| Refrigerant In |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
(To Water Loop) | Mixing Valve |
|
|
|
|
|
|
| (Cooling) |
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Water In |
|
| Internal Pump |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| COAX |
|
|
| ||||||||||||||
(From Water Loop) |
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
| Refrigerant Out |
|
|
| |||||||||||||||||
|
|
|
|
|
| (Cooling) | Entering Air |
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: All components shown are | Evaporator Coil | |
internal to the heat pump unit. | ||
|
Leaving
Air
Reheat
Coil
Fig. 33 — HWR Schematic
START-UP
Use the procedure outlined below to initiate proper unit
NOTE: This equipment is designed for indoor installation only.
Operating Limits
ENVIRONMENT — This equipment is designed for indoor installation ONLY. Extreme variations in temperature, humidi- ty and corrosive water or air will adversely affect the unit per- formance, reliability and service life.
POWER SUPPLY — A voltage variation of ± 10% of name- plate utilization voltage is acceptable.
UNIT STARTING CONDITIONS — Units start and operate in an ambient temperature of 45 F with
NOTE: These operating limits are not normal or continuous operating conditions. Assume that such a
WARNING
When the disconnect switch is closed, high voltage is pres- ent in some areas of the electrical panel. Exercise caution when working with the energized equipment.
3.Balance airflow at registers.
4.Adjust all valves to the full open position and turn on the line power to all heat pump units.
5.Operate unit in the cooling cycle first, then the heating cycle. Refer to Table 18 for unit operating limits. Al- low 15 minutes between cooling and heating tests for pressure to equalize.
NOTE: Two factors determine the operating limits of a unit:
Table 18 — Operating Limits —
50PTH, PTV, PTD Units
AIR LIMITS | COOLING (F) | HEATING (F) |
Min. Ambient Air | 45 | 40 |
Rated Ambient Air | 80 | 70 |
Max. Ambient Air | 100 | 85 |
Min. Entering Air | 50 | 40 |
Rated Entering Air db/wb | 80/67 | 70 |
Max. Entering Air db/wb | 110/83 | 80 |
WATER LIMITS |
|
|
Min. Entering Water | 30 | 20 |
Normal Entering Water | ||
Max. Entering Water | 120 | 90 |
LEGEND |
|
|
db — Dry Bulb wb — Wet Bulb
1.Restore power to system.
2.Turn thermostat fan position to ON. Blower should start.
NOTE: Value in heating column is dry bulb only. Any wet bulb reading is acceptable.
33