BM (ECM)
SW1 |
SW2 |
SW3 |
SW4
SW5
SW6
SW7
SW8
SW9
OFF ON
ECM
INTERFACE
BOARD
17
LEGEND
AL | — Alarm Relay Contacts | P1 | — Field Wiring Terminal Block | |||||||||
ASTAT | — Aquastat | RVS | — Reversing Valve Solenoid | |||||||||
BM | — Blower Motor | TRANS | — Transformer | |||||||||
CB | — Circuit Breaker |
|
|
|
|
|
|
|
|
|
| Field Line Voltage Wiring |
CC | — Compressor Contactor |
|
|
|
|
|
|
|
|
|
| Field Low Voltage Wiring |
CO | — Sensor, Condensate Overflow |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| Printed Circuit Trace | ||
COMPR | — Compressor |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
DDC | — Direct Digital Control |
|
|
|
|
|
|
|
|
|
| Relay/Contactor Coil |
DTS | — Discharge Temp Switch |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
ECM | — Electronically Commutated Motor |
|
|
|
|
|
|
|
|
|
| Condensate Pan |
FP1 | — Sensor, Water Coil Freeze Protection |
|
|
|
|
|
|
|
|
|
| |
FP2 | — Sensor, Air Coil Freeze Protection |
|
|
|
|
|
|
|
|
|
| Solenoid Coil |
HP | — |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
HWG | — Hot Water Generator |
|
|
|
|
|
|
|
|
|
| Thermistor |
JW1 | — Jumper, Alarm |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
NSB | — Digital Night Setback |
|
|
|
|
|
|
|
|
|
| Ground |
LOC | — Loss of Charge Pressure Switch |
|
|
|
|
|
|
|
|
|
| Wire Nut |
MV | — Motorized Valve |
|
|
|
|
|
|
|
|
|
| |
NEC | — National Electrical Code |
|
|
|
|
|
|
|
|
|
|
|
BM (ECM)
|
| J1 |
|
| Y |
W | R | S1 |
| CFM | |
|
| SW1 |
O |
|
|
|
|
| SW2 |
| |
G |
|
|
|
| SW3 |
| ||
|
|
|
|
|
| SW4 |
| |
|
|
|
|
|
| SW5 |
| |
Y2 | G |
|
|
|
| SW6 |
| |
|
|
|
| SW7 |
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
| SW8 |
| |
Y1 | G |
|
|
|
| SW9 |
| |
|
|
|
|
| OFF | ON | ||
|
|
|
|
|
|
| ||
G | G | TB1 |
|
|
| G | DEHUM | |
|
|
|
|
|
|
|
| |
R | C | Y2 Y1 G | O | W | C | R DH AL1 A | A | AL1 |
NOTES:
1.Compressor and blower motor thermally protected internally.
2.All wiring to the unit must comply with NEC and local codes.
3.Transformer for 208/230 v will be connected for 208 v operation. For 230 v operation, dis- connect RED lead at L1 and attach ORN lead to L1. Insulate open end of RED lead. Trans- former for 220/240 v will be connected for 220 v operation. For 240 v operation, disconnect RED lead at L1 and attach ORN lead to L1. Transformer is energy limiting or may have cir- cuit breaker.
4.FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.
5.Typical Aquazone™ thermostat wiring shown. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.
6.
7.Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
8.Aquastat is
9.Place jumpers on 2 and 3, ECM board, when dehumidification mode is used.