Baldor MN735 manual Relay Invert

Page 39

Table 4-1 Parameter Definitions Continued

Display

Parameter

Description

Range

Factory

 

 

 

 

Setting

 

RELAY INVERT

True =Inverts the input signal.

0= False

0

 

 

 

1= True

 

 

RELAY VALUE

The output signal that represents the OP31

0= False

0

 

~

choice.

1= True

 

 

 

SET::TRIP Menu

 

 

 

DISABLE LOOP

Disables LOST I LOOP trip (4-20mA)

0= Trip Enabled

1

 

 

 

1= Trip Disabled

 

 

AIN2

Disables the overload trip (Terminal 3)

0= Trip Enabled

0

 

OVERLOAD

 

1= Trip Disabled

 

 

DISABLE

Disables STALL trip

0= Trip Enabled

0

 

STALL

 

1= Trip Disabled

 

 

DISABLE

Disables the motor thermistor trip

0= Trip Enabled

0

 

MOTOR

 

1= Trip Disabled

 

 

OVERTEMP

 

 

 

 

 

SET::SETP Menu

 

 

 

Inverse Time

Disables the inverse time trip

0= Trip Enabled

1

 

 

 

1= Trip Disabled

 

 

Display

Disables the display (keypad) trip

0= Trip Enabled

0

 

(Keypad)

 

1= Trip Disabled

 

 

Jog Accel Time

As P4, for Jog

0.0 to 3000.0s

1.0

 

Jog Decel Time

As P5, for Jog

0.0 to 3000.0s

1.0

 

Ramp Type

Selects the ramp type

0=LINEAR

0

 

 

 

1=S

 

 

S Ramp Jerk

Rate of change of acceleration of the curve in

0.01 to 100.00s3

10.00s3

 

 

units per second3

 

 

 

S Ramp

When True and the S Ramp is selected, forces

0=FALSE

1

 

Continuous

a smooth transition if the speed setpoint is

1=TRUE

 

 

 

changed when ramping. The curve is controlled

 

 

 

 

by the S Ramp Jerk parameter.

 

 

 

 

When False, there is an immediate transition

 

 

 

 

from the old curve to the new curve

 

 

 

Skip

The center frequency of skip band 1 in Hz

0.0 to 240.0 Hz

0.0

 

Frequency 1

 

 

 

 

Skip Frequency

The width of skip band 1 in Hz

0.0 to 60.0 Hz

0.0

 

Band 1

 

 

 

 

Skip

The center frequency of skip band 2 in Hz

0.0 to 240.0 Hz

0.0

 

Frequency 2

 

 

 

 

Skip Frequency

The width of skip band 2 in Hz

0.0 to 60.0 Hz

0.0

 

Band 2

 

 

 

 

Auto Restart

Determines the number of restarts that will be

0 to 10

0

 

Attempts

permitted before requiring an external fault

 

 

 

 

reset

 

 

 

Auto Restart

The delay between restart attempts for a trip

0.0 to 600.0 s

10.0s

 

Delay

included in Auto Restart Triggers and Auto

 

 

 

 

Restart Triggers+. The delay is measured from

 

 

 

 

all error conditions clearing

 

 

 

Auto Restart

Allows Auto Restart to be enabled for a

0x0000 to 0xFFFF

0x0000

 

Triggers

selection of trip conditions. Refer to Section 5

 

 

4–10 Start–Up and Operation

MN735

Image 39
Contents MN735 Series 35D Inverter ControlTable of Contents Appendix B Appendix aSection Quick Start Power and Motor ConnectionsSize 1 and 3 Terminal Strips Remote ModeThermistor Connection to motor thermistor Power Connection DescriptionsTerminal Signal Name Description Range Analog/Digital Signal DescriptionsSection General Information Limited WarrantyProduct Notice Intended use Could result in damage to propertyOn next Precautions To prevent equipment damage, be certain that the input power Section Receiving & Installation Receiving & InspectionLocation and Mounting Inverter Sizes Watts Loss Ratings Catalog No Output CurrentPower Conditioning Input Power ConditioningUngrounded Distribution System Impedance + Clamp Terminal Unshielded and Shielded CouplingsAWG MM2 Wire SizePower Connection Descriptions Power and Ground Connections Size 2 Shown Resistance thresholds are Rising temperature trip resistance One control to PE Receiving & Installation MN735 External Brake Resistor Keypad Connection Diagram Keypad ModeStandard Run Connection Diagram Standard Run 3 Wire ModeRelated Parameters Speed 2 Wire Mode10 Epot Connection Diagram 11 Epot Connection Diagram 12 PID Connection Diagram PID 2 Wire ModeReceiving & Installation MN735 Keypad Description Section Start-Up and OperationDiagnostics Menu DisplayDrive Status Indications shown on keypad Menu Level Reset to Factory Settings 2 button Reset Select Local or RemoteRemote to Local Quick Application Selection Password ProtectionParameter Definitions Display Parameter Description Range Factory SettingDisplay Parameter Description Range PI P Gain Analog Output Relay Invert =FALSE =TRUE Method for Setting-up the PI Gains Proportional Gain P501Integral P502 Current Power Dependent Parameters Inverter Size Factory SettingPackaging Routine MaintenanceSaving Your Application Data Material Recycle DisposalSection Troubleshooting Reset a TripTrips DC Link Ripple General FailuresGeneral Specifications Section Specifications & Product DataControl Specifications Keypad DisplayAnalog Inputs Ratings Catalog Analog OutputsDigital Inputs Relay OutputDimensions Appendix a Dynamic Brake Size 1 and 2 230VAC 1 PhaseSize 3 230VAC 3 Phase 460VAC 3 Phase Controls Size 2 and 3 460VACTable A-1 External Brake Resistor Selection EMC Conformity and CE Marking Wiring of Shielded Screened CablesAppendix B CE Guidelines CE Declaration of ConformityCabinet EMC Wiring TechniqueCable Screens Grounding EMC Installation InstructionsInput Signal Cable Grounding Date 1/5/02 EC Declarations of Conformity Standard EMC DirectiveTion CE Guidelines MN735  Baldor Electric Company MN735 02 C&J Box Ft. Smith, AR 479 Fax 479