APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME | POINT NAME |
| PASSWORD | EDITABLE | RANGE | DEFAULT | NOTES | |
| LEVEL | |||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Defines the hysteresis applied above |
|
| SPT Occupied Alarm |
|
| X | 2 - 20 ° F | 5 ° F | the cooling and below the heating set |
|
| Hysteresis |
|
| points before an alarm condition will | |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| occur |
|
|
|
|
|
|
|
| Used to calculate the delay time before |
|
| SPT Alarm Delay |
|
| X | 0 - 30 min per degree | 10 min | an alarm is generated after the alarm |
|
|
|
|
|
|
|
| condition occurs |
|
| SPT Unoccupied Low |
|
| X | 35 - 90 ° F | 45 ° F | Defines the fixed unoccupied |
|
| Alarm Temperature |
|
| ow SPT alarm limit | |||
|
|
|
|
|
|
| ||
|
| SPT Unoccupied High |
|
| X | 45 - 100 ° F | 95 ° F | Defines the fixed unoccupied |
|
| Alarm Temperature |
|
| high SPT alarm limit | |||
|
|
|
|
|
|
| ||
|
| SAT Low SAT |
|
| X | 15 - 90 ° F | 45 ° F | Defines the fixed minimum |
|
| Alarm Limit |
|
| SAT alarm limit | |||
|
|
|
|
|
|
| ||
|
| SAT High SAT |
|
| X | 90 - 175 ° F | 120 ° F | Defines the fixed maximum |
|
| Alarm Limit |
|
| SAT alarm limit | |||
|
|
|
|
|
|
| ||
|
| Condensate Overflow |
|
|
|
|
| Defines the delay time before an alarm |
|
|
|
| X | 5 - 600 sec | 10 sec | is generated after the alarm condition | |
|
| Alarm Delay |
|
| ||||
|
|
|
|
|
|
| occurs | |
|
|
|
|
|
|
|
| |
|
| Space Humidity Occupied |
|
| X | 45% - 100% | 100% | Defines the fixed occupied |
|
| High Alarm Limit |
|
| high space RH alarm limit | |||
|
|
|
|
|
|
| ||
|
| Space Humidity Alarm |
|
|
|
|
| Used to calculate the delay time before |
Configuration |
|
| X | 0 - 30 min per % RH | 5 min | an alarm is generated after the alarm | ||
Delay |
|
| ||||||
|
|
|
|
|
|
| condition occurs | |
|
|
|
|
|
|
|
| |
| → | Space Humidity Unoccu- |
| Admin Password | X | 45% - 100% | 100% | Defines the fixed unnoccupied |
|
| pied High Alarm Limit |
| level access only | high space RH alarm limit | |||
|
|
|
|
|
| |||
| Alarm | IAQ/Ventilation Occupied |
|
| X | 0 - 9999 ppm | 1100 ppm | Defines the fixed occupied high |
Configuration | High Alarm Limit |
|
| space IAQ/Ventilation alarm limit | ||||
|
|
|
|
| ||||
|
| IAQ/Ventilation |
|
|
|
|
| Used to calculate the delay time before |
|
|
|
| X | 0.1 - 1.0 min per ppm | 0.25 min | an alarm is generated after the alarm | |
|
| Alarm Delay |
|
| ||||
|
|
|
|
|
|
| condition occurs | |
|
|
|
|
|
|
|
| |
|
| Rnet Sensor SPT Alarm |
|
| X | Ignore/Display | Ignore | Determines if the SPT alarm is |
|
|
|
| displayed on the local Rnet sensor | ||||
|
|
|
|
|
|
|
| |
|
| Rnet Sensor SAT Alarm |
|
| X | Ignore/Display | Ignore | Determines if the SAT alarm is |
|
|
|
| displayed on the local Rnet sensor | ||||
|
|
|
|
|
|
|
| |
|
| Rnet Sensor Compressor |
|
|
|
|
| Determines if the Compressor Lockout |
|
|
|
| X | Ignore/Display | Display | alarm is displayed on the local Rnet | |
|
| Lockout Alarm |
|
| ||||
|
|
|
|
|
|
| sensor | |
|
|
|
|
|
|
|
| |
|
| Rnet Sensor Condenser |
|
|
|
|
| Determines if the Condenser Water |
|
|
|
| X | Ignore/Display | Display | Temperature alarm is displayed on the | |
|
| Water Temperature Alarm |
|
| ||||
|
|
|
|
|
|
| local Rnet sensor | |
|
|
|
|
|
|
|
| |
|
| Rnet Sensor Condensate |
|
|
|
|
| Determines if the Condensate |
|
|
|
| X | Ignore/Display | Display | Overflow alarm is displayed on the | |
|
| Overflow Alarm |
|
| ||||
|
|
|
|
|
|
| local Rnet sensor | |
|
|
|
|
|
|
|
| |
|
| Rnet Sensor Dirty |
|
| X | Ignore/Display | Display | Determines if the Dirty Filter alarm is |
|
| Filter Alarm |
|
| displayed on the local Rnet sensor | |||
|
|
|
|
|
|
| ||
|
| Rnet Sensor Space |
|
|
|
|
| Determines if the High Space |
|
|
|
| X | Ignore/Display | Ignore | RH alarm is displayed on the | |
|
| High Humidity Alarm |
|
| ||||
|
|
|
|
|
|
| local Rnet sensor | |
|
|
|
|
|
|
|
| |
Configuration | Loop Control Network |
|
|
|
|
| See TPI | |
Number |
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
| → | Loop Control Network |
|
|
|
|
| See TPI |
| Address |
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
Linkage | Number of Linked Heat |
|
|
|
|
| See TPI | |
Pumps |
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
| LEGEND |
|
|
|
|
| ||
BAS — Building Automation System |
|
|
|
|
| |||
DCV | — Demand Controlled Ventilation |
|
|
|
|
| ||
IAQ | — Indoor Air Quality |
|
|
|
|
| ||
OAT | — Outdoor Air Temperature |
|
|
|
|
| ||
RH | — Relative Humidity |
|
|
|
|
| ||
SAT — Supply Air Temperature |
|
|
|
|
| |||
SPT | — Space Temperature |
|
|
|
|
| ||
TPI | — Third Party Integration |
|
|
|
|
|
59