CAUTION

Puron® refrigerant (R-410A) requires the use of synthetic lubricant (POE oil). Do not use common tools on systems that contain R-22 refrigerants or mineral oil. Contamina- tion and failure of this equipment may result.

IMPORTANT: Due to the hygroscopic nature of the POE oil in Puron refrigerant (R-410A) and other envi- ronmentally sound refrigerants, any component replace- ment must be conducted in a timely manner using caution and proper service procedure for these types of refrigerants. A complete installation instruction will be included with each replacement TXV/filter drier assem- bly. It is of critical importance these instructions are carefully understood and followed. Failure to follow these instructions can result in a system that is contami- nated with moisture to the extent that several filter drier replacements may be required to properly dry the system.

IMPORTANT: Repair of any sealed refrigerant system requires training in the use of refrigeration tools and proce- dures. Repair should only be attempted by a qualified ser- vice technician. A universal refrigerant handling certificate will be required. Local and/or state license or certificate may also be required.

See Tables 30-32 for additional troubleshooting information.

CAUTION

Disconnect power from unit before removing or replacing connectors, or servicing motor. Wait 5 minutes after dis- connecting power before opening motor.

Table 30 — ECM Troubleshooting

FAULT

DESCRIPTION

SOLUTION

Motor rocks slightly when

 

This is normal start-up for ECM.

starting

 

 

Motor will not start

No movement

Check power at motor.

 

 

Check low voltage (24-vac R to C) at motor.

 

 

Check low voltage connections (G,Y, W, R, C) at motor.

 

 

Check for unseated pins in connectors on motor harness. See Fig. 39.

 

 

Test with a temporary jumper between R and G.

 

 

Check motor for tight shaft.

 

 

Perform motor/control replacement check.

 

 

Run moisture check. See Moisture Check section in Troubleshooting.

 

Motor rocks

Check for loose or non-compliant motor mount.

 

 

Make sure blower wheel is tight on shaft.

 

 

Perform motor/control replacement check.

Motor oscillates up and down

 

It is normal for motor to oscillate with no load on shaft.

while being tested off of blower

 

 

Motor starts, but runs erratically

Varies up and down or intermittent

Check line voltage for variation or “sag.”

 

 

Check low voltage connections (G,Y, W, R, C) at motor, unseated pins in motor harness

 

 

connectors. See Fig. 39.

 

 

Check “Bk” for erratic cfm command (in variable speed applications).

 

 

Check system controls, thermostat.

 

 

Perform moisture check. See Moisture Check section in Troubleshooting.

 

“Hunts” or “puffs” at high cfm

If removing panel or filter reduces “puffing,” reduce restriction or reduce maximum airflow.

 

(speed)

 

 

Stays at low cfm despite system

Check low voltage (thermostat) wires and connections.

 

call for cool or heat cfm

 

 

 

Verify fan is not in delay mode. Wait until delay is complete.

 

 

Check to see if “R” is missing/not connected at motor.

 

 

Perform motor/control replacement check.

 

Stays at high cfm

Check to see if “R” is missing/not connected at motor.

 

 

Verify fan is not in delay mode. Wait until delay is complete.

 

 

Perform motor/control replacement check.

 

Blower will not shut off

Check to see if there is current leakage from controls into G, Y, or W. Check for Triac switched

 

 

thermostat or solid state relay.

Excessive noise

Noisy blower or cabinet

Determine if it’s air, cabinet, duct, or motor noise.

 

 

Check for loose blower housing, panels, etc.

 

 

If high static is creating high blower speed, check for air whistling through seams in ducts,

 

 

cabinets, or panels.

 

 

If high static is creating high blower speed, check for cabinet/duct deformaton.

 

“Hunts” or “puffs” at high cfm

If removing panel or filter reduces “puffing,” reduce restriction or reduce maximum airflow.

 

(speed)

 

Evidence of moisture

Motor failure or malfunction has

Replace motor and perform moisture check. See Moisture Check section in Troubleshooting.

 

occurred and moisture is present

 

 

Evidence of moisture present

Perform moisture check. See Moisture Check section in Troubleshooting.

 

inside air mover

 

48

Image 48
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Typical Installation 50PTH Unit Aux Electric Heat Disconnect50PTV Dimensional Data 50PTD Dimensional Data Side Discharge Back DischargeInstall Condensate Drain Mount the UnitRotate Move to SideHorizontal Unit Pitch Trap Condensate DrainTypical Ground-Water Piping Installation Drains field-installedWire Field Power Supply Water Quality GuidelinesMetal Hose Minimum Bend Radii 50PTH,PTV,PTD Electrical Data Alarm Relay Contacts Sensor, Water Coil Freeze ProtectionRVS TransECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 A50 8364LWT SPTA50-8571 Wshp Open ControlRnet Wiring Specifications Field-Supplied Sensors for Wshp Open ControllerSPT Sensors Wire Field Controls Rnet WiringWire Terminal A50-8443A50-8141 A50-7764tfA50-8441 A50-8442Cooling Settings Dehumidificaton Mode SettingsHeating Settings CFM Adjust SettingsBlower Performance Data PRE-START-UP Wshp Open Fan Only / Low Fan and Med Fan AirflowWshp Open High Fan Airflow Complete C Control Jumper Settings Deluxe D Control Jumper SettingsField Selectable Inputs DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings Units with Modulating Hot Water Reheat HWR OptionMode Input Output HWR Operating ModesSTART-UP Operating LimitsA50-8145 Water Out Operating Limits 50PTH, PTV, PTD UnitsUnit Start-Up Cooling Mode Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger Suction Discharge Super Sub Water Air Temp Unit Start-Up with Wshp Open Controls A50-8444Unit 50PTH, PTV Water Temperature F GPM Coaxial Water Pressure DropPTD 026 038 049Approximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Page Complete C Control LED Code Fault Descriptions LED Status Description of Operation Alarm RelayLED Fault Description Code Complete C and Deluxe D Board System TestAlarm Relay Aquazone Deluxe D Control LED IndicaService Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s Bat90.0 80.070.0 KOhm 60.0 50.0Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Wshp Troubleshooting Fault Heating Cooling Possible Cause SolutionGood Practices Code 7 Auto Resetting No Fault Code ShownOver/Under Voltage Performance MonitorTemperature in Heating High Head PressureLow Suction Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Alarm StatusStatus SensorAppendix a Wshp Open Screen Configuration MaintenanceSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Page Copyright 2010 Carrier Corporation 50PTH,PTV,PTD START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8449 A50-8450