Baldor MN735 manual EMC Wiring Technique, Cabinet

Page 53

Using CE approved components will not guarantee a CE compliant system!

1.The components used in the drive, installation methods used, materials selected for interconnection of components are important.

2.The installation methods, interconnection materials, shielding, filtering and grounding of the system as a whole will determine CE compliance.

3.The responsibility of CE mark compliance rests entirely with the party who offers the end system for sale (such as an OEM or system integrator).

Baldor products which meet EMC directive requirements are indicated by a “CE” mark. A duly signed CE declaration of conformity is available from Baldor.

EMC Wiring Technique

Y

Capacitor

1CABINET

The drawing shows an electroplated zinc coated enclosure, connected to ground. This enclosure has the following advantages:

-All parts mounted on the back plane are connected to ground.

-All shield (screen) connections are connected to ground.

Within the cabinet there should be a spatial separation between power wiring (motor and AC power cables) and control wiring.

2SCREEN CONNECTIONS

All connections between components must use shielded cables. The cable shields must be connected to the enclosure. Use conductive clamps to ensure good ground connection. With this technique, a good ground shield can be achieved.

3EMC - FILTER

The EMI or main filter should be mounted next to the power supply (here BPS). For the connection to and from the main filter screened cables should be used. The cable screens should be connected to screen clamps on both sides. (Exception: Analog Command Signal).

4Grounding (Earth)

For safety reasons (VDE0160), all BALDOR components must be connected to ground with a separate wire. The diameter of the wire must be at minimum AWG#6 (10mm@). Ground connections (dashed lines) must be made from the central ground to the regen resistor enclosure and from the central ground to the Shared Power Supply.

5Y-CAPACITOR

The connection of the regeneration resistor can cause RFI (radio frequency interference) to be very high. To minimize RFI, a Y-capacitor is used. The capacitor should only be connected between the dynamic brake resistor housing and terminal pin R1 (lead from Lin).

Recommendation:

0,1F / 250VAC Type: PME265

BALDOR-Ordering-No.: ASR27104

B–2 CE Guidelines

MN735

Image 53
Contents MN735 Series 35D Inverter ControlTable of Contents Appendix B Appendix aSection Quick Start Power and Motor ConnectionsSize 1 and 3 Terminal Strips Remote ModeThermistor Connection to motor thermistor Power Connection DescriptionsTerminal Signal Name Description Range Analog/Digital Signal DescriptionsSection General Information Limited WarrantyOn next Product Notice Intended useCould result in damage to property Precautions To prevent equipment damage, be certain that the input power Location and Mounting Section Receiving & InstallationReceiving & Inspection Inverter Sizes Watts Loss Ratings Catalog No Output CurrentUngrounded Distribution System Power ConditioningInput Power Conditioning Impedance + Clamp Terminal Unshielded and Shielded CouplingsAWG MM2 Wire SizePower Connection Descriptions Power and Ground Connections Size 2 Shown Resistance thresholds are Rising temperature trip resistance One control to PE Receiving & Installation MN735 External Brake Resistor Keypad Connection Diagram Keypad ModeStandard Run Connection Diagram Standard Run 3 Wire ModeRelated Parameters Speed 2 Wire Mode10 Epot Connection Diagram 11 Epot Connection Diagram 12 PID Connection Diagram PID 2 Wire ModeReceiving & Installation MN735 Keypad Description Section Start-Up and OperationDrive Status Indications shown on keypad Diagnostics MenuDisplay Menu Level Remote to Local Reset to Factory Settings 2 button ResetSelect Local or Remote Quick Application Selection Password ProtectionParameter Definitions Display Parameter Description Range Factory SettingDisplay Parameter Description Range PI P Gain Analog Output Relay Invert =FALSE =TRUE Integral P502 Method for Setting-up the PI GainsProportional Gain P501 Current Power Dependent Parameters Inverter Size Factory SettingSaving Your Application Data Routine MaintenanceMaterial Recycle Disposal PackagingTrips Section TroubleshootingReset a Trip DC Link Ripple General FailuresGeneral Specifications Section Specifications & Product DataAnalog Inputs Control SpecificationsKeypad Display Digital Inputs Analog OutputsRelay Output Ratings CatalogDimensions Size 3 230VAC 3 Phase Size 1 and 2 230VAC 1 Phase460VAC 3 Phase Controls Size 2 and 3 460VAC Appendix a Dynamic BrakeTable A-1 External Brake Resistor Selection Appendix B CE Guidelines Wiring of Shielded Screened CablesCE Declaration of Conformity EMC Conformity and CE MarkingCabinet EMC Wiring TechniqueCable Screens Grounding EMC Installation InstructionsInput Signal Cable Grounding Tion Date 1/5/02 EC Declarations of ConformityStandard EMC Directive CE Guidelines MN735  Baldor Electric Company MN735 02 C&J Box Ft. Smith, AR 479 Fax 479