Table 14A — WSHP Open — Fan Only / Low Fan and Med Fan Airflow
50PT UNIT | MAX | FAN MOTOR | TAP SETTING | SW 3 | SW 4 | FAN ONLY | COOLING AND | COOLING AND | |
SIZE | ESP | HP | (SW 1) | (SW 2) | HEATING LOW FAN | HEATING MED FAN | |||
|
| ||||||||
|
|
| 4 | OFF | OFF | 475 | 920 | 1050 | |
|
|
|
|
|
|
|
|
| |
26 | 0.5 | 0.5 | 3 | OFF | ON | 425 | 825 | 950 | |
|
|
|
|
|
| ||||
2 | ON | OFF | 370 | 710 | 820 | ||||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
|
|
| 1 | ON | ON | 300 | 600 | 690 | |
|
|
|
|
|
|
|
|
| |
|
|
| 4 | OFF | OFF | 700 | 1120 | 1400 | |
|
|
|
|
|
|
|
|
| |
38 | 0.5 | 0.5 | 3 | OFF | ON | 630 | 1000 | 1250 | |
|
|
|
|
|
| ||||
2 | ON | OFF | 540 | 860 | 1080 | ||||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
|
|
| 1 | ON | ON | 450 | 730 | 900 | |
|
|
|
|
|
|
|
|
| |
|
|
| 4 | OFF | OFF | 870 | 1560 | 1850 | |
|
|
|
|
|
|
|
|
| |
49 | 0.75 | 1 | 3 | OFF | ON | 780 | 1400 | 1650 | |
|
|
|
|
|
| ||||
2 | ON | OFF | 670 | 1200 | 1430 | ||||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
|
|
| 1 | ON | ON | 560 | 1010 | 1200 | |
|
|
|
|
|
|
|
|
| |
|
|
| 4 | OFF | OFF | 1020 | 1860 | 2280 | |
|
|
|
|
|
|
|
|
| |
64 | 0.75 | 1 | 3 | OFF | ON | 920 | 1650 | 2040 | |
|
|
|
|
|
| ||||
2 | ON | OFF | 780 | 1430 | 1750 | ||||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
|
|
| 1 | ON | ON | 660 | 1200 | 1470 | |
|
|
|
|
|
|
|
|
| |
|
|
| 4 | OFF | OFF | 1050 | 1600 | 2230 | |
|
|
|
|
|
|
|
|
| |
72 | 0.75 | 1 | 3 | OFF | ON | 980 | 1600 | 2100 | |
|
|
|
|
|
| ||||
2 | ON | OFF | 910 | 1400 | 1850 | ||||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
|
|
| 1 | ON | ON | 850 | 1240 | 1620 | |
|
|
|
|
|
|
|
|
|
NOTE: Factory default setting shown bold.
IMPORTANT: The tap setting for high fan MUST equal or exceed the tap setting for fan only/low/med fan
Table 14B — WSHP Open — High Fan Airflow
50PT UNIT SIZE | MAX ESP | FAN MOTOR HP TAP SETTING | SW 5 | SW 6 | COOLING AND HEATING HIGH FAN | |
|
| 4 | OFF | OFF | 1060 | |
|
|
|
|
|
|
|
26 |
| 3 | OFF | ON | 950 | |
0.5 | 0.5 |
|
|
|
| |
| ON | OFF | 820 | |||
|
|
| 2 | |||
|
| 1 | ON | ON | 690 |
|
|
| 4 | OFF | OFF | 1400 |
38 |
| 3 | OFF | ON | 1350 | |
0.5 | 0.5 |
|
|
|
| |
| ON | OFF | 1350 | |||
|
|
| 2 | |||
|
| 1 | ON | ON | 1350 |
|
|
| 4 | OFF | OFF | 1850 |
49 |
| 3 | OFF | ON | 1660 | |
0.75 | 1 |
|
|
|
| |
| ON | OFF | 1430 | |||
|
|
| 2 | |||
|
| 1 | ON | ON | 1350 |
|
|
| 4 | OFF | OFF | 2280 |
64 |
| 3 | OFF | ON | 2050 | |
0.75 | 1 |
|
|
|
| |
| ON | OFF | 1750 | |||
|
|
| 2 | |||
|
| 1 | ON | ON | 1470 |
|
|
| 4 | OFF | OFF | 2230 |
72 |
| 3 | OFF | ON | 2100 | |
0.75 | 1 |
|
|
|
| |
| ON | OFF | 1870 | |||
|
|
| 2 | |||
|
| 1 | ON | ON | 1670 |
NOTE: Factory default setting shown bold.
IMPORTANT: The tap setting for high fan MUST equal or exceed the tap setting for fan only/low/med fan
PRE-START-UP
System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:
1.Voltage is within the utilization range specifications of the unit compressor and fan motor and voltage is balanced for
2.Fuses, breakers and wire are correct size.
3.Low voltage wiring is complete.
4.Piping and system flushing is complete.
5.Air is purged from closed loop system.
6.System is balanced as required. Monitor if necessary.
7.Isolation valves are open.
8.Water control valves or loop pumps are wired.
9.Condensate line is open and correctly pitched.
10.Transformer switched to lower voltage tap if necessary.
11.Blower rotates freely — shipping support is removed.
12.Blower speed is on correct setting.
13.Air filter is clean and in position.
14.Service/access panels are in place.