Carrier PTV, 50PTH specifications Lwt, Spt

Page 22

 

 

 

 

 

Deluxe D

22

 

 

 

 

 

 

LEGEND

 

 

NOTES:

AL

Alarm Relay Contacts

Field Line Voltage Wiring

 

ASTAT

Aquastat

Relay Contacts - N.C.

1.

Compressor and blower motor thermally protected internally.

 

BM

Blower Motor

Field Low Voltage Wiring

 

2.

All wiring to the unit must comply with NEC and local codes.

BMC

Blower Motor Capacitor

Relay Contacts - N.O.

3.

208-240 60 Hz units are wired for 208v operation. For 240v 60 Hz

 

BR

Blower Relay

Printed Circuit Trace

Low Pressure Switch

 

operation switch RED wire to ORG wire. 2240240v 50 Hz units are

CB

Circuit Breaker

 

wired for 240v operation. For 220v 50 Hz operation switch ORG

 

 

CC

Compressor Contactor

Optional Wiring

High Pressure Switch

 

wire to RED. Transformer is energy limiting or may have circuit

DTS

Discharge Temperature Switch

 

 

breaker.

ECM

Electronically Commutated Motor

Relay/Contactor Coil

Circuit Breaker

4.

FP1 thermistor provides low temperature protection for water.

FP1

Sensor, Water Coil Freeze Protection

 

When using antifreeze solutions, cut JW3 jumper.

 

 

 

FP2

Sensor, Air Coil Freeze Protection

 

 

5.

Refer to thermostat installation, application and operation manual

HP

High-Pressure Switch

Condensate Float Switch

Splice Cap

 

for control wiring to the unit. Wire from ECM to “Y” CXM when a

HPWS

High-Pressure Water Switch

 

 

 

motorized valve is not used. Thermostat wiring must be “Class 1”

HWG

Hot Water Generator

Solenoid Coil

 

 

and volatage rating equal to or greater than unit supply voltage.

JW

Jumper Wire

 

 

6.

24v alarm signal shown. For dry alarm contact, cut JW1 jumper.

LOC

Loss of Charge Pressure Switch

Temperature Switch

 

 

Dry contact will be available between AL1 and AL2.

LWT

Leaving Water Temperature

Thermistor

 

7.

Transformer secondary ground via green wire with yellow stripe

MV

Motorized Valve

 

 

from “C” terminal to control box

MVES

Motorized Valve End Switch

Ground

 

8.

Aquastat is supplied with unit and must be wired in series with the

NEC

National Electrical Code

 

 

hot leg to the pump. Aquastat is rated for voltages up to 277v.

P1

Field Wiring Terminal Block

Wire Nut

 

9.

For field-installed two-position hot water reheat coils disconnect

RH

Relative Humidity

 

 

wire from terminal W1 and connect to field-supplied hot water

 

 

 

RVS

Reversing Valve Solenoid

 

* Optional wiring.

 

valve.

SPT

Space Temperature Sensor

 

 

 

 

 

 

 

TRANS

Transformer

 

 

 

 

Fig. 23 — Wiring of 50PTH,PTV,PTD026-072 with Deluxe D and WSHP Open Multiple Protocol Controls (Single-Phase 208-230 V)

Image 22
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Typical Installation 50PTH Unit Aux Electric Heat Disconnect50PTV Dimensional Data 50PTD Dimensional Data Side Discharge Back DischargeRotate Install Condensate DrainMount the Unit Move to SideHorizontal Unit Pitch Trap Condensate DrainTypical Ground-Water Piping Installation Drains field-installedWater Quality Guidelines Wire Field Power SupplyMetal Hose Minimum Bend Radii 50PTH,PTV,PTD Electrical Data Alarm Relay Contacts Sensor, Water Coil Freeze ProtectionRVS TransECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 A50 8364LWT SPTA50-8571 Wshp Open ControlField-Supplied Sensors for Wshp Open Controller Rnet Wiring SpecificationsSPT Sensors Wire Terminal Wire Field ControlsRnet Wiring A50-8443A50-8441 A50-8141A50-7764tf A50-8442Heating Settings Cooling SettingsDehumidificaton Mode Settings CFM Adjust SettingsBlower Performance Data Wshp Open Fan Only / Low Fan and Med Fan Airflow PRE-START-UPWshp Open High Fan Airflow Deluxe D Control Jumper Settings Complete C Control Jumper SettingsField Selectable Inputs Humidistat/Dehumidistat Logic Deluxe D DIP Switch Settings DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Units with Modulating Hot Water Reheat HWR OptionMode Input Output HWR Operating ModesA50-8145 Water Out START-UPOperating Limits Operating Limits 50PTH, PTV, PTD UnitsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Suction Discharge Super Sub Water Air Temp Unit Start-Up with Wshp Open Controls A50-8444PTD Unit 50PTH, PTV Water Temperature F GPMCoaxial Water Pressure Drop 026 038 049Operation Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Page LED Fault Description Code Complete C Control LED Code Fault DescriptionsLED Status Description of Operation Alarm Relay Complete C and Deluxe D Board System TestAlarm Relay Aquazone Deluxe D Control LED IndicaService Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Replacing the Wshp Open Controller’s Bat70.0 90.080.0 KOhm 60.0 50.0Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Fault Heating Cooling Possible Cause Solution Wshp TroubleshootingGood Practices Over/Under Voltage Code 7 Auto ResettingNo Fault Code Shown Performance MonitorLow Suction Pressure Temperature in HeatingHigh Head Pressure Low Discharge AirStatus Appendix a Wshp Open Screen ConfigurationAlarm Status SensorSystem Settings Appendix a Wshp Open Screen ConfigurationMaintenance ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm Page Page Copyright 2010 Carrier Corporation 50PTH,PTV,PTD START-UP Checklist II. START-UPA50-8449 Heating Cycle AnalysisCooling Cycle Analysis A50-8450