Carrier PTV, 50PTH Heating Cycle Analysis, Cooling Cycle Analysis, A50-8449, A50-8450

Page 64

HEATING CYCLE ANALYSIS

PSI

SAT

- - - - - - - - - - - - - -

°F

AIR

COIL

°F

EXPANSION

VALVE

COAX

°F

SUCTION

COMPRESSOR

DISCHARGE

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - -

 

°

F

 

 

 

 

 

 

 

a50-8449

 

 

 

 

 

 

 

 

 

LIQUID LINE

 

°F

 

 

°F

 

 

 

 

 

PSI

 

 

 

PSI

 

 

 

 

 

 

 

 

 

FLUID IN

 

FLUID OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOOK UP PRESSURE DROP IN TABLES 20-23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO DETERMINE FLOW RATE

COOLING CYCLE ANALYSIS

PSISAT

- - - - - - - - - - - - - - - - - - - - - - - - - - ALONG DOTTED LINE

°F

AIR

COIL

°F

EXPANSION

VALVE

COAX

°F

SUCTION

COMPRESSOR

DISCHARGE

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - LINECUT

 

 

 

 

 

°

F

 

 

 

 

 

 

 

 

 

a50-8450

 

 

 

LIQUID LINE

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

PSI

 

 

 

PSI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLUID IN

 

FLUID OUT

LOOK UP PRESSURE DROP IN TABLES 20-23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO DETERMINE FLOW RATE

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

 

FLOW RATE (GPM) x

TEMP. DIFF. (DEG. F) x

 

FLUID FACTOR* =

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Btu/hr)

SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE

=

 

(DEG F)

 

 

 

 

 

 

 

 

 

 

 

SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE

=(DEG F)

*Use 500 for water, 485 for antifreeze.

Copyright 2010 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53500079-01

Printed in U.S.A.

Form 50PT-4SI

Pg CL-2

7-10

Replaces: 50PT-3SI

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED

Image 64
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Typical Installation 50PTH Unit Aux Electric Heat Disconnect50PTV Dimensional Data 50PTD Dimensional Data Side Discharge Back DischargeInstall Condensate Drain Mount the UnitRotate Move to SideHorizontal Unit Pitch Trap Condensate DrainTypical Ground-Water Piping Installation Drains field-installedWater Quality Guidelines Wire Field Power SupplyMetal Hose Minimum Bend Radii 50PTH,PTV,PTD Electrical Data Alarm Relay Contacts Sensor, Water Coil Freeze ProtectionRVS TransECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 A50 8364LWT SPTA50-8571 Wshp Open ControlField-Supplied Sensors for Wshp Open Controller Rnet Wiring SpecificationsSPT Sensors Wire Field Controls Rnet WiringWire Terminal A50-8443A50-8141 A50-7764tfA50-8441 A50-8442Cooling Settings Dehumidificaton Mode SettingsHeating Settings CFM Adjust SettingsBlower Performance Data Wshp Open Fan Only / Low Fan and Med Fan Airflow PRE-START-UPWshp Open High Fan Airflow Deluxe D Control Jumper Settings Complete C Control Jumper SettingsField Selectable Inputs DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings Units with Modulating Hot Water Reheat HWR OptionMode Input Output HWR Operating ModesSTART-UP Operating LimitsA50-8145 Water Out Operating Limits 50PTH, PTV, PTD UnitsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Suction Discharge Super Sub Water Air Temp Unit Start-Up with Wshp Open Controls A50-8444Unit 50PTH, PTV Water Temperature F GPM Coaxial Water Pressure DropPTD 026 038 049Approximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Page Complete C Control LED Code Fault Descriptions LED Status Description of Operation Alarm RelayLED Fault Description Code Complete C and Deluxe D Board System TestAlarm Relay Aquazone Deluxe D Control LED IndicaService Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s Bat90.0 80.070.0 KOhm 60.0 50.0Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Fault Heating Cooling Possible Cause Solution Wshp TroubleshootingGood Practices Code 7 Auto Resetting No Fault Code ShownOver/Under Voltage Performance MonitorTemperature in Heating High Head PressureLow Suction Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Alarm StatusStatus SensorAppendix a Wshp Open Screen Configuration MaintenanceSystem Settings ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm Page Page Copyright 2010 Carrier Corporation 50PTH,PTV,PTD START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8449 A50-8450