Carrier PTV, 50PTH specifications Side Discharge, Back Discharge

Page 8

Supply Air

 

 

 

Building

 

Flexible

Loop

 

 

 

Connection

 

 

 

Water

 

 

Out

 

 

Water

 

 

In

Balancing Valve

Stainless steel

(field-installed

braid hose

accessory)

with integral

 

“J” swivel

 

(field-installed

Low Pressure

accessory)

Drop Water

Power

 

 

Control Valve

Thermostat

 

(optional)

 

(field-installed

Wiring

 

accessory)

 

Ball Valve with optional

Compressor

integral P/T plug

(typical for supply and

Access Panel

return piping) (field-Installed

 

 

accessory)

NOTE: Ball valve with integral pressure temperature plug recommended.

Fig. 5 — Typical Vertical Installation — 50PTV Unit

Provide adequate clearance for filter replacement and drain pan cleaning. Do not block filter access with pip- ing, conduit or other materials. Refer to Fig. 1, 3, and 4 for dimensional data.

Provide access for fan and fan motor maintenance and for servicing the compressor and coils without removing the unit.

Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of the unit, if necessary.

In limited side access installations, pre-removal of the control box side mounting screws will allow control box removal for future servicing.

Provide access to water valves and fittings and screw- driver access to the unit side panels, discharge collar and all electrical connections.

NOTE: Correct placement of the horizontal unit can play an important part in minimizing sound problems. Since duct- work is normally applied to these units, the unit can be placed so that the principal sound emission is outside the oc- cupied space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.

Power

Thermostat

Wiring

Compressor

Access Panel

Flexible

Building

 

Connection

Loop

 

 

Water

Water

 

Out

Stainless

In

steel

 

braid hose

 

with

 

Balancing Valve

integral ”J”

(field-installed

swivel(field-

accessory)

installed

Low Pressure

accessory)

Drop Water

 

 

Control Valve

 

 

(optional)

 

 

(field-installed

 

 

accessory)

 

 

Ball Valve with

Flexible

optional integral

P/T plug (typical for

Connection

 

 

supply and return

Supply Air

piping)(field-installed

accessory)

 

FIELD CONVERSION OF DISCHARGE AIR — The dis- charge air of the 50PTH horizontal units can be converted between side and back discharge in the field. The conversion process is the same for right and left return configurations. See Fig. 7 and 8.

NOTE: It is not possible to convert return air between left or right return models in the field due to refrigerant piping changes.

Water

Connection End

Return Air

Supply

Duct

Side Discharge

Water

 

Connection End

NOTE: Ball valve with integral pressure temperature plug recommended.

Fig. 6 — Typical Downflow Installation —

50PTD Unit

Return Air

Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for a WSHP:

Units are for indoor use only.

Locate in areas where ambient temperatures are between

 

39 F and 102 F and relative humidity is no greater than

Drain

Discharge Air

Back Discharge

 

75%.

 

 

Provide sufficient space

for water, electrical and duct

 

connections.

 

 

• Locate unit in an area that allows easy access and removal

 

of filter and access panels.

 

Allow enough space

for

service personnel to perform

 

maintenance.

 

 

• Return air must be able to freely enter the space if unit needs

 

to be installed in a confined area such as a closet.

• Install the unit on a piece of rubber, neoprene or other

 

mounting pad material for sound isolation. The pad

 

should be at least 3/

in. [10 mm] to 1/ in. [13 mm] in

 

8

 

2

 

thickness. Extend the pad beyond all four edges of the

 

unit.

 

 

Fig. 7 — Conversion Right Return,

Side Discharge to Back Discharge

Preparation — The unit should be on the ground in a well lit area. Hung units should be taken down to ground level before converting.

Side to Back Discharge Conversion

1.Remove screws to free the top and discharge panels. Set screws aside for later use. See Fig. 8.

2.Remove the access panel and set aside.

3.Lift the discharge panel from side of unit and rotate it to back using care not to damage blower wiring.

4.Check blower wire routing and connections for undue tension or contact with sheet metal edges. Re-route if necessary.

8

Image 8
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50PTH, PTV, PTD026-072 Units 50PTH026-072 Dimensional Data Typical Installation 50PTH Unit Aux Electric Heat Disconnect50PTV Dimensional Data 50PTD Dimensional Data Side Discharge Back DischargeInstall Condensate Drain Mount the UnitRotate Move to SideHorizontal Unit Pitch Trap Condensate DrainTypical Ground-Water Piping Installation Drains field-installedMetal Hose Minimum Bend Radii Wire Field Power SupplyWater Quality Guidelines 50PTH,PTV,PTD Electrical Data Alarm Relay Contacts Sensor, Water Coil Freeze ProtectionRVS TransECM BM ECM Alarm Relay Contacts Discharge Temp Switch Relay/Contactor Coil A50-8363 A50 8364LWT SPTA50-8571 Wshp Open ControlSPT Sensors Rnet Wiring SpecificationsField-Supplied Sensors for Wshp Open Controller Wire Field Controls Rnet WiringWire Terminal A50-8443A50-8141 A50-7764tfA50-8441 A50-8442Cooling Settings Dehumidificaton Mode SettingsHeating Settings CFM Adjust SettingsBlower Performance Data Wshp Open High Fan Airflow PRE-START-UPWshp Open Fan Only / Low Fan and Med Fan Airflow Field Selectable Inputs Complete C Control Jumper SettingsDeluxe D Control Jumper Settings DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings Units with Modulating Hot Water Reheat HWR OptionMode Input Output HWR Operating ModesSTART-UP Operating LimitsA50-8145 Water Out Operating Limits 50PTH, PTV, PTD UnitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Suction Discharge Super Sub Water Air Temp Unit Start-Up with Wshp Open Controls A50-8444Unit 50PTH, PTV Water Temperature F GPM Coaxial Water Pressure DropPTD 026 038 049Approximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Page Complete C Control LED Code Fault Descriptions LED Status Description of Operation Alarm RelayLED Fault Description Code Complete C and Deluxe D Board System TestAlarm Relay Aquazone Deluxe D Control LED IndicaService Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s Bat90.0 80.070.0 KOhm 60.0 50.0Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Good Practices Wshp TroubleshootingFault Heating Cooling Possible Cause Solution Code 7 Auto Resetting No Fault Code ShownOver/Under Voltage Performance MonitorTemperature in Heating High Head PressureLow Suction Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Alarm StatusStatus SensorAppendix a Wshp Open Screen Configuration MaintenanceSystem Settings ConfigurationSchedule Test Appendix a Wshp Screen Open ConfigurationService Screen Name Configuration ServicePoint Name Password Editable Range Default Level Alarm Page Page Copyright 2010 Carrier Corporation 50PTH,PTV,PTD START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8449 A50-8450