Omega Engineering FP-6000 manual Make sure the bleed valve is closed full clockwise position

Page 17

3.Wipe the FP-6000 Series sensor body with a dry, clean cloth. Orient the alignment hole on the sensor flange to point downstream. Place the slotted flange over the threaded rods. Lower the sensor into fitting until the sensor flange rests on the lower hex and jam nuts.

4.Secure the sensor with lock-washers and upper hex nuts on the top of the flange. Before tighten- ing, align the sensor flange so that the alignment rod is parallel and level with the process pipe.

5.Make sure the bleed valve is closed (full clockwise position).

sensor flange

alignment rod

 

direction of flow

process pipe (top view)

The flow sensor alignment rod MUST be parallel to the process pipe as shown.

Upper hex nuts (3/16 x 1/4-20)

1/4 in. lock washers

sensor flange

lower hex nut and jam nuts

18 inch threaded rods

Brass sensor nut

alignment rod

13.75 in.

Bleed valve

direction of flow

process pipe (side view)

11

Image 17
Contents User’s Guide Servicing Europe Servicing North AmericaFor immediate technical or application assistance Table of Contents Page Important Safety Information Type Omega FP-6000 Series Warranty RecordTheory of Operation Chapter IntroductionDescription Sensor Position Chapter Installation and WiringLocation of Fitting +30 Sensor WiringHardware, Standard Sensor Standard Fitting InstallationHardware, Hot-Tap Sensor 11/4 in mm diameter drill Pipe thread sealant Tape measureThread brass sensor nut into pipe fitting Hot-Tap Fitting InstallationRemove brass sensor nut from sensor Wall Thickness Calculating the H DimensionHot-Tap Sensor = 15.00 pipe wall thickness 0.10 X I.D Record your pipes H dimension for future referenceStandard Installation Sensor flange Alignment rod Direction of flow Thread one jam nut and lower hex nut onto Hot-Tap InstallationStep Direction of flow Make sure the bleed valve is closed full clockwise positionUsing the Hot-Tap Installation Tool Protector plate Installation tool shaft Upper hex nuts Standard Sensor Removal ChapterHot-Tap Sensor Removal Into the port to prevent damageCap nuts Installation tool Replacement Parts Chapter Maintenance and Replacement PartsMaintenance Rotor Replacement Procedure Dimensions for Standard Sensors DimensionsWrought Steel Pipe Per Ansi Conversion Stainless Steel Pipe Per Ansi B36.19 Mm = inchesDimensions for Hot-Tap Sensors GPM/HZ LPM/HZ Factors Stainless SteelFactors Wrought Steel GPM/HZ LPM/HZ Factors Plastic PipeGeneral Data SpecificationsSpecifications WARRANTY/DISCLAIMER OMEGA…Of Course