Carrier 50PTH, PTV specifications Pre-Start-Up, Wshp Open Fan Only / Low Fan and Med Fan Airflow

Page 29

Table 14A — WSHP Open — Fan Only / Low Fan and Med Fan Airflow

50PT UNIT

MAX

FAN MOTOR

TAP SETTING

SW 3

SW 4

FAN ONLY

COOLING AND

COOLING AND

SIZE

ESP

HP

(SW 1)

(SW 2)

HEATING LOW FAN

HEATING MED FAN

 

 

 

 

 

4

OFF

OFF

475

920

1050

 

 

 

 

 

 

 

 

 

26

0.5

0.5

3

OFF

ON

425

825

950

 

 

 

 

 

 

2

ON

OFF

370

710

820

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

300

600

690

 

 

 

 

 

 

 

 

 

 

 

 

4

OFF

OFF

700

1120

1400

 

 

 

 

 

 

 

 

 

38

0.5

0.5

3

OFF

ON

630

1000

1250

 

 

 

 

 

 

2

ON

OFF

540

860

1080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

450

730

900

 

 

 

 

 

 

 

 

 

 

 

 

4

OFF

OFF

870

1560

1850

 

 

 

 

 

 

 

 

 

49

0.75

1

3

OFF

ON

780

1400

1650

 

 

 

 

 

 

2

ON

OFF

670

1200

1430

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

560

1010

1200

 

 

 

 

 

 

 

 

 

 

 

 

4

OFF

OFF

1020

1860

2280

 

 

 

 

 

 

 

 

 

64

0.75

1

3

OFF

ON

920

1650

2040

 

 

 

 

 

 

2

ON

OFF

780

1430

1750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

660

1200

1470

 

 

 

 

 

 

 

 

 

 

 

 

4

OFF

OFF

1050

1600

2230

 

 

 

 

 

 

 

 

 

72

0.75

1

3

OFF

ON

980

1600

2100

 

 

 

 

 

 

2

ON

OFF

910

1400

1850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

850

1240

1620

 

 

 

 

 

 

 

 

 

NOTE: Factory default setting shown bold.

IMPORTANT: The tap setting for high fan MUST equal or exceed the tap setting for fan only/low/med fan

Table 14B — WSHP Open — High Fan Airflow

50PT UNIT SIZE

MAX ESP

FAN MOTOR HP TAP SETTING

SW 5

SW 6

COOLING AND HEATING HIGH FAN

 

 

4

OFF

OFF

1060

 

 

 

 

 

 

 

26

 

3

OFF

ON

950

0.5

0.5

 

 

 

 

 

ON

OFF

820

 

 

 

2

 

 

1

ON

ON

690

 

 

 

4

OFF

OFF

1400

38

 

3

OFF

ON

1350

0.5

0.5

 

 

 

 

 

ON

OFF

1350

 

 

 

2

 

 

1

ON

ON

1350

 

 

 

4

OFF

OFF

1850

49

 

3

OFF

ON

1660

0.75

1

 

 

 

 

 

ON

OFF

1430

 

 

 

2

 

 

1

ON

ON

1350

 

 

 

4

OFF

OFF

2280

64

 

3

OFF

ON

2050

0.75

1

 

 

 

 

 

ON

OFF

1750

 

 

 

2

 

 

1

ON

ON

1470

 

 

 

4

OFF

OFF

2230

72

 

3

OFF

ON

2100

0.75

1

 

 

 

 

 

ON

OFF

1870

 

 

 

2

 

 

1

ON

ON

1670

NOTE: Factory default setting shown bold.

IMPORTANT: The tap setting for high fan MUST equal or exceed the tap setting for fan only/low/med fan

PRE-START-UP

System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:

1.Voltage is within the utilization range specifications of the unit compressor and fan motor and voltage is balanced for 3-phase units.

2.Fuses, breakers and wire are correct size.

3.Low voltage wiring is complete.

4.Piping and system flushing is complete.

5.Air is purged from closed loop system.

6.System is balanced as required. Monitor if necessary.

7.Isolation valves are open.

8.Water control valves or loop pumps are wired.

9.Condensate line is open and correctly pitched.

10.Transformer switched to lower voltage tap if necessary.

11.Blower rotates freely — shipping support is removed.

12.Blower speed is on correct setting.

13.Air filter is clean and in position.

14.Service/access panels are in place.

15.Return-air temperature is between 40 to 80 F heating and 50 to 110 F cooling.

29

Image 29
Contents Safety Considerations ContentsGeneral InstallationPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Aux Electric Heat Disconnect Typical Installation 50PTH Unit50PTV Dimensional Data 50PTD Dimensional Data Back Discharge Side DischargeMount the Unit Install Condensate DrainRotate Move to SideTrap Condensate Drain Horizontal Unit PitchDrains field-installed Typical Ground-Water Piping InstallationMetal Hose Minimum Bend Radii Wire Field Power SupplyWater Quality Guidelines 50PTH,PTV,PTD Electrical Data Sensor, Water Coil Freeze Protection Alarm Relay ContactsTrans RVSECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 8364 A50SPT LWTWshp Open Control A50-8571SPT Sensors Rnet Wiring SpecificationsField-Supplied Sensors for Wshp Open Controller Rnet Wiring Wire Field ControlsWire Terminal A50-8443A50-7764tf A50-8141A50-8441 A50-8442Dehumidificaton Mode Settings Cooling SettingsHeating Settings CFM Adjust SettingsBlower Performance Data Wshp Open High Fan Airflow PRE-START-UPWshp Open Fan Only / Low Fan and Med Fan Airflow Field Selectable Inputs Complete C Control Jumper SettingsDeluxe D Control Jumper Settings DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings Units with Modulating Hot Water Reheat HWR OptionHWR Operating Modes Mode Input OutputOperating Limits START-UPA50-8145 Water Out Operating Limits 50PTH, PTV, PTD UnitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Suction Discharge Super Sub Water Air Temp A50-8444 Unit Start-Up with Wshp Open ControlsCoaxial Water Pressure Drop Unit 50PTH, PTV Water Temperature F GPMPTD 026 038 049Antifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Page LED Status Description of Operation Alarm Relay Complete C Control LED Code Fault DescriptionsLED Fault Description Code Complete C and Deluxe D Board System TestAquazone Deluxe D Control LED Indica Alarm RelayService Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s Bat80.0 90.070.0 KOhm 60.0 50.0Page Fault Description Solution ECM TroubleshootingA50-8448 ECM Pin ConnectorsA50-8447 ECM Troubleshooting Flow DiagramGood Practices Wshp TroubleshootingFault Heating Cooling Possible Cause Solution No Fault Code Shown Code 7 Auto ResettingOver/Under Voltage Performance MonitorHigh Head Pressure Temperature in HeatingLow Suction Pressure Low Discharge AirAlarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Test Appendix a Wshp Screen Open ConfigurationService Screen Name Configuration ServicePoint Name Password Editable Range Default Level Alarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50PTH,PTV,PTD START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8449 A50-8450