Carrier 50PTH, PTV specifications A50-8571, Wshp Open Control

Page 23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+ 24vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Gnd

 

 

 

 

 

 

 

 

 

 

 

 

Fan (DO-1) (Fan On or Low Speed)

 

FIELD INSTALLED (OPTIONAL) – SEE NOTE 2

 

 

 

 

Aux Heat (DO-2)

 

 

 

 

 

 

 

 

 

 

 

 

 

Reversing Valve (DO-3)

NC FIRE/SMOKE

 

SPACE RH

PRIMARY

SPACE CO2

 

PRIMARY

Comp #2 (DO-4)

DETECTOR CONTACT

 

SENSOR

 

 

 

 

SENSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

Comp #1 (DO-5)

(FIELD-INSTALLED)

 

+24vac

 

 

 

 

+24vac

 

 

 

 

 

 

Comp Status (DI-5) (If not installed, it must be connected to DO-5)

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LWT (Input 6)

 

 

4-20mA

 

 

 

 

4-20mA

 

 

 

 

 

 

 

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

SAT (LAT) (Input 7)

AO1 – Aux Reheat or Cond.

WTR. Loop Econ. (AO 1)

 

 

 

 

 

J1

 

J2

 

 

 

 

 

 

1

10

1

7

6

5

4

3

2

 

CONDENSATE

1

 

 

 

 

 

 

 

 

 

 

OVERFLOW SWITCH

J4

8

7

6

5

4

3

2

1

J5

REMOTE OCCUPANCY/

FAN STATUS SWITCH (FIELD-INSTALLED)

OA DAMPER (AO-2)

(FIELD-INSTALLED)

 

 

 

 

 

LEGEND

AI

 

 

 

Analog Input

AO

 

 

 

Analog Output

BI

 

 

 

Binary Input

BO

 

 

 

Binary Output

SPT

 

 

 

Space Temperature

 

 

 

 

 

 

 

 

 

Factory Wiring

 

 

 

 

 

 

 

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

NOTES:

10.Mount the water source heat pump controller in the equipment controls enclosure with at least two #6 x 1 in. self-tapping screws. Allow adequate clearance for wiring.

11.Verify sensor power and wiring requirements prior to making any terminations. Sen- sors requiring a separate isolated 24 vac power source will not utilize WSHP termi- nals J4-1, or 4.

a50-8571

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J22

 

 

J11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Installed

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Local Access Port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J12

 

 

 

4 5

FAN SPEED (DO-7) (MED OR LOW)

 

WSHP Open Inputs and Outputs Table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSB

 

 

LSB

 

 

4

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

3

BLACK

 

To

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

0

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

9

1

 

 

9

1

 

 

2

WHITE

 

SPT PLUS

 

 

2

 

 

 

 

 

CONNECTION

CHANNEL

 

 

 

 

2

 

 

 

 

 

 

 

 

 

INPUT/OUTPUT TYPE

 

PART NUMBERS

TYPE OF I/O

 

8

 

 

 

8

 

 

 

2

 

 

 

 

FAN SPEED (DO-8) (HIGH OR FAN ON )

 

 

7

 

 

 

3

7

 

 

 

3

 

1

GREEN

 

 

 

 

1

 

PIN NUMBERS

DESIGNATION

 

 

 

4

 

 

4

 

 

 

 

 

 

 

 

 

 

 

6

 

5

 

6

 

5

 

 

 

 

 

 

 

 

 

 

 

Inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSTP Baud

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Space Temperature Sensor

 

SPS, SPPL, SPP

Communicating

J13, 1 - 4

Local Access Port

 

 

 

9600

19.2k

38.4k

76.8k

 

 

 

 

 

 

J17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Space Relative Humidity

 

33ZCSENSRH-01

AI (4 - 20mA)

J4, 5 and 6

Analog Input 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Air Quality

 

33ZCSENCO2

AI (4 -20mA)

J4, 2 and 3

Analog Input 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

J14

 

Condensate Switch

 

N/A

BI (Dry Contacts)

J1, 2

Binary Input 3

 

 

 

 

 

 

 

 

 

 

 

N

4

3

2

1

J19

 

 

 

 

Stage 1 Compressor Status

 

N/A

BI (Dry Contacts)

J1, 10

Binary Input 5

 

8

 

7

6

5

4

3

 

2

1

O

 

 

 

 

Leaving Condenser Water Temperature

 

10K Type II

AI (10K Thermistor)

J2, 1 and 2

Analog Input 6

 

 

 

 

J20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply Air Temperature

 

33ZCSENSAT

AI (10K Thermistor)

J2, 3 and 4

Analog Input 7

FIELD INSTALLED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPT PLUS Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modulating Valve (Auxiliary Heat/Water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shown

