Water | Flow |
Control | Regulator |
Valve | |
accessory) | |
accessory) |
|
Pressure
Tank
Water Out
Water In
From Pump
Boiler
Drains (field-installed)
Valve
Strainer
Fig. 13 — Typical Ground-Water Piping Installation
Water Supply and Quantity — Check water supply. Water supply should be plentiful and of good quality. See Table 2 for water quality guidelines.
IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed- system application design requirements may cause damage to the
In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water treat- ment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits.
•Limit piping materials to only polyethylene fusion in the buried sections of the loop.
•Do not use galvanized or steel fittings at any time due to corrosion.
•Avoid all plastic to metal threaded fittings due to the poten- tial to leak. Use a flange fitted substitute.
•Do not overtighten connections.
•Route piping to avoid service access areas to unit.
•Use
INSTALLATION OF SUPPLY AND RETURN HOSE KIT — Follow these piping guidelines.
1.Install a drain valve at the base of each supply and return riser to facilitate system flushing.
2.Install shutoff/balancing valves and unions at each unit to permit unit removal for servicing.
3.Place strainers at the inlet of each system circulating pump.
4.Select the proper hose length to allow slack between con- nection points. Hoses may vary in length by +2% to
5.Refer to Table 3. Do not exceed the minimum bend radius for the hose selected. Exceeding the minimum bend radi- us may cause the hose to collapse, which reduces water flow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum.
NOTE: Piping must comply with all applicable codes.
Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum ex- pected dew point of the pipe ambient. Insulation is required if loop water temperature drops below the dew point.
CAUTION
Do not bend or kink supply lines or hoses.
Pipe joint compound is not necessary when Teflon threaded tape is
NOTE: When
Maximum allowable torque for brass fittings is 30
Optional
CAUTION
Backup wrench is required when tightening water connec- tions to prevent water line damage.
Refer to Fig. 14 for an illustration of a supply/return hose kit. Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life.
11