I-TEC COMMERCIAL ROOM
VENTILATOR SYSTEM
GENERAL DESCRIPTION
The
Ventilation is accomplished with (2) blower/motor assemblies for maximum ventilation at low sound levels. The intake and exhaust blowers are programmed independently and are balanced to maintain a slight positive pressurization in accordance to ASHRAE 62.1 Standard.
The
CONTROL WIRING
The
1.The indoor blower must be run whenever the
2.Select and configure the correct CFM ventilation level that the
3.Run the
Operating the
RECOMMENDED CONTROL SEQUENCES
Several possible scenarios are listed below:
1.Use a programmable electronic thermostat with auxiliary terminal to control the CRV based on daily programmed occupance periods. Bard markets and recommends Bard Part
2.Use Bard CompleteStat™ that incorporates temperature, humidity and occupancy control with learning capability into a single device. No programming required.
3.Use a DDC control system to control the CRV based upon a room occupancy schedule to control the CRV.
4.Tie the operation of the CRV into the light switch. The lights in a room are usually on only when occupied.
5.Use a manual timer that the occupants turn to energize the CRV for a specific number of hours.
6.Use a programmable mechanical timer to energize the CRV and indoor blower during occupied periods of the day.
NOTE: The ventilation package comes with a blower interlock function, but is disabled when it is shipped from the factory in case you do not utilize a thermostat with an occupancy output, or a occupancy sensor and must tie "A" terminal to "G" terminal to drive the ventilation package. If you do have a thermostat or control that does drive occupancy output, you will need to remove the tape from the orange wire located in the low voltage terminal box, and connect it to the "G" terminal to activate this function. (See Figures
SETTING THE VENTILATION CFM LEVELS
The
! | WARNING |
| |
HAZARD OF ELECTRICAL SHOCK. |
| ||
ELECTRICAL SHOCK CAN RESULT |
| ||
IN SERIOUS INJURY OR DEATH. | 2 | ||
DISCONNECT THE REMOTE | - | ||
ELECTRIC POWER SUPPLY OR | |||
7961 | |||
SUPPLIES BEFORE SERVICING. | |||
|
1.Open front swinging doors of main unit (by popping front door latches).
2.Throw main power disconnect to the “OFF” position to eliminate risk of injury or death due to electrical shock.
3.Remove six (6) screws holding front CRV door in place (See Figure 22).
4.Locate “Brown Wire with White Trace” that has a black terminal on the end where it connects to the terminal strip (See Figure 21).
5.Move “Brown Wire with White Trace” to the corresponding CFM level needed in accordance with Figure 21.
Manual | |
Page | 34 of 59 |