3.15 ATS Status Menu

ATS menus appear if a Model RXT transfer switch is connected to the generator set. If no transfer switch is connected, or another model ATS is connected to the engine start connections, Remote ATS is displayed on the ATS Status screen.

The ATS Status menu displays Model RXT transfer switch and source information.

The voltage shown in these menus can be calibrated. Follow the safety precautions at the beginning of this manuals. Use a voltmeter to measure the line-to-line voltage and follow the instructions in Figure 3-16 to calibrate the voltage readings.

ATS ---->

Status

 

Note: If there is no Model RXT transfer

 

switch connected to the generator set,

ATS Position:

Remote ATS is displayed and the other

Normal

screens on this page do not appear.

Normal Status:

Not/Acceptable

Emerg. Status:

 

Standby

Note: Sample data shown.

 

Single-phase

Three-phase

Normal Volts:

Normal Voltage:

240.0 V

L1--L2

240 V

Normal Freq.:

Normal Voltage:

60.0 Hz

L2--L3

240 V

Emerg Volts:

Normal Voltage:

240.0 V

L3--L1:

240 V

Emerg. Freq.:

Normal Freq.:

60.0 Hz

 

60.0 Hz

 

Normal Rotation:

 

 

Similar screens appear for

 

 

the emergency source.

Reset

Reset

 

Calibration

Calib? No

<---- Return

Reset

tp6810

Calib? Yes

 

Figure 3-16ATS Status Menu, with Calibration

TP-6880 10/14

Section 3 RDC2 Controller Operation 41

Image 41
Contents TP-6880 10/14a RDC2Product Identification Information Accessory Number Accessory DescriptionGenerator Set Identification Numbers Controller IdentificationTable of Contents DC2 Controller Operation Scheduled MaintenanceTroubleshooting Battery Safety Precautions and InstructionsAccidental Starting Accidental starting Can cause severe injury or deathExhaust System Engine Backfire/Flash FireCarbon monoxide Can Cause Fire Can cause severe injury or deathHazardous voltage Will cause severe injury or death Fuel System Hazardous NoiseHot Parts Heavy EquipmentAccessory Literature Transfer Switch LiteratureIntroduction List of Related LiteratureEmission Information NameplateGenerator Set Application Emission Compliance PeriodService Assistance Service Assistance TP-6880 10/14 Descriptions and Service Views RDC2 Controller Features DC2 Controller Features Carburetor Heater AccessoriesProgrammable Interface Module PIM Load Control Module LCM1214 Service Views3Service View Generator Set Operation Prestart ChecklistGenerator Set Operation TP-6880 10/14 Generator Set Operation Exercising the Generator SetSetting the Exerciser Automatic Operation with Other Transfer SwitchesUnloaded Cycle Exercise with Complete System Diagnostics ExerciseSystem Diagnostics Power Failure During Exercise CycleUnloaded Full-Speed Exercise Loaded Full-Speed Exercise with RXT onlyATS Communication Errors FaultsResetting the Controller after a Fault Shutdown ShutdownsFault Message Shutdown SD Condition Check Fault Shutdown SD Condition Check 3Controller Fault MessagesGenerator Enclosure Thermostat Generator Set Operation TP-6880 10/14 RDC2 Controller Operation RDC2 Generator Set/ Transfer Switch ControllerControls and Indicators Button Controller Keypad LED IndicatorsButton Function LED OperationActive Alert LCD DisplayBattery Charging Controller PowerChanging Settings Procedure to Change Settings7Changing Settings Changing Settings on the RDC2 ControllerSetting the Exerciser at Controller Power-up Setting the ExerciserChanging the Exercise Settings Procedure to Set the Exerciser8Procedure to Set the Exerciser on the RDC2 Controller Main Menu RDC2 Controller MenusEngine Metering Menu Overview MenuVoltage Calibration Generator Metering MenuGenset Run Time Menu Generator Set Information MenuAdjusting the Display Contrast Setting the ExerciserGenset System Menu Voltage Regulator VR Voltage AdjScreens on this page do not appear ATS Status MenuChanging ATS Configuration Settings ATS Configuration MenuNetworking Information Menus Date and Time MenuDhcp Networking Status SubmenuDhcp Submenu Networking Configuration Submenu OnCue Plus PasswordPassword 21Network Configuration Submenu 22RBUS Information Submenu Rbus InformationFrom Figure Remote Devices SubmenuProgrammable Interface Module PIM Status Menu 25Load Control Module LCM or Load Shed Kit Status Menu Load Control Module LCM or Load Shed Kit MenusEvent Log Procedure to View Event HistoryRDC2 Controller Operation TP-6880 10/14 DC2 Controller Operation DC2 Generator Set/ Transfer Switch ControllerButton Button Function Controller KeypadLED Indication Description5Status Displays, Generator Running Exercise Modes Exerciser ResetOnCue Plus Password Maintenance TimerDC2 Controller Operation TP-6880 10/14 Scheduled Maintenance Scheduled Maintenance Service Schedule Lubrication System Oil Change ProcedureEngine Oil Recommendation Low Oil Pressure ShutdownDrain the oil Reset the maintenance timer on the controllerReplace the oil filter Fill with oilSpark Plugs Resetting the Maintenance TimerModel Resv RDC2 Model Resvl DC2Paper Element Service Air Cleaner ServiceAir Cleaner, 8RESV/RESVL Models Cooling System Air Cleaner, 10/12RESV/RESVL ModelsHazardous noise Can cause hearing loss EZ-273000-J Storage Procedure Scheduled Maintenance TP-6880 10/14 Fault Messages TroubleshootingIntroduction USB PortProblem Possible Cause Corrective Action TroubleshootingAnsi Appendix a AbbreviationsLCB Page TP-6880 10/14