5.Check refrigerant tubing for contact with other compo- nents. Adjust if necessary.
6.Reinstall top panel using screws set aside in Step 1.
NOTE: Location for some screws at bottom of discharge panel may have to be changed.
7.Manually spin fan wheel to check for obstructions. Adjust for any obstruction found.
8.Replace access panel.
Water | Remove Screws |
Connection End |
|
Return Air
Side Discharge
Water
Connection End
Rotate
Return Air
Move to Side
Water | Replace Screws |
Connection End |
|
Return Air
Drain
Back Discharge | Discharge Air |
Fig. 8 — Conversion Left Return,
Side Discharge to Back Discharge
Back to Side Discharge Conversion — Follow instructions above for Side to Back Discharge Conversion, noting the panels would be reversed.
Step 4 — Mount the Unit
HORIZONTAL UNIT (50PTH) — Horizontal units should be mounted using the
VERTICAL UNITS (50PTV,PTD) — Vertical and downflow units are available in left or right return air configurations. See Fig. 3 and 4. Mount the unit (except 50PTD) on a vibration absorption pad slightly larger than the entire base to minimize vibration transmission. It is not necessary to mount the unit on the floor. See Fig. 9.
NOTE: Some codes require the use of a secondary drain pan under vertical units. Check local codes for more information.
Fig. 9 — 50PTV Units Mounted With
Vibration Absorption Pad
Step 5 — Check Duct System — Size the duct sys- tem to handle the design airflow quietly.
NOTE: Depending on the unit, the fan wheel may have a ship- ping support installed at the factory. This must be removed before operating unit.
SOUND ATTENUATION — To eliminate the transfer of vibration to the duct system, a flexible connector is recom- mended for both discharge and return air duct connections on metal duct systems. The supply and return plenums should in- clude internal duct liner of fiberglass or be made of duct board construction to maximize sound attenuation of the blower. Installing the WSHP unit to uninsulated ductwork in an uncon- ditioned space is not recommended since it will sweat and adversely affect the unit’s performance.
To reduce air noise, at least one
EXISTING DUCT SYSTEM — If the unit is connected to existing ductwork, consider the following:
•Verify that the existing ducts have the proper capacity to handle the unit airflow. If the ductwork is too small, install larger ductwork.
•Check existing ductwork for leaks and repair as necessary.
NOTE: Local codes may require ventilation air to enter the space for proper indoor air quality.
Step 6 — Install Condensate Drain
HORIZONTAL UNIT (50PTH) — Slope the unit toward the drain at 1/4 in. See Fig. 10. If it is not possible to meet the re- quired pitch, install a condensate at the unit to pump conden- sate to building drain.
Horizontal units are not internally trapped, therefore an ex- ternal trap is necessary. Install each unit with its own individual trap and means to flush or blow out the condensate drain line. Do not install units with a common trap or vent. See Fig. 11 for typical condensate connections.
NOTE: Never use a pipe size smaller than the connection.
VERTICAL UNITS (50PTV,PTD) — Each unit uses a con- densate hose inside all cabinets as a trapping loop, therefore an external trap is not necessary. See Fig. 12.
9