Bard I60H1, I42H1D Teccommercial Room Ventilator System General Description, Control Wiring

Page 34

I-TECCOMMERCIAL ROOM

VENTILATOR SYSTEM

GENERAL DESCRIPTION

The I-TEC Commercial Room Ventilator (CRV) is designed to be used with all Bard I-TEC models. The only intent of this device is to provide the required ventilation by delivering fresh air to meet I.A.Q. (Indoor Air Quality) requirements. In the installed application, this system also includes exhaust provisions which are balanced with the intake air to maintain building pressurization requirements of ASHRAE 62.1 Standard.

Ventilation is accomplished with (2) blower/motor assemblies for maximum ventilation at low sound levels. The intake and exhaust blowers are programmed independently and are balanced to maintain a slight positive pressurization in accordance to ASHRAE 62.1 Standard.

The I-TEC CRV is also provided with filters to reduce the required service needed and to further improve the I.A.Q. The exhaust air blowers are protected by disposable filters, and the intake air blowers are protected by washable filters. Both are accessible without the need for tools.

CONTROL WIRING

The I-TEC CRV comes wired from the factory set to 375 CFM of ventilation. Care must be taken when deciding how to control the operation of the ventilator. When designing the control circuit for the ventilator, the following requirements must be met.

1.The indoor blower must be run whenever the I-TEC CRV is run.

2.Select and configure the correct CFM ventilation level that the I-TEC CRV needs to operate and configure the system to this level following later instructions within this section. Over ventilating serves no useful purpose and significantly affects the overall efficiency of the heat pump system. System operating costs would also increase.

3.Run the I-TEC CRV only during periods when the conditioned space is occupied. Running the ventilation during unoccupied periods wastes energy, decreases the expected life of the CRV, and can result in large moisture buildup in the structure. Running the CRV when the structure is unoccupied allows moisture to build up in the structure because there is little or no cooling load. Thus, the air conditioner is not running enough to remove the excess moisture being brought in. Use a control system that in some way can control the system based upon occupancy.

Operating the I-TECCRV during unoccupied periods can result in a build up of excess moisture in the structure.

RECOMMENDED CONTROL SEQUENCES

Several possible scenarios are listed below:

1.Use a programmable electronic thermostat with auxiliary terminal to control the CRV based on daily programmed occupance periods. Bard markets and recommends Bard Part #8403-060 programmable electronic thermostat.

2.Use Bard CompleteStat™ that incorporates temperature, humidity and occupancy control with learning capability into a single device. No programming required.

3.Use a DDC control system to control the CRV based upon a room occupancy schedule to control the CRV.

4.Tie the operation of the CRV into the light switch. The lights in a room are usually on only when occupied.

5.Use a manual timer that the occupants turn to energize the CRV for a specific number of hours.

6.Use a programmable mechanical timer to energize the CRV and indoor blower during occupied periods of the day.

NOTE: The ventilation package comes with a blower interlock function, but is disabled when it is shipped from the factory in case you do not utilize a thermostat with an occupancy output, or a occupancy sensor and must tie "A" terminal to "G" terminal to drive the ventilation package. If you do have a thermostat or control that does drive occupancy output, you will need to remove the tape from the orange wire located in the low voltage terminal box, and connect it to the "G" terminal to activate this function. (See Figures 13-19.)

SETTING THE VENTILATION CFM LEVELS

The I-TEC CRV has four pre-set levels of ventilation CFM available. These are 300, 375, 450 and 525 CFM of ventilation air. The I-TEC CRV is shipped from the factory set on the 375 CFM ventilation level. To change between these four different levels of provided ventilation CFM, first refer to Figure 21 to look up the corresponding CFM needed for the intake and exhaust blowers to meet the design criteria and determine which “speed/wire color” is needed. Then, perform the following steps.

!

WARNING

 

HAZARD OF ELECTRICAL SHOCK.

 

ELECTRICAL SHOCK CAN RESULT

 

IN SERIOUS INJURY OR DEATH.

2

DISCONNECT THE REMOTE

-

-754

ELECTRIC POWER SUPPLY OR

7961

SUPPLIES BEFORE SERVICING.

 

1.Open front swinging doors of main unit (by popping front door latches).