 

 

 

 

 

 

 

 

 

 

N/A

AO (0-10Vdc/2 - 10Vdc)

J2 4 and 5*

Analog Output 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Economizer)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside Air Damper

 

N/A

AO (0-10Vdc/2 - 10Vdc)

J22 1 and 2*

Analog Output 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply Fan On/Low Speed

 

N/A

BO Relay (24VAC, 1A)

J1, 4*

Binary Output 1 (G)

To WSHPController RnetTerminals(J13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED1

 

 

(3 Speed Only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5BT81BT4-012207

 

Auxiliary Heat or 2-Position Water Loop

 

 

 

 

 

 

 

BLACK

 

WHITE

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N/A

BO Relay (24VAC, 1A)

J1, 5*

Binary Output 2

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Install BT485 where device is

Reversing Valve (B or O Operation)

 

N/A

BO Relay (24VAC, 1A)

J1, 6*

Binary Output 3 (RV)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

located at the end of network

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

segment only.

 

Compressor 2nd Stage

 

N/A

BO Relay (24VAC, 1A)

J1, 7

Binary Output 4 (Y2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 1st Stage

 

N/A

BO Relay (24VAC, 1A)

J1, 8

Binary Output 5 (Y1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification Relay

 

N/A

BO Relay (24VAC, 1A)

J11, 7 and 8 (NO)

Binary Output 6

 

+12V

 

Rnet-

 

Rnet+

Gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Speed Medium/Low (3 Speed Only)

N/A

BO Relay (24VAC, 1A)

J11, 5 and 6 (NO)*

Binary Output 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Speed High/Low (3 Speed Only)

 

N/A

BO Relay (24VAC, 1A)

J11, 2 and 3 (NO)*

Binary Output 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*These inputs are configurable.

 

 

 

 

 

Fig. 24 — WSHP Open Control

Image 23
Contents Safety Considerations ContentsGeneral InstallationPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Aux Electric Heat Disconnect Typical Installation 50PTH Unit50PTV Dimensional Data 50PTD Dimensional Data Back Discharge Side DischargeMove to Side Install Condensate DrainMount the Unit RotateTrap Condensate Drain Horizontal Unit PitchDrains field-installed Typical Ground-Water Piping InstallationMetal Hose Minimum Bend Radii Wire Field Power SupplyWater Quality Guidelines 50PTH,PTV,PTD Electrical Data Sensor, Water Coil Freeze Protection Alarm Relay ContactsTrans RVSECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 8364 A50SPT LWTWshp Open Control A50-8571SPT Sensors Rnet Wiring SpecificationsField-Supplied Sensors for Wshp Open Controller A50-8443 Wire Field ControlsRnet Wiring Wire TerminalA50-8442 A50-8141A50-7764tf A50-8441CFM Adjust Settings Cooling SettingsDehumidificaton Mode Settings Heating SettingsBlower Performance Data Wshp Open High Fan Airflow PRE-START-UPWshp Open Fan Only / Low Fan and Med Fan Airflow Field Selectable Inputs Complete C Control Jumper SettingsDeluxe D Control Jumper Settings Units with Modulating Hot Water Reheat HWR Option DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Humidistat/Dehumidistat Logic Deluxe D DIP Switch SettingsHWR Operating Modes Mode Input OutputOperating Limits 50PTH, PTV, PTD Units START-UPOperating Limits A50-8145 Water OutWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Suction Discharge Super Sub Water Air Temp A50-8444 Unit Start-Up with Wshp Open Controls026 038 049 Unit 50PTH, PTV Water Temperature F GPMCoaxial Water Pressure Drop PTDUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Page Page Complete C and Deluxe D Board System Test Complete C Control LED Code Fault DescriptionsLED Status Description of Operation Alarm Relay LED Fault Description CodeAquazone Deluxe D Control LED Indica Alarm RelayService Replacing the Wshp Open Controller’s Bat TroubleshootingRefrigerant Charging Air Coil Fan Motor RemovalKOhm 60.0 50.0 90.080.0 70.0Page Fault Description Solution ECM TroubleshootingA50-8448 ECM Pin ConnectorsA50-8447 ECM Troubleshooting Flow DiagramGood Practices Wshp TroubleshootingFault Heating Cooling Possible Cause Solution Performance Monitor Code 7 Auto ResettingNo Fault Code Shown Over/Under VoltageLow Discharge Air Temperature in HeatingHigh Head Pressure Low Suction PressureSensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Test Appendix a Wshp Screen Open ConfigurationService Screen Name Configuration ServicePoint Name Password Editable Range Default Level Alarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50PTH,PTV,PTD START-UP ChecklistA50-8450 Heating Cycle AnalysisCooling Cycle Analysis A50-8449