4.7 Maintenance Timer

The maintenance timer keeps track of the time until the next recommended maintenance according to the maintenance schedule for the generator set. Reset the maintenance timer after changing the oil and performing the other maintenance tasks recommended in Section 5.

To reset the maintenance timer:

1.Press and hold the OFF and AUTO buttons together until Maintenance Timer Reset is displayed.

2.Release the OFF and AUTO buttons.

4.8 OnCue Plus Password

To set the OnCuer Plus password on the DC2 controller,

1.Press the OFF button and verify that the generator set is not running.

2.Press and hold the Exercise button until Press Again to Reset OnCue PW is displayed.

3.Release the Exercise button and press it again within 5 seconds.

Note: If the Exercise button is not pressed within 5 seconds, the controller exits the password reset mode.

4.The genset serial number and new password (PW) will be displayed for 10 seconds. Record the password for entry into the OnCuer Plus program.

TP-6880 10/14

Section 4 DC2 Controller Operation 57

Image 57
Contents TP-6880 10/14a RDC2Product Identification Information Accessory Number Accessory DescriptionGenerator Set Identification Numbers Controller IdentificationTable of Contents Scheduled Maintenance TroubleshootingDC2 Controller Operation Battery Safety Precautions and InstructionsAccidental Starting Accidental starting Can cause severe injury or deathExhaust System Engine Backfire/Flash FireCarbon monoxide Can Cause Fire Can cause severe injury or deathHazardous voltage Will cause severe injury or death Fuel System Hazardous NoiseHot Parts Heavy EquipmentAccessory Literature Transfer Switch LiteratureIntroduction List of Related LiteratureEmission Information NameplateGenerator Set Application Emission Compliance PeriodService Assistance Service Assistance TP-6880 10/14 Descriptions and Service Views RDC2 Controller Features DC2 Controller Features Carburetor Heater AccessoriesProgrammable Interface Module PIM Load Control Module LCM1214 Service Views3Service View Generator Set Operation Prestart ChecklistGenerator Set Operation TP-6880 10/14 Generator Set Operation Exercising the Generator SetSetting the Exerciser Automatic Operation with Other Transfer SwitchesUnloaded Cycle Exercise with Complete System Diagnostics ExerciseSystem Diagnostics Power Failure During Exercise CycleUnloaded Full-Speed Exercise Loaded Full-Speed Exercise with RXT onlyATS Communication Errors FaultsResetting the Controller after a Fault Shutdown ShutdownsFault Message Shutdown SD Condition Check Fault Shutdown SD Condition Check 3Controller Fault MessagesGenerator Enclosure Thermostat Generator Set Operation TP-6880 10/14 RDC2 Generator Set/ Transfer Switch Controller Controls and IndicatorsRDC2 Controller Operation Button Controller Keypad LED IndicatorsButton Function LED OperationActive Alert LCD DisplayBattery Charging Controller PowerChanging Settings Procedure to Change Settings7Changing Settings Changing Settings on the RDC2 ControllerSetting the Exerciser at Controller Power-up Setting the ExerciserChanging the Exercise Settings Procedure to Set the Exerciser8Procedure to Set the Exerciser on the RDC2 Controller Main Menu RDC2 Controller MenusEngine Metering Menu Overview MenuVoltage Calibration Generator Metering MenuGenset Run Time Menu Generator Set Information MenuAdjusting the Display Contrast Setting the ExerciserGenset System Menu Voltage Regulator VR Voltage AdjScreens on this page do not appear ATS Status MenuChanging ATS Configuration Settings ATS Configuration MenuNetworking Information Menus Date and Time MenuDhcp Networking Status SubmenuNetworking Configuration Submenu OnCue Plus Password PasswordDhcp Submenu 21Network Configuration Submenu 22RBUS Information Submenu Rbus InformationFrom Figure Remote Devices SubmenuProgrammable Interface Module PIM Status Menu 25Load Control Module LCM or Load Shed Kit Status Menu Load Control Module LCM or Load Shed Kit MenusEvent Log Procedure to View Event HistoryRDC2 Controller Operation TP-6880 10/14 DC2 Controller Operation DC2 Generator Set/ Transfer Switch ControllerButton Button Function Controller KeypadLED Indication Description5Status Displays, Generator Running Exercise Modes Exerciser ResetOnCue Plus Password Maintenance TimerDC2 Controller Operation TP-6880 10/14 Scheduled Maintenance Scheduled Maintenance Service Schedule Lubrication System Oil Change ProcedureEngine Oil Recommendation Low Oil Pressure ShutdownDrain the oil Reset the maintenance timer on the controllerReplace the oil filter Fill with oilSpark Plugs Resetting the Maintenance TimerModel Resv RDC2 Model Resvl DC2Air Cleaner Service Air Cleaner, 8RESV/RESVL ModelsPaper Element Service Cooling System Air Cleaner, 10/12RESV/RESVL ModelsHazardous noise Can cause hearing loss EZ-273000-J Storage Procedure Scheduled Maintenance TP-6880 10/14 Fault Messages TroubleshootingIntroduction USB PortProblem Possible Cause Corrective Action TroubleshootingAnsi Appendix a AbbreviationsLCB Page TP-6880 10/14