2.Throw main power disconnect to the “OFF” position to eliminate risk of injury or death due to electrical shock.

3.Remove six (6) screws holding front CRV door in place (See Figure 22).

4.Locate “Brown Wire with White Trace” that has a black terminal on the end where it connects to the terminal strip (See Figure 21).

5.Move “Brown Wire with White Trace” to the corresponding CFM level needed in accordance with Figure 21.

Manual

2100-549G

Page

34 of 59

Image 34
Contents TEC Series Packaged Heat Pump Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersGeneral Ansi Z535.5 DefinitionsFactory BUILT-IN Electric Heat Table Indoor Blower PerformanceElectrical Specifications Unit Specification Sheet Unit DimensionsUnit Removal from Skid Shipping DamageHandling Unit After Removal from Skid Seismic Considerations Minimum Installation HeightWall Mounting Bracket Location Bracket Wall Section View Center of Gravity Center of GravityRequired Clearances & Recommended Access Compressor Shipping Bolts Removal of AIR DuctDucted Application Basic Unit 3 Riser Application 6 Riser Application Supply Duct Connections Duct WorkFilters Filter LocationWith no Vent Option With Energy Recovery VentilatorCondensate Drain With Commercial Room VentilatorUnit Mounting 16 3/4 NON-TAPPING 16 1/2 NON-TAPPINGTEC Unit Mounting the Unit Wiring Main PowerComponent Location Operating Voltage Range Wiring LOW Voltage WiringLOW Voltage Connections Wall ThermostatsBasic Heat Pump with no Ventilation Package SC SC SCY2 B/W1 W2 W3 CRV Wiring Harness Heat Pump with CRV, Without CO2 ControlHeat Pump with CRV and CO2 Control To functionERV Wiring Harness Heat Pump with ERV, Without CO2 ControlHeat Pump with ERV and CO2 Control ON/OFF Cycling ERV Wiring Harness Bard #8403-067 Heat Pump with ERV and CO2 Control Fully ModulatingHeat Pump with Combination CRV and DB Economizer N Vent Code Safety Practices Topping OFF System ChargeThree Phase Scroll Compressor Start UP Information Important Installer NotePhase Monitor Service HintsSequence of Operation Pressure Service PortsSound Defrost Cycle Defrost CycleTeccommercial Room Ventilator System General Description Control WiringSetting the Ventilation CFM Levels Recommended Control SequencesCRV Motor SPEED/CFM Configuration Vent Option INTAKE/EXHAUST SpeedsCRV Speed Change Terminal Access Control Wiring TECECON. Sequence of Operation Economizer Control CircuitVentilation Mode Heating Mode OperationMotor SPEED/CFM Configuration Tecenergy Recovery Ventilator System General Description Changing Ventilation CFM Rates in Manual Mode Changing to Fully Modulating ModePerformance and Application Data Winter Heating Performance Indoor Design Conditions 70F DBERV Manual Mode Jumper PIN on M Terminal ERV Modulating Mode Jumper PIN on P TerminalVentilation Airflow Diagram Indoor Air Supply Air Outdoor AirERV Access Specifications Control Board CONFIGURATION/SETTINGMounting WiringAccessing Menu Parameters Selection of Voltage OutputsMenu Descriptions Maintenance Procedures Quarterly Maintenance Energy Recovery Ventilator Maintenance General InformationCleanability and Performance FrequencyAnnual Maintenance Troubleshooting Solid State Heat Pump Control Troubleshooting ProcedureCodes Function Checking Temperature Sensor Temperature F VS Resistance R of Temperature SensorTroubleshooting ECM 142R Outdoor FAN Motor Heat Pump Mode Troubleshooting ECM 142R Outdoor FAN MotorCooling Mode Replacing the MotorTroubleshooting Indoor ECM Blower Motors Troubleshooting Indoor ECM Blower Motors Cont’d Power Connector Motor Half FAN Blade Setting DimensionsControl Connector Motor Half Refrigerant ChargeFull Load Cooling PRESSURE/TEMPERATURE Full Load Heating PRESSURE/TEMPERATUREPart Load Cooling PRESSURE/TEMPERATURE Part Load Heating PRESSURE/TEMPERATURE