3.15 ATS Status Menu
ATS menus appear if a Model RXT transfer switch is connected to the generator set. If no transfer switch is connected, or another model ATS is connected to the engine start connections, Remote ATS is displayed on the ATS Status screen.
The ATS Status menu displays Model RXT transfer switch and source information.
The voltage shown in these menus can be calibrated. Follow the safety precautions at the beginning of this manuals. Use a voltmeter to measure the
ATS
Status
| Note: If there is no Model RXT transfer |
| switch connected to the generator set, |
ATS Position: | Remote ATS is displayed and the other |
Normal | screens on this page do not appear. |
Normal Status:
Not/Acceptable
Emerg. Status: |
|
Standby | Note: Sample data shown. |
|
Normal Volts: | Normal Voltage: | ||
240.0 V | 240 V | ||
Normal Freq.: | Normal Voltage: | ||
60.0 Hz | 240 V | ||
Emerg Volts: | Normal Voltage: | ||
240.0 V | 240 V | ||
Emerg. Freq.: | Normal Freq.: | ||
60.0 Hz |
| 60.0 Hz | |
| Normal Rotation: | ||
|
| Similar screens appear for | |
|
| the emergency source. | |
Reset | Reset |
| |
Calibration | Calib? No | ||
Reset | tp6810 | ||
Calib? Yes | |||
|
Figure 3-16 ATS Status Menu, with Calibration
Section 3 RDC2 Controller Operation 41 |