6 – PID 2 Wire Mode

In PID 2 wire mode, the control is operated by the opto isolated inputs and the analog command input. The opto inputs can be switches as shown in Figure 3-12 or logic signals from another device.

Figure 3-12 PID Connection Diagram

Process

 

Enable

Command

Open

Analog Input 1 (Speed Ref)

Closed

PID

 

 

Analog Input 1 = 0–10VDC Setpoint Analog Input 2 = 4–20mA Feedback

Related Parameters

p8 Jog Speed

Jog Accel

Jog Decel

 

Jog

 

Process Enable

 

Run REV

 

Run FWD

 

+24VDC

 

Speed Output

 

Pot Reference

 

Analog Input 2

10KW Pot or

Analog Input 1

 

0-10VDC

Analog GND

10

9

8

7

6

5

4

3

2

1

RLY1A

Fault

RLY1B

1Analog GND. Reference for analog inputs.

2PID Setpoint 0–10VDC. Single ended analog voltage input, referenced to 1.

3PID Feedback 4–20mA. Single ended analog current input, referenced to 1.

4+10VDC reference voltage for potentiometer.

5Analog output that represents the commanded speed output.

6+24VDC for Optical Inputs power.

7Momentary CLOSED starts motor operation in the Forward direction. In Jog mode (10 Closed), jogs motor in forward direction as long as switch is closed.

8Momentary CLOSED starts motor operation in the Reverse direction. In Jog mode (10 Closed), jogs motor in reverse direction as long as switch is closed.

9CLOSED enables process mode. OPEN selects Analog Input 1 setpoint.

10CLOSED places control in Jog mode. Forward and Reverse run are used to Jog the motor at Jog speed.

RLY1 Digital output that represents the fault status.

MN735

Receiving & Installation 3–17

Image 28
Contents Series 35D Inverter Control MN735Table of Contents Appendix a Appendix BPower and Motor Connections Section Quick StartRemote Mode Size 1 and 3 Terminal StripsPower Connection Descriptions Thermistor Connection to motor thermistorAnalog/Digital Signal Descriptions Terminal Signal Name Description RangeLimited Warranty Section General InformationCould result in damage to property Product Notice Intended useOn next Precautions To prevent equipment damage, be certain that the input power Receiving & Inspection Section Receiving & InstallationLocation and Mounting Watts Loss Ratings Catalog No Output Current Inverter SizesInput Power Conditioning Power ConditioningUngrounded Distribution System Impedance + Unshielded and Shielded Couplings Clamp TerminalWire Size AWG MM2Power Connection Descriptions Power and Ground Connections Size 2 Shown Resistance thresholds are Rising temperature trip resistance One control to PE Receiving & Installation MN735 External Brake Resistor Keypad Mode Keypad Connection DiagramStandard Run 3 Wire Mode Standard Run Connection Diagram Speed 2 Wire Mode Related Parameters10 Epot Connection Diagram 11 Epot Connection Diagram PID 2 Wire Mode 12 PID Connection DiagramReceiving & Installation MN735 Section Start-Up and Operation Keypad DescriptionDisplay Diagnostics MenuDrive Status Indications shown on keypad Menu Level Select Local or Remote Reset to Factory Settings 2 button ResetRemote to Local Password Protection Quick Application SelectionDisplay Parameter Description Range Factory Setting Parameter DefinitionsDisplay Parameter Description Range PI P Gain Analog Output Relay Invert =FALSE =TRUE Proportional Gain P501 Method for Setting-up the PI GainsIntegral P502 Power Dependent Parameters Inverter Size Factory Setting CurrentRoutine Maintenance Saving Your Application DataMaterial Recycle Disposal PackagingReset a Trip Section TroubleshootingTrips General Failures DC Link RippleSection Specifications & Product Data General SpecificationsKeypad Display Control SpecificationsAnalog Inputs Analog Outputs Digital InputsRelay Output Ratings CatalogDimensions Size 1 and 2 230VAC 1 Phase Size 3 230VAC 3 Phase460VAC 3 Phase Controls Size 2 and 3 460VAC Appendix a Dynamic BrakeTable A-1 External Brake Resistor Selection Wiring of Shielded Screened Cables Appendix B CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingEMC Wiring Technique CabinetEMC Installation Instructions Cable Screens GroundingInput Signal Cable Grounding Standard EMC Directive Date 1/5/02 EC Declarations of ConformityTion CE Guidelines MN735 Box Ft. Smith, AR 479 Fax 479  Baldor Electric Company MN735 02 C&J