Baldor MN735 manual Impedance +

Page 15

Line Impedance The Baldor control requires a 1% line impedance minimum . If the impedance of the incoming power does not meet the requirement for the control, a 3 phase line reactor can be used to provide the needed impedance in most cases. Line reactors are optional and are available from Baldor.

The input impedance of the power lines can be determined as follows: Measure the line to line voltage at no load and at full rated load. Use these measured values to calculate impedance as follows:

%Impedance +

(VoltsNo Load Speed *

VoltsFull Load Speed)

100

(VoltsNo Load Speed)

 

 

 

Line Reactors Three phase line reactors are available from Baldor. The line reactor to order is based on the full load current of the motor (FLA). If providing your own line reactor, use the following formula to calculate the minimum inductance required.

L +

(VL*

L

0.03)

 

 

 

 

 

 

 

(I

￿3

377)

 

Where: L

Minimum inductance in Henries.

VL-L

Input volts measured line to line.

0.03

 

Desired percentage of input impedance.

I

Input current rating of control.

377

 

Constant used with 60Hz power.

 

 

Use 314 if input power is 50Hz.

Load Reactors Line reactors may be used at the control output to the motor. When used this way, they are called Load Reactors. Load reactors serve several functions that include:

SProtect the control from a short circuit at the motor.

SLimit the rate of rise of motor surge currents.

SSlowing the rate of change of power the control delivers to the motor. Load reactors should be installed as close to the control as possible. Selection should be based on the motor nameplate FLA value.

Power Disconnect A power disconnect should be installed between the input power service and the control for a fail safe method to disconnect power. The control will remain in a powered-up condition until all input power is removed from the control and the internal bus voltage is depleted.

Protective Devices Recommended fuse sizes are based on the following: 115% of maximum continuous current for time delay.

150% of maximum continuous current for Fast or Very Fast action.

Note: These general size recommendations do not consider harmonic currents or ambient temperatures greater than 40° C.

Be sure a suitable input power protection device is installed. Use the recommended fuses and wire sizes shown in Table 3-2 is based on the use of copper conductor wire rated at 75 ° C. The table is specified for NEMA B motors.

Reduced Input Voltage Derating All power ratings stated in Section 6 are for the stated nominal AC input voltages (230 or 460VAC). The power rating of the control must be reduced when operating at a reduced input voltage. The amount of reduction is the ratio of the voltage change.

3–4 Receiving & Installation

MN735

Image 15
Contents MN735 Series 35D Inverter ControlTable of Contents Appendix B Appendix aSection Quick Start Power and Motor ConnectionsSize 1 and 3 Terminal Strips Remote ModeThermistor Connection to motor thermistor Power Connection DescriptionsTerminal Signal Name Description Range Analog/Digital Signal DescriptionsSection General Information Limited WarrantyProduct Notice Intended use Could result in damage to propertyOn next Precautions To prevent equipment damage, be certain that the input power Section Receiving & Installation Receiving & InspectionLocation and Mounting Inverter Sizes Watts Loss Ratings Catalog No Output CurrentPower Conditioning Input Power ConditioningUngrounded Distribution System Impedance + Clamp Terminal Unshielded and Shielded CouplingsAWG MM2 Wire SizePower Connection Descriptions Power and Ground Connections Size 2 Shown Resistance thresholds are Rising temperature trip resistance One control to PE Receiving & Installation MN735 External Brake Resistor Keypad Connection Diagram Keypad ModeStandard Run Connection Diagram Standard Run 3 Wire ModeRelated Parameters Speed 2 Wire Mode10 Epot Connection Diagram 11 Epot Connection Diagram 12 PID Connection Diagram PID 2 Wire ModeReceiving & Installation MN735 Keypad Description Section Start-Up and OperationDiagnostics Menu DisplayDrive Status Indications shown on keypad Menu Level Reset to Factory Settings 2 button Reset Select Local or RemoteRemote to Local Quick Application Selection Password ProtectionParameter Definitions Display Parameter Description Range Factory SettingDisplay Parameter Description Range PI P Gain Analog Output Relay Invert =FALSE =TRUE Method for Setting-up the PI Gains Proportional Gain P501Integral P502 Current Power Dependent Parameters Inverter Size Factory SettingPackaging Routine MaintenanceSaving Your Application Data Material Recycle DisposalSection Troubleshooting Reset a TripTrips DC Link Ripple General FailuresGeneral Specifications Section Specifications & Product DataControl Specifications Keypad DisplayAnalog Inputs Ratings Catalog Analog OutputsDigital Inputs Relay OutputDimensions Appendix a Dynamic Brake Size 1 and 2 230VAC 1 PhaseSize 3 230VAC 3 Phase 460VAC 3 Phase Controls Size 2 and 3 460VACTable A-1 External Brake Resistor Selection EMC Conformity and CE Marking Wiring of Shielded Screened CablesAppendix B CE Guidelines CE Declaration of ConformityCabinet EMC Wiring TechniqueCable Screens Grounding EMC Installation InstructionsInput Signal Cable Grounding Date 1/5/02 EC Declarations of Conformity Standard EMC DirectiveTion CE Guidelines MN735  Baldor Electric Company MN735 02 C&J Box Ft. Smith, AR 479 Fax 479