Baldor MN735 manual Control Specifications, Keypad Display, Analog Inputs

Page 47

Control Specifications:

 

 

Control method:

 

Random carrier input, 0–240Hz PWM output.

Output rating:

 

Peak overload capacity of 150% for 30 seconds

 

 

for constant torque;

PWM Frequency:

 

Random PWM for quiet motor operation.

V/Hz Ratio:

 

Linear squared reduced; base frequency; min fre-

 

 

quency limit; max frequency limit.

Torque Boost

 

Adjustable 0–25% of input voltage.

Brake Torque:

 

Optional external braking resistors available for

 

 

460VAC controls.

Frequency Setting:

 

0–5VDC, 0–10VDC, 0–20mA, 4–20mA, digital us-

 

 

ing keypad or RS232.

Accel/Decel:

 

Separate Accel and Decel rates from 0–3000 sec-

 

 

onds to maximum frequency.

Protective Features:

 

Adjustable time base overload, display fault

 

 

condition, isolated control circuitry, heatsink

 

 

thermal sensor and motor thermal monitoring.

Outputs:

 

Analog meter output, opto isolated output, relay

 

 

output.

Keypad Display:

 

 

Display:

 

7 segment and custom character display.

Keys:

 

10 key membrane with tactile response

Display Function:

Running

Output frequency, set speed %, DC link voltage,

 

Setting

motor current

 

Parameter values for setting and viewing

 

Trip

Separate message for each trip

Analog Inputs:

 

 

Operating range

 

0–5VDC and 0–10VDC (no sign), set with

 

 

parameter SIP13 (AIN1)

 

 

0–5VDC, 0–10VDC, 0–20mA and 4–20mA (no

 

 

sign), set with parameter SIP23 (AIN2)

 

 

25mA maximum input current; 24VDC maximum

 

 

input voltage

Input impedance

 

40k ohms (current input <6VDC @ 20mA)

Resolution

 

10 bits (1 in 1024)

Sample rate

 

10mseconds

6–2 Specifications & Product Data

MN735

Image 47
Contents MN735 Series 35D Inverter ControlTable of Contents Appendix B Appendix aSection Quick Start Power and Motor ConnectionsSize 1 and 3 Terminal Strips Remote ModeThermistor Connection to motor thermistor Power Connection DescriptionsTerminal Signal Name Description Range Analog/Digital Signal DescriptionsSection General Information Limited WarrantyOn next Product Notice Intended useCould result in damage to property Precautions To prevent equipment damage, be certain that the input power Location and Mounting Section Receiving & InstallationReceiving & Inspection Inverter Sizes Watts Loss Ratings Catalog No Output CurrentUngrounded Distribution System Power ConditioningInput Power Conditioning Impedance + Clamp Terminal Unshielded and Shielded CouplingsAWG MM2 Wire SizePower Connection Descriptions Power and Ground Connections Size 2 Shown Resistance thresholds are Rising temperature trip resistance One control to PE Receiving & Installation MN735 External Brake Resistor Keypad Connection Diagram Keypad ModeStandard Run Connection Diagram Standard Run 3 Wire ModeRelated Parameters Speed 2 Wire Mode10 Epot Connection Diagram 11 Epot Connection Diagram 12 PID Connection Diagram PID 2 Wire ModeReceiving & Installation MN735 Keypad Description Section Start-Up and OperationDrive Status Indications shown on keypad Diagnostics MenuDisplay Menu Level Remote to Local Reset to Factory Settings 2 button ResetSelect Local or Remote Quick Application Selection Password ProtectionParameter Definitions Display Parameter Description Range Factory SettingDisplay Parameter Description Range PI P Gain Analog Output Relay Invert =FALSE =TRUE Integral P502 Method for Setting-up the PI GainsProportional Gain P501 Current Power Dependent Parameters Inverter Size Factory SettingPackaging Routine MaintenanceSaving Your Application Data Material Recycle Disposal Trips Section Troubleshooting Reset a Trip DC Link Ripple General FailuresGeneral Specifications Section Specifications & Product DataAnalog Inputs Control SpecificationsKeypad Display Ratings Catalog Analog OutputsDigital Inputs Relay OutputDimensions Appendix a Dynamic Brake Size 1 and 2 230VAC 1 PhaseSize 3 230VAC 3 Phase 460VAC 3 Phase Controls Size 2 and 3 460VACTable A-1 External Brake Resistor Selection EMC Conformity and CE Marking Wiring of Shielded Screened CablesAppendix B CE Guidelines CE Declaration of ConformityCabinet EMC Wiring TechniqueCable Screens Grounding EMC Installation InstructionsInput Signal Cable Grounding Tion Date 1/5/02 EC Declarations of ConformityStandard EMC Directive CE Guidelines MN735  Baldor Electric Company MN735 02 C&J Box Ft. Smith, AR 479 Fax 479