Omega Engineering FP-6000 manual Standard Installation

Page 14

Step 1

hex nut lock washer

brass sensor nut

Step 2

Once the correct dimensions are calculated and recorded, the sensor can be installed in the fitting. The Standard and Hot-Tap versions require substantially different procedures.

3.6 Standard Installation

1.Thread one hex nut onto each of the three threaded rods included in package. Install threaded rod with a lock-washer onto the brass sensor nut. Secure rods in place by tightening each hex nut against the brass sensor nut.

2.Thread one jam nut and lower hex nut onto each stud so that the top surface of each nut is at the proper "H" dimension for your pipe. Secure each hex nut with a jam nut.

3.Insert the flow sensor into the brass sensor nut, making sure the alignment hole on the sensor flange is pointing downstream.

lower hex nut, 2nd

lower hex nuts

jam nut, 1'st

(3/16 x 1/4-20)

 

jam nuts

 

(5/32 x 1/4-20)

"H"

hex nut and lock washer

 

brass sensor nut

process pipe

8

Image 14
Contents User’s Guide Servicing Europe Servicing North AmericaFor immediate technical or application assistance Table of Contents Page Important Safety Information Warranty Record Type Omega FP-6000 SeriesTheory of Operation Chapter IntroductionDescription Sensor Position Chapter Installation and WiringLocation of Fitting Sensor Wiring +30Hardware, Hot-Tap Sensor Standard Fitting InstallationHardware, Standard Sensor 11/4 in mm diameter drill Pipe thread sealant Tape measureThread brass sensor nut into pipe fitting Hot-Tap Fitting InstallationRemove brass sensor nut from sensor Calculating the H Dimension Wall ThicknessRecord your pipes H dimension for future reference Hot-Tap Sensor = 15.00 pipe wall thickness 0.10 X I.DStandard Installation Sensor flange Alignment rod Direction of flow Thread one jam nut and lower hex nut onto Hot-Tap InstallationStep Make sure the bleed valve is closed full clockwise position Direction of flowUsing the Hot-Tap Installation Tool Protector plate Installation tool shaft Upper hex nuts Hot-Tap Sensor Removal ChapterStandard Sensor Removal Into the port to prevent damageCap nuts Installation tool Replacement Parts Chapter Maintenance and Replacement PartsMaintenance Rotor Replacement Procedure Wrought Steel Pipe Per Ansi DimensionsDimensions for Standard Sensors Conversion Stainless Steel Pipe Per Ansi B36.19 Mm = inchesDimensions for Hot-Tap Sensors Factors Stainless Steel GPM/HZ LPM/HZFactors Wrought Steel Factors Plastic Pipe GPM/HZ LPM/HZSpecifications General DataSpecifications WARRANTY/DISCLAIMER OMEGA…Of Course