APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
SCREEN NAME | POINT NAME | PASSWORD | EDITABLE | RANGE | DEFAULT | NOTES | ||
LEVEL | ||||||||
|
|
|
|
|
|
| ||
|
|
|
|
| Off, Fan Only, Economize, |
|
| |
|
| Operating Mode |
|
| Cooling, Heating, Cont Fan, |
| Displays unit operating mode | |
|
|
|
|
| Test, Start Delay, Dehumidify |
|
| |
|
| SPT |
|
| ° F |
| Displays SPT | |
|
| SAT |
|
| ° F |
| Displays SAT | |
|
| Condenser Leaving |
|
| ° F |
| Displays leaving condenser | |
|
| Temperature |
|
|
| water temperature | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
| Displays entering condenser | |
|
| Condenser Entering |
|
| ° F |
| water temperature (Value | |
|
| Temperature |
|
|
| will not update when compressor | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
| is operating) | |
|
|
|
|
| Off/Low Speed/ |
|
| |
|
| Fan |
|
| Medium Speed |
| Displays fan speed status | |
| Equipment |
| No Password |
| High Speed/On |
|
| |
| Compressor Capacity |
| 0 - 100% |
| Displays compressor capacity | |||
| Status | Required |
|
| ||||
|
|
|
|
| Displays current damper position | |||
|
|
|
|
|
|
| ||
|
| Damper Position |
|
| 0 - 100% |
| (Viewable only if Ventilation DMP | |
|
|
|
|
|
|
| Type = 2 position or DCV) | |
|
| H2O Economizer |
|
| 0 - 100% |
| Displays position of economizer valve | |
|
|
|
|
|
|
| Displays position of auxiliary | |
|
| Auxiliary Heat |
|
| 0 - 100% |
| reheat valve (Viewable only if Leaving | |
|
|
|
|
| Air Auxiliary Heat Type = 2 position, | |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 1 stage Elect or Modulating) | |
|
| Space RH |
|
| 0 - 100% |
| Displays space RH% (Viewable only if | |
|
|
|
|
| Humidity Sensor = Installed) | |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Displays if dehumidification is active | |
|
| Dehumidification |
|
| Inactive/Active |
| (Viewable only if Factory | |
|
|
|
|
|
|
| Dehumidification Reheat = Installed) | |
|
| IAQ CO2 |
|
| 0 - 9999 ppm |
| Displays the space CO2 level | |
|
| SPT Alarm Status |
|
| Normal/Alarm |
| Displays current space | |
|
|
|
|
| temperature condition | |||
|
|
|
|
|
|
| ||
|
|
|
|
| ° F |
| Displays the SPT that | |
|
| Alarming SPT |
|
|
| exceeded the alarm limit (when SPT | ||
|
|
|
|
|
|
| alarm above is in Alarm) | |
|
|
|
|
| ° F |
| Displays the SPT alarm limit that was | |
|
| SPT Alarm Limit |
|
|
| exceeded; causing the alarm condition | ||
|
|
|
|
|
|
| (when SPT alarm above is in Alarm) | |
|
|
|
|
|
|
| Displays the status of the Rnet | |
|
| SPT Sensor Alarm |
|
| Normal/Alarm |
| SPT sensor - ALARM is displayed | |
|
| Status |
|
|
| should the sensor fail to communicate | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
| with the control module | |
|
| IAQ Alarm Status |
|
| Normal/Alarm |
| Current IAQ/ventilation condition | |
Alarm Status | Compressor Alarm | No Password |
| Normal/Alarm |
| Current compressor condition | ||
Status | Required |
|
| |||||
|
|
|
|
|
| |||
|
| SAT Alarm Status |
|
| Normal/Alarm |
| Current SAT condition | |
|
| Condensate Overflow |
|
| Normal/Alarm |
| Current status of the condensate | |
|
| Alarm Status |
|
|
| drain (overflow switch) | ||
|
|
|
|
|
| |||
|
| Condenser Water Tem- |
|
| Normal/Alarm |
| Current status of the | |
|
| perature Alarm Status |
|
|
| condenser water | ||
|
|
|
|
|
| |||
|
| Filter Alarm Status |
|
| Normal/Alarm |
| Current filter condition | |
|
| Space RH Alarm Status |
|
| Normal/Alarm |
| Current space RH condition | |
|
| OAT Alarm Status |
|
| Normal/Alarm |
| Current status of the OAT | |
|
|
|
|
| broadcast function | |||
|
|
|
|
|
|
| ||
|
| Airside Linkage Status |
|
| Normal/Alarm |
| Current linkage status if enabled | |
|
| Condenser Water |
|
| Normal/Alarm |
| Current linkage status if enabled | |
|
| Linkage |
|
|
| |||
|
|
|
|
|
|
| ||
|
| SAT |
|
| ° F |
| Display SAT | |
|
| SAT Offset |
| X | 0 ° F | Used to correct sensor reading | ||
|
| Leaving Condenser |
|
| ° F |
| Displays Leaving Condenser | |
|
| Water Temperature |
|
|
| Water Temperature | ||
|
|
|
|
|
| |||
| Sensor | Leaving CW Offset | Admin Password | X | 0 ° F | Used to correct sensor reading | ||
Calibration | Rnet Sensor | level access only |
| ° F |
| Displays SPT | ||
|
| Temperature |
|
|
| |||
|
|
|
|
|
|
| ||
|
| Rnet Offset |
| X | 0 ° F | Used to correct sensor reading | ||
|
| RH |
|
| % |
| Displays Space RH value | |
|
| RH Sensor Offset |
| X | 0 % | Used to correct sensor reading | ||
| LEGEND |
|
|
|
|
| ||
BAS — Building Automation System |
|
|
|
|
| |||
DCV | — Demand Controlled Ventilation |
|
|
|
|
| ||
IAQ | — Indoor Air Quality |
|
|
|
|
| ||
OAT | — Outdoor Air Temperature |
|
|
|
|
| ||
RH | — Relative Humidity |
|
|
|
|
| ||
SAT — Supply Air Temperature |
|
|
|
|
| |||
SPT | — Space Temperature |
|
|
|
|
| ||
TPI | — Third Party Integration |
|
|
|
|
|