blower speed, locate “Brown Wire with White Trace” that has as black terminal on the end where it connects to the terminal strip (see Figure 24).

5.Move the “Brown Wire with White Trace” to the corresponding CFM level needed in accordance with Figure 24.

6.For Economizer Blower Speed, locate “Pink Wire” that has a black terminal on the end where it connects to the terminal strip (see Figure 24).

7.Move the “Pink” to the corresponding CFM level needed in accordance with Figure 24.

Manual

2100-549G

Page

37 of 59

Image 37
Contents TEC Series Packaged Heat Pump Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsAnsi Z535.5 Definitions GeneralIndoor Blower Performance Factory BUILT-IN Electric Heat TableElectrical Specifications Unit Dimensions Unit Specification SheetUnit Removal from Skid Shipping DamageHandling Unit After Removal from Skid Seismic Considerations Minimum Installation HeightWall Mounting Bracket Location Bracket Wall Section View Center of Gravity Center of GravityRequired Clearances & Recommended Access Removal of AIR Duct Compressor Shipping BoltsDucted Application Basic Unit 3 Riser Application 6 Riser Application Filters Duct WorkSupply Duct Connections Filter LocationCondensate Drain With Energy Recovery VentilatorWith no Vent Option With Commercial Room Ventilator16 3/4 NON-TAPPING 16 1/2 NON-TAPPING Unit MountingTEC Unit Mounting the Unit Wiring Main PowerComponent Location LOW Voltage Connections Wiring LOW Voltage WiringOperating Voltage Range Wall ThermostatsSC SC SC Basic Heat Pump with no Ventilation PackageHeat Pump with CRV, Without CO2 Control Y2 B/W1 W2 W3 CRV Wiring HarnessTo function Heat Pump with CRV and CO2 ControlHeat Pump with ERV, Without CO2 Control ERV Wiring HarnessHeat Pump with ERV and CO2 Control ON/OFF Cycling Heat Pump with ERV and CO2 Control Fully Modulating ERV Wiring Harness Bard #8403-067Heat Pump with Combination CRV and DB Economizer N Vent Code Topping OFF System Charge Safety PracticesPhase Monitor Important Installer NoteThree Phase Scroll Compressor Start UP Information Service HintsSequence of Operation Pressure Service PortsSound Defrost Cycle Defrost CycleSetting the Ventilation CFM Levels Control WiringTeccommercial Room Ventilator System General Description Recommended Control SequencesVent Option INTAKE/EXHAUST Speeds CRV Motor SPEED/CFM ConfigurationCRV Speed Change Terminal Access Control Wiring Economizer Control Circuit TECECON. Sequence of OperationVentilation Mode Heating Mode OperationMotor SPEED/CFM Configuration Tecenergy Recovery Ventilator System General Description Changing to Fully Modulating Mode Changing Ventilation CFM Rates in Manual ModeWinter Heating Performance Indoor Design Conditions 70F DB Performance and Application DataERV Modulating Mode Jumper PIN on P Terminal ERV Manual Mode Jumper PIN on M TerminalIndoor Air Supply Air Outdoor Air Ventilation Airflow DiagramERV Access Control Board CONFIGURATION/SETTING SpecificationsAccessing Menu Parameters WiringMounting Selection of Voltage OutputsMenu Descriptions Cleanability and Performance Energy Recovery Ventilator Maintenance General InformationMaintenance Procedures Quarterly Maintenance FrequencyAnnual Maintenance Troubleshooting Solid State Heat Pump Control Troubleshooting ProcedureCodes Function Temperature F VS Resistance R of Temperature Sensor Checking Temperature SensorTroubleshooting ECM 142R Outdoor FAN Motor Cooling Mode Troubleshooting ECM 142R Outdoor FAN MotorHeat Pump Mode Replacing the MotorTroubleshooting Indoor ECM Blower Motors Troubleshooting Indoor ECM Blower Motors Cont’d Control Connector Motor Half FAN Blade Setting DimensionsPower Connector Motor Half Refrigerant ChargeFull Load Heating PRESSURE/TEMPERATURE Full Load Cooling PRESSURE/TEMPERATUREPart Load Heating PRESSURE/TEMPERATURE Part Load Cooling PRESSURE/TEMPERATURE