Baldor MN735 manual Unshielded and Shielded Couplings, Clamp Terminal

Page 16

Examples:

A 5hp, 230VAC control operating at 208VAC has a reduced power rating of 4.5hp.

5HP

208VAC

+

4.5hp

230VAC

Likewise, a 3hp, 460VAC control operating at 380VAC has a reduced power rating of 2.47hp.

3HP

380VAC

+

2.47hp

460VAC

Electrical Installation All interconnection wires between the control, AC power source, motor, host control and any operator interface stations should be in metal conduits or shielded cable must be used. Use listed closed loop connectors that are of appropriate size for wire gauge being used. Connectors are to be installed using crimp tool specified by the manufacturer of the connector. Only class 1 wiring should be used.

Figure 3-3 Unshielded and Shielded Couplings

Rubber

Metal

360 Degree

Grommet

Coupling

Coupling

360 Degree Coupling

Holes are required in the enclosure assembly to allow connections to be made. Use the correct size rubber grommet, conduit coupling or 360 degree coupling.

Clamp Terminals To install a wire into a clamp terminal, first strip wire insulation to 0.20–0.24 in. (5–6mm). Insert a flat–blade screwdriver, maximum blade size 0.138 in. (3.5mm) into the adjacent hole. Do not twist or rotate the screwdriver as this action may damage the terminal. A very slight downward pressure on the screwdriver should open the terminals and allow the wire to be inserted. Insert the wire into the clamp opening (Figure 3-4). Remove the screwdriver. The terminal provides the correct force for a secure connection.

Figure 3-4 Clamp Terminal

MN735

Receiving & Installation 3–5

Image 16
Contents Series 35D Inverter Control MN735Table of Contents Appendix a Appendix BPower and Motor Connections Section Quick StartRemote Mode Size 1 and 3 Terminal StripsPower Connection Descriptions Thermistor Connection to motor thermistorAnalog/Digital Signal Descriptions Terminal Signal Name Description RangeLimited Warranty Section General InformationCould result in damage to property Product Notice Intended useOn next Precautions To prevent equipment damage, be certain that the input power Receiving & Inspection Section Receiving & InstallationLocation and Mounting Watts Loss Ratings Catalog No Output Current Inverter SizesInput Power Conditioning Power ConditioningUngrounded Distribution System Impedance + Unshielded and Shielded Couplings Clamp TerminalWire Size AWG MM2Power Connection Descriptions Power and Ground Connections Size 2 Shown Resistance thresholds are Rising temperature trip resistance One control to PE Receiving & Installation MN735 External Brake Resistor Keypad Mode Keypad Connection DiagramStandard Run 3 Wire Mode Standard Run Connection DiagramSpeed 2 Wire Mode Related Parameters10 Epot Connection Diagram 11 Epot Connection Diagram PID 2 Wire Mode 12 PID Connection DiagramReceiving & Installation MN735 Section Start-Up and Operation Keypad DescriptionDisplay Diagnostics MenuDrive Status Indications shown on keypad Menu Level Select Local or Remote Reset to Factory Settings 2 button ResetRemote to Local Password Protection Quick Application SelectionDisplay Parameter Description Range Factory Setting Parameter DefinitionsDisplay Parameter Description Range PI P Gain Analog Output Relay Invert =FALSE =TRUE Proportional Gain P501 Method for Setting-up the PI GainsIntegral P502 Power Dependent Parameters Inverter Size Factory Setting CurrentRoutine Maintenance Saving Your Application DataMaterial Recycle Disposal PackagingReset a Trip Section TroubleshootingTrips General Failures DC Link RippleSection Specifications & Product Data General SpecificationsKeypad Display Control SpecificationsAnalog Inputs Analog Outputs Digital InputsRelay Output Ratings CatalogDimensions Size 1 and 2 230VAC 1 Phase Size 3 230VAC 3 Phase460VAC 3 Phase Controls Size 2 and 3 460VAC Appendix a Dynamic BrakeTable A-1 External Brake Resistor Selection Wiring of Shielded Screened Cables Appendix B CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingEMC Wiring Technique CabinetEMC Installation Instructions Cable Screens GroundingInput Signal Cable Grounding Standard EMC Directive Date 1/5/02 EC Declarations of ConformityTion CE Guidelines MN735 Box Ft. Smith, AR 479 Fax 479  Baldor Electric Company MN735 02 C&J