Carrier 50PTH, PTV specifications Mount the Unit, Install Condensate Drain, Rotate, Move to Side

Page 9

5.Check refrigerant tubing for contact with other compo- nents. Adjust if necessary.

6.Reinstall top panel using screws set aside in Step 1.

NOTE: Location for some screws at bottom of discharge panel may have to be changed.

7.Manually spin fan wheel to check for obstructions. Adjust for any obstruction found.

8.Replace access panel.

Water

Remove Screws

Connection End

 

Return Air

Side Discharge

Water

Connection End

Rotate

Return Air

Move to Side

Water

Replace Screws

Connection End

 

Return Air

Drain

Back Discharge

Discharge Air

Fig. 8 — Conversion Left Return,

Side Discharge to Back Discharge

Back to Side Discharge Conversion — Follow instructions above for Side to Back Discharge Conversion, noting the panels would be reversed.

Step 4 — Mount the Unit

HORIZONTAL UNIT (50PTH) — Horizontal units should be mounted using the factory-installed hangers. Proper attach- ment of hanging rods to building structure is critical for safety. See Fig. 1. Rod attachments must be able to support the weight of the unit. See Table 1 for unit operating weights.

VERTICAL UNITS (50PTV,PTD) — Vertical and downflow units are available in left or right return air configurations. See Fig. 3 and 4. Mount the unit (except 50PTD) on a vibration absorption pad slightly larger than the entire base to minimize vibration transmission. It is not necessary to mount the unit on the floor. See Fig. 9.

NOTE: Some codes require the use of a secondary drain pan under vertical units. Check local codes for more information.

Fig. 9 — 50PTV Units Mounted With

Vibration Absorption Pad

Step 5 — Check Duct System — Size the duct sys- tem to handle the design airflow quietly.

NOTE: Depending on the unit, the fan wheel may have a ship- ping support installed at the factory. This must be removed before operating unit.

SOUND ATTENUATION — To eliminate the transfer of vibration to the duct system, a flexible connector is recom- mended for both discharge and return air duct connections on metal duct systems. The supply and return plenums should in- clude internal duct liner of fiberglass or be made of duct board construction to maximize sound attenuation of the blower. Installing the WSHP unit to uninsulated ductwork in an uncon- ditioned space is not recommended since it will sweat and adversely affect the unit’s performance.

To reduce air noise, at least one 90-degree elbow could be included in the supply and return air ducts, provided system performance is not adversely impacted. The blower speed can also be changed in the field to reduce air noise or excessive air- flow, provided system performance is not adversely impacted.

EXISTING DUCT SYSTEM — If the unit is connected to existing ductwork, consider the following:

Verify that the existing ducts have the proper capacity to handle the unit airflow. If the ductwork is too small, install larger ductwork.

Check existing ductwork for leaks and repair as necessary.

NOTE: Local codes may require ventilation air to enter the space for proper indoor air quality. Hard-duct ventilation may be required for the ventilating air supply. If hard ducted ventilation is not required, be sure that a proper air path is provided for ventilation air to unit to meet ventila- tion requirement of the space.

Step 6 — Install Condensate Drain

HORIZONTAL UNIT (50PTH) — Slope the unit toward the drain at 1/4 in. See Fig. 10. If it is not possible to meet the re- quired pitch, install a condensate at the unit to pump conden- sate to building drain.

Horizontal units are not internally trapped, therefore an ex- ternal trap is necessary. Install each unit with its own individual trap and means to flush or blow out the condensate drain line. Do not install units with a common trap or vent. See Fig. 11 for typical condensate connections.

NOTE: Never use a pipe size smaller than the connection.

VERTICAL UNITS (50PTV,PTD) — Each unit uses a con- densate hose inside all cabinets as a trapping loop, therefore an external trap is not necessary. See Fig. 12.

9

Image 9
Contents Safety Considerations ContentsGeneral InstallationPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Aux Electric Heat Disconnect Typical Installation 50PTH Unit50PTV Dimensional Data 50PTD Dimensional Data Back Discharge Side DischargeMount the Unit Install Condensate DrainRotate Move to SideTrap Condensate Drain Horizontal Unit PitchDrains field-installed Typical Ground-Water Piping InstallationWire Field Power Supply Water Quality GuidelinesMetal Hose Minimum Bend Radii 50PTH,PTV,PTD Electrical Data Sensor, Water Coil Freeze Protection Alarm Relay ContactsTrans RVSECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 8364 A50SPT LWTWshp Open Control A50-8571Rnet Wiring Specifications Field-Supplied Sensors for Wshp Open ControllerSPT Sensors Rnet Wiring Wire Field ControlsWire Terminal A50-8443A50-7764tf A50-8141A50-8441 A50-8442Dehumidificaton Mode Settings Cooling SettingsHeating Settings CFM Adjust SettingsBlower Performance Data PRE-START-UP Wshp Open Fan Only / Low Fan and Med Fan AirflowWshp Open High Fan Airflow Complete C Control Jumper Settings Deluxe D Control Jumper SettingsField Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings Units with Modulating Hot Water Reheat HWR OptionHWR Operating Modes Mode Input OutputOperating Limits START-UPA50-8145 Water Out Operating Limits 50PTH, PTV, PTD UnitsUnit Start-Up Cooling Mode Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger Suction Discharge Super Sub Water Air Temp A50-8444 Unit Start-Up with Wshp Open ControlsCoaxial Water Pressure Drop Unit 50PTH, PTV Water Temperature F GPMPTD 026 038 049Antifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Page LED Status Description of Operation Alarm Relay Complete C Control LED Code Fault DescriptionsLED Fault Description Code Complete C and Deluxe D Board System TestAquazone Deluxe D Control LED Indica Alarm RelayService Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s Bat80.0 90.070.0 KOhm 60.0 50.0Page Fault Description Solution ECM TroubleshootingA50-8448 ECM Pin ConnectorsA50-8447 ECM Troubleshooting Flow DiagramWshp Troubleshooting Fault Heating Cooling Possible Cause SolutionGood Practices No Fault Code Shown Code 7 Auto ResettingOver/Under Voltage Performance MonitorHigh Head Pressure Temperature in HeatingLow Suction Pressure Low Discharge AirAlarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50PTH,PTV,PTD START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8449 A50-8450