Operation Using a Programmable Logic Controller (PLC)

Digital Inputs

Safety Interlock: This normally open contact works like a soft emergency stop button. If the ProMix PD2K reads the input as CLOSED it interrupts system operation and removes power from the pumps regardless of the current operating mode. If the input is read as OPEN, the system operates normally

NOTE: This digital input is always enabled.

Do not toggle this input to put the system into Standby mode.

Gun Trigger: This normally open (maintained) contact provides a signal to the system to indicate whether or not a spray device is triggered. This input provides timing for alarm functions and also drives the flow control algorithm. If the input is OPEN the system operates as though the spray device is off. The input must be maintained CLOSED to signal that the spray device is triggered.

NOTE: The Gun Trigger discrete input must be enabled via Configure Screen 5 on the ADM. If it is set to ‘Network’ the discrete input is ignored and the spray device trigger signal is handled via the network communications.

If enabled, it is imperative that this signal be sent any time the spray device is triggered. Without the signal, the flow control features will not work.

Analog Inputs

Flow Control Set Point: When enabled, this 4-20mA signal input is used to set and adjust the operating flow control set point. The ProMix PD2K scales the set point linearly from 0 to the Max Set Point setting (see System Screen 5, page 71). Examples,

In Flow Control Mode: If the Max Set Point is 500 cc/min, a 4mA signal is 0 cc/min and a 20mA signal is 500 cc/min.

In Pressure Control Mode: If the Max Set Point is 500 psi, a 4mA signal is 0 psi and a 20mA signal is 500 psi.

NOTE: The Flow Control discrete input must be enabled via Configure Screen 5 on the ADM. If set to ‘Network’ the discrete input is ignored and set point adjustment is handled via the network communications.

4–20 mA Flow Control Set Point Input

PD2K Discrete Input

PLC (4–20 MA Signal)

Figure 10

O = Output

R = Return

332564B

25

Image 25
Contents ProMix PD2K Proportioner for Automatic Spray Applications Important Safety InstructionsContents Manual No Description Related ManualsManual No ECB Labels Models0359 Model AC2000 High Pressure Identification Label Fire and Explosion Hazard Intrinsic Safety Personal Protective Equipment Isocyanate Conditions Important Isocyanate ISO InformationKeep Components a and B Separate Moisture Sensitivity of IsocyanatesGeneral Information Advanced Display Module ADM USB Download ProcedureADM Display USB Upload Procedure ADM Keys and Indicators Function ADM Keys and IndicatorsSoft Key Functions Soft Key IconsKey Function Key Function Screen Icons Navigating the ScreensPower On Pre-operation ChecklistPre-Operation Tasks Flush Before Using Equipment Initial System SetupValve Settings With Color Change Without Color ChangePrime and Fill the System Operation Using Automatic Display Module ADMSpraying Flush Mixed Material PurgingFlush the System ShutdownSingle Color System Color Change SystemNetwork Communications and Discrete I/O Operation Using a Programmable Logic Controller PLCDiscrete I/O PD2K Discrete I/O ConnectionsAnalog Inputs Digital InputsKEY Discrete I/O Connections on EfcmCGM Overview Communication Gateway Module CGM DetailsCGM Kits Number Operation Mode Description Output Register 00 Current System ModeNetwork Communication I/O Data Map ProMix PD2K Network OutputsPump States for Output Registers Description Ber Output Registers 01, 02, 03, and 04 Pump StatusOutput Register 05 Actual Mix Flow Output Register 06 Actual Mix RatioOutput Register 27 Safety Interlock Input Status Output Register 14 Active Recipe Potlife Timeout Set PointOutput Registers 28 36 DCS Command Structure Output Register 12 Active Recipe Material B Flush SequenceOutput Register 38 40 Software Version Output Register 37 TimeOperation Using a Programmable Logic Controller PLC None Network Output Data Map Read OnlyPSI = ACK = Busy= NAK = ERRProMix PD2K Network Inputs Input Register 00 System Mode CommandInput Register 03 Mix Pump 1 Control Set Point Input Register 02 Flush/Prime Pump CommandInput Register 07 Go to Recipe Number Input Registers 14 21 DCS Command Structure Input Register 08 Clear Active AlarmInput Register 09 Job Complete Input Register 10 Gun 1 TriggerOperation Using a Programmable Logic Controller PLC Network Input Data Map Write/Read 40180 Gun 3 Trigger Uint32 Purge Mode Sequence Operation Flow ChartsInactive Pump Flush and Prime Sequences Flush Pump CommandChange Color Change SequenceStandby Mix Ready? no Mixing SequenceClear Active Alarm Alarm Clearing SequenceDynamic Command Description Network Communication Dynamic Command Structure DCSDynamic Commands with Command ID List of DCS