Page 21

21 LEGEND

Deluxe D

 

a50-

 

HP

8364

LOC

SEE NOTE 4

FP1

FP2

RVS

CO

AL

Alarm Relay Contacts

ASTAT

Aquastat

BM

Blower Motor

BMC

Blower Motor Capacitor

BR

Blower Relay

CB

Circuit Breaker

CCCompressor Contactor

CO

Sensor, Condensate Overflow

DTS

Discharge Temperature Switch

ECM

Electronically Commutated Motor

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

HP

High-Pressure Switch

HPWS

High-Pressure Water Switch

HWG

Hot Water Generator

JW1

Clippable Field Selection Jumper

LOC

Loss of Charge Pressure Switch

LON

Local Operating Network

MV

Motorized Valve

NEC

National Electrical Code

P1

Field Wiring Terminal Block

RVS

Reversing Valve Solenoid

TRANS

Transformer

*Optional Wiring.

Field Line Voltage Wiring

Field Low Voltage Wiring

Printed Circuit Trace

Optional Wiring

Relay/Contactor Coil

Condensate Pan

Solenoid Coil

Temperature Switch

Thermistor

Ground

Wire Nut

Relay Contacts - N.C.

Relay Contacts - N.O.

Low Pressure Switch

High Pressure Switch

Splice Cap

Circuit Breaker

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 460 v (BLK/RED) lead for 460/3/60 units. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Typical thermostat wiring shown. Refer to thermostat installation instructions for wiring to the unit. Ther- mostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.

6.Factory cut JW1 jumper. Dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground avail- able from top two standoffs as shown.)

8.Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltages up to 277-v.

9.Place jumpers on 2 and 3, ICM board, when dehumidification mode is used.

10.Optional LON wires. Only connect if LON connection is desired at the wall sensor.

11.Blower motor is factory wired for medium and high speeds. For any other combination of speeds, at the motor attach the BLK wire to the higher of the two desired speed taps and the BLU wire to the lower of the two desired speed taps.

12.Blower motor is factory wired for high and low speeds. No other combination is available.

13.The 460-v units using an ECM (electronically commutated motor) fan motor, modulating HWR, and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.

Fig. 22 — Wiring of 50PTH,PTV,PTD026-072 Units with Deluxe D and LON Controller, Three Phase (460 V)

Image 21
Contents Safety Considerations ContentsGeneral InstallationPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Aux Electric Heat Disconnect Typical Installation 50PTH Unit50PTV Dimensional Data 50PTD Dimensional Data Back Discharge Side DischargeMount the Unit Install Condensate DrainRotate Move to SideTrap Condensate Drain Horizontal Unit PitchDrains field-installed Typical Ground-Water Piping InstallationWire Field Power Supply Water Quality GuidelinesMetal Hose Minimum Bend Radii 50PTH,PTV,PTD Electrical Data Sensor, Water Coil Freeze Protection Alarm Relay ContactsTrans RVSECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 8364 A50SPT LWTWshp Open Control A50-8571Rnet Wiring Specifications Field-Supplied Sensors for Wshp Open ControllerSPT Sensors Rnet Wiring Wire Field ControlsWire Terminal A50-8443A50-7764tf A50-8141A50-8441 A50-8442Dehumidificaton Mode Settings Cooling SettingsHeating Settings CFM Adjust SettingsBlower Performance Data PRE-START-UP Wshp Open Fan Only / Low Fan and Med Fan AirflowWshp Open High Fan Airflow Complete C Control Jumper Settings Deluxe D Control Jumper SettingsField Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings Units with Modulating Hot Water Reheat HWR OptionHWR Operating Modes Mode Input OutputOperating Limits START-UPA50-8145 Water Out Operating Limits 50PTH, PTV, PTD UnitsUnit Start-Up Cooling Mode Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger Suction Discharge Super Sub Water Air Temp A50-8444 Unit Start-Up with Wshp Open ControlsCoaxial Water Pressure Drop Unit 50PTH, PTV Water Temperature F GPMPTD 026 038 049Antifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Page LED Status Description of Operation Alarm Relay Complete C Control LED Code Fault DescriptionsLED Fault Description Code Complete C and Deluxe D Board System TestAquazone Deluxe D Control LED Indica Alarm RelayService Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s Bat80.0 90.070.0 KOhm 60.0 50.0Page Fault Description Solution ECM TroubleshootingA50-8448 ECM Pin ConnectorsA50-8447 ECM Troubleshooting Flow DiagramWshp Troubleshooting Fault Heating Cooling Possible Cause SolutionGood Practices No Fault Code Shown Code 7 Auto ResettingOver/Under Voltage Performance MonitorHigh Head Pressure Temperature in HeatingLow Suction Pressure Low Discharge AirAlarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50PTH,PTV,PTD START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8449 A50-8450