2.5 Faults

The RDC2/DC2 controller displays fault messages for generator set warnings and shutdowns. Selected fault messages are shown in Figure 2-3.

2.5.1Warnings

The controller displays a fault message but the generator set does not shut down on a warning. The controller resets automatically after a warning condition is corrected.

2.5.2Shutdowns

Under a fault shutdown condition, the generator set shuts down automatically and the controller displays a fault message. The OFF LED flashes. In some cases, the engine cooldown cycle runs before the engine shuts down. See Figure 2-3.

Shutdown switches (such as the low oil pressure switch or high engine temperature switch) on the generator set will automatically reset when the problem is corrected. However, the fault condition at the controller does not clear until the controller is reset.

The generator set cannot be restarted until the fault condition is corrected and the controller is reset. See Section 2.5.4 for instructions to reset the controller after a fault shutdown.

2.5.3ATS Communication Errors

When a Model RXT transfer switch is used, an ATS fault indicates that the connection to the interface board on the transfer switch has been lost. Check the connection to the ATS interface board.

2.5.4Resetting the Controller after a Fault Shutdown

Always identify and correct the cause of a fault shutdown before resetting the controller. Check the fault message displayed on the controller and refer to Figure 2-3 to identify and correct the fault condition before proceeding. Contact an authorized distributor/dealer for service, if necessary.

RDC2 Controller

Press the OFF button to reset the controller, or follow the procedure below. See Figure 2-2.

1.While the fault message is displayed, press the Select button to go to the Overview menu.

2.Press Select again. The active fault message is displayed.

3.Press Select. Confirm Clear Fault: NO is displayed.

4.Press the Down arrow button. Confirm Clear Fault: YES is displayed.

5.Press the Select button to enter YES and clear the fault.

6.Press the Select button to return to the overview menu. The controller changes to OFF mode.

7.Press AUTO to put the generator set into automatic mode.

DC2 Controller

Press the OFF button to clear the fault message on the controller.

Fault Message

Overview ---->

Fault Message

Confirm Clear

 

1.2 h

 

Fault: NO

 

 

Press Up arrow button.

 

 

 

 

Confirm Clear

 

 

 

Fault: YES

 

 

 

tp6809

Figure 2-2Clearing a Fault on the RDC2 Controller

24 Section 2 Generator Set Operation

TP-6880 10/14

Image 24
Contents RDC2 TP-6880 10/14aAccessory Number Accessory Description Product Identification InformationGenerator Set Identification Numbers Controller IdentificationTable of Contents Scheduled Maintenance TroubleshootingDC2 Controller Operation Safety Precautions and Instructions BatteryAccidental Starting Accidental starting Can cause severe injury or deathEngine Backfire/Flash Fire Exhaust SystemCarbon monoxide Can Cause Fire Can cause severe injury or deathFuel System Hazardous Noise Hazardous voltage Will cause severe injury or deathHeavy Equipment Hot PartsTransfer Switch Literature Accessory LiteratureIntroduction List of Related LiteratureNameplate Emission InformationGenerator Set Application Emission Compliance PeriodService Assistance Service Assistance TP-6880 10/14 Descriptions and Service Views RDC2 Controller Features DC2 Controller Features Accessories Carburetor HeaterProgrammable Interface Module PIM Load Control Module LCMService Views 12143Service View Prestart Checklist Generator Set OperationGenerator Set Operation TP-6880 10/14 Exercising the Generator Set Generator Set OperationAutomatic Operation with Other Transfer Switches Setting the ExerciserUnloaded Cycle Exercise with Complete System Diagnostics ExercisePower Failure During Exercise Cycle System DiagnosticsUnloaded Full-Speed Exercise Loaded Full-Speed Exercise with RXT onlyFaults ATS Communication ErrorsResetting the Controller after a Fault Shutdown ShutdownsFault Message Shutdown SD Condition Check 3Controller Fault Messages Fault Shutdown SD Condition CheckGenerator Enclosure Thermostat Generator Set Operation TP-6880 10/14 RDC2 Generator Set/ Transfer Switch Controller Controls and IndicatorsRDC2 Controller Operation Controller Keypad LED Indicators ButtonButton Function LED OperationLCD Display Active AlertController Power Battery ChargingChanging Settings Procedure to Change SettingsChanging Settings on the RDC2 Controller 7Changing SettingsSetting the Exerciser Setting the Exerciser at Controller Power-upChanging the Exercise Settings Procedure to Set the Exerciser8Procedure to Set the Exerciser on the RDC2 Controller RDC2 Controller Menus Main MenuOverview Menu Engine Metering MenuGenerator Metering Menu Voltage CalibrationGenerator Set Information Menu Genset Run Time MenuSetting the Exerciser Adjusting the Display ContrastGenset System Menu Voltage Regulator VR Voltage AdjATS Status Menu Screens on this page do not appearATS Configuration Menu Changing ATS Configuration SettingsDate and Time Menu Networking Information MenusNetworking Status Submenu DhcpNetworking Configuration Submenu OnCue Plus Password PasswordDhcp Submenu 21Network Configuration Submenu Rbus Information 22RBUS Information SubmenuRemote Devices Submenu From FigureProgrammable Interface Module PIM Status Menu Load Control Module LCM or Load Shed Kit Menus 25Load Control Module LCM or Load Shed Kit Status MenuProcedure to View Event History Event LogRDC2 Controller Operation TP-6880 10/14 DC2 Generator Set/ Transfer Switch Controller DC2 Controller OperationController Keypad Button Button FunctionLED Indication Description5Status Displays, Generator Running Exerciser Reset Exercise ModesMaintenance Timer OnCue Plus PasswordDC2 Controller Operation TP-6880 10/14 Scheduled Maintenance Scheduled Maintenance Service Schedule Oil Change Procedure Lubrication SystemEngine Oil Recommendation Low Oil Pressure ShutdownReset the maintenance timer on the controller Drain the oilReplace the oil filter Fill with oilResetting the Maintenance Timer Spark PlugsModel Resv RDC2 Model Resvl DC2Air Cleaner Service Air Cleaner, 8RESV/RESVL ModelsPaper Element Service Air Cleaner, 10/12RESV/RESVL Models Cooling SystemHazardous noise Can cause hearing loss EZ-273000-J Storage Procedure Scheduled Maintenance TP-6880 10/14 Troubleshooting Fault MessagesIntroduction USB PortTroubleshooting Problem Possible Cause Corrective ActionAppendix a Abbreviations AnsiLCB Page TP-6880 10/14