FILL CONDENSER WITH CLEANING SOLUTION. DO NOT ADD SOLUTION MORE RAPIDLY THAN VENT CAN EXHAUST GASES CAUSED BY CHEMICAL ACTION.
VENT
PIPE
3’ TO 4’
PAIL
FUNNEL
1”
PIPE
5’ APPROX
CONDENSER
Refrigerant Charging
WARNING
To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system — this can cause compressor flooding.
NOTE: Do not vent or depressurize unit refrigerant to atmo- sphere. Remove and recover refrigerant following accepted practices.
Air Coil Fan Motor Removal
CAUTION
Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent coil damage.
PAIL
Fig. 35 — Gravity Flow Method
Disconnect motor power wires from motor terminals before motor is removed from unit.
1. | Shut off unit main power supply. |
2. | Loosen bolts on mounting bracket so that fan belt can be |
PUMP PRIMING CONN.
SUCTION
PUMP
SUPPORT
TANK
FINE MESH
SCREEN
GAS VENT
GLOBE
VALVES
SUPPLY
1” PIPE
CONDENSER
REMOVE WATER
REGULATING VALVE
RETURN
removed. |
3. Loosen and remove the 2 motor mounting bracket bolts |
on left side of bracket. |
Slide motor/bracket assembly to extreme right and lift out through space between fan scroll and side frame. Rest motor on a high platform such as a step ladder. Do not allow motor to hang by its power wires.
Replacing the WSHP Open Controller’s Bat-
tery — The WSHP Open controller’s
NOTE: Power must be ON to the WSHP Open controller when replacing the battery, or the date, time and trend data will be lost.
Fig. 36 — Forced Circulation Method
Checking System Charge — Units are shipped with full operating charge. If recharging is necessary:
1.Insert thermometer bulb in insulating rubber sleeve on liquid line near filter drier. Use a digital thermometer for all temperature measurements. DO NOT use a mercury or
2.Connect pressure gage to discharge line near compressor.
3.After unit conditions have stabilized, read head pressure on discharge line gage.
NOTE: Operate unit a minimum of 15 minutes before checking charge.
4.From standard
5.Read liquid line temperature on thermometer; then subtract from saturated condensing temperature. The dif- ference equals subcooling temperature.
6.Compare the subcooling temperature with the normal temperature listed in Tables
1.Remove the battery from the controller, making note of the battery's polarity.
2.Insert the new battery, matching the battery's polarity with the polarity indicated on the WSHP Open controller.
TROUBLESHOOTING
When troubleshooting problems with a WSHP, consider the following:
Thermistor — A thermistor may be required for single- phase units where starting the unit is a problem due to low voltage. See Fig. 37 for thermistor nominal resistance.
Control Sensors — The control system employs 2 nom- inal 10,000 ohm thermistors (FP1 and FP2) that are used for freeze protection. Be sure FP1 is located in the discharge fluid and FP2 is located in the air discharge. See Fig. 38.
45