Carrier PTV Screen Name, Configuration Service, Point Name Password Editable Range Default Level

Page 58

APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

SCREEN NAME

Configuration

Service

Configuration

POINT NAME

PASSWORD

EDITABLE

RANGE

DEFAULT

NOTES

LEVEL

 

 

 

 

 

# of Fan Speeds

 

X

1,2,3

3

Used to set number of

 

fan motor speeds

 

 

 

 

 

 

 

 

 

 

When set to Fan On, G output is

 

 

 

 

 

energized when ever any fan speed

G Output Type

 

X

Fan On/Fan Low

Fan On

is active (required for ECM and Fan

 

control board). When set to Fan

 

 

 

 

 

 

 

 

 

 

Low, output is only energized for

 

 

 

 

 

Low Speed

Compressor Stages

 

X

One Stage/Two Stages

One Stage

Defines the number of

 

stages of compression

 

 

 

 

 

Reversing Valve Type

 

X

O type output/B type output

O type

Determines reversing valve

 

signal output type

 

 

 

 

 

Leaving Air Auxiliary

 

X

None/2-Position HW/1 Stage

None

Determines Auxiliary

Heat Type

 

Electric/Modulating HW

Reheat Coil Type

 

 

 

Entering Air Water

 

X

None/2-Position/Modulating

None

Determines Entering Air

Economizer Type

 

Economizer Coil Type

 

 

 

 

2-Position Water

 

X

Normally Closed/Normally Open

Normally

Determines type of 2-position

Valve Type

 

Closed

water valve used

 

 

 

Modulating Water

 

X

Normally Closed/Normally Open

Normally

Determines type of modulating

Valve Type

 

Closed

water valve used

 

 

 

Ventilation Damper

 

X

None/2-Position/DCV

None

Determines type of ventilation

Type

 

damper control to be used

 

 

 

 

 

 

 

 

 

Used to determine ventilation

Damper Actuator Type

 

X

(0-10 volt)/(2-10 volt)

0-10 volt

damper output signal range

 

 

 

 

 

(closed - open)

Humidity Sensor

 

X

None/Installed

None

Set to Installed if humidity

 

sensor is present

 

 

 

 

 

Factory Dehumidifica-

Admin Password

X

None/Installed

None

Set to Installed if factory-installed

tion Reheat Coil

level access only

dehumidification reheat coil

 

 

 

 

is present

 

 

 

 

 

Occupancy

 

X

Occupied Open/Occupied Closed

Occupied

Used to determine external occu-

Input Logic

 

CLOSED

pancy switch contact occupied state

 

 

 

Condensate Switch

 

X

5 - 600 seconds

10 sec

Delay before equipment alarms on

Alarm Delay

 

high condensate level

 

 

 

 

Condensate Switch

 

X

Alarm OPEN/Alarm CLOSED

Alarm

Determine Alarm state of

Alarm State

 

CLOSED

condensate switch input

 

 

 

Minimum Condenser

 

 

25 - 60 ° F

60 ° F

Determines the minimum

Water Temperature in

 

X

acceptable water loop temperature

Heating

 

 

 

 

to start heating

Maximum Condenser

 

 

65 - 100 ° F

90 ° F

Determines the maximum

Water Temperature in

 

X

acceptable water loop temperature

Heating

 

 

 

 

to start heating

Minimum Condenser

 

 

30 - 60 ° F

60 ° F

Determines the minimum

Water Temperature in

 

X

acceptable water loop temperature

Cooling

 

 

 

 

to start cooling

Maximum Condenser

 

 

85 - 120 ° F

95 ° F

Determines the maximum

Water Temperature in

 

X

acceptable water loop temperature

Cooling

 

 

 

 

to start cooling

IAQ sensor

 

X

0 - 5 ma

4 ma

Minimum output current (mA)

minimum input

 

for IAQ sensor

 

 

 

 

IAQ sensor

 

X

5 - 20 ma

20 ma

Maximum output current (mA) for

maximum input

 

IAQ sensor

 

 

 

 

IAQ sensor

 

X

0 - 9999 ppm

0 ppm

Corresponding value in ppm for

minimum output

 

minimum output current

 

 

 

 

IAQ sensor

 

X

0 - 9999 ppm

2000 ppm

Corresponding value in ppm for

maximum output

 

maximum output current

 

 

 

 

 

LEGEND

BAS

Building Automation System

DCV

Demand Controlled Ventilation

IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration

58

Image 58
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Typical Installation 50PTH Unit Aux Electric Heat Disconnect50PTV Dimensional Data 50PTD Dimensional Data Side Discharge Back DischargeRotate Install Condensate DrainMount the Unit Move to SideHorizontal Unit Pitch Trap Condensate DrainTypical Ground-Water Piping Installation Drains field-installedWater Quality Guidelines Wire Field Power SupplyMetal Hose Minimum Bend Radii 50PTH,PTV,PTD Electrical Data Alarm Relay Contacts Sensor, Water Coil Freeze ProtectionRVS TransECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 A50 8364LWT SPTA50-8571 Wshp Open ControlField-Supplied Sensors for Wshp Open Controller Rnet Wiring SpecificationsSPT Sensors Wire Terminal Wire Field ControlsRnet Wiring A50-8443A50-8441 A50-8141A50-7764tf A50-8442Heating Settings Cooling SettingsDehumidificaton Mode Settings CFM Adjust SettingsBlower Performance Data Wshp Open Fan Only / Low Fan and Med Fan Airflow PRE-START-UPWshp Open High Fan Airflow Deluxe D Control Jumper Settings Complete C Control Jumper SettingsField Selectable Inputs Humidistat/Dehumidistat Logic Deluxe D DIP Switch Settings DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Units with Modulating Hot Water Reheat HWR OptionMode Input Output HWR Operating ModesA50-8145 Water Out START-UPOperating Limits Operating Limits 50PTH, PTV, PTD UnitsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Suction Discharge Super Sub Water Air Temp Unit Start-Up with Wshp Open Controls A50-8444PTD Unit 50PTH, PTV Water Temperature F GPMCoaxial Water Pressure Drop 026 038 049Operation Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Page LED Fault Description Code Complete C Control LED Code Fault DescriptionsLED Status Description of Operation Alarm Relay Complete C and Deluxe D Board System TestAlarm Relay Aquazone Deluxe D Control LED IndicaService Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Replacing the Wshp Open Controller’s Bat70.0 90.080.0 KOhm 60.0 50.0Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Fault Heating Cooling Possible Cause Solution Wshp TroubleshootingGood Practices Over/Under Voltage Code 7 Auto ResettingNo Fault Code Shown Performance MonitorLow Suction Pressure Temperature in HeatingHigh Head Pressure Low Discharge AirStatus Appendix a Wshp Open Screen ConfigurationAlarm Status SensorSystem Settings Appendix a Wshp Open Screen ConfigurationMaintenance ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm Page Page Copyright 2010 Carrier Corporation 50PTH,PTV,PTD START-UP Checklist II. START-UPA50-8449 Heating Cycle AnalysisCooling Cycle Analysis A50-8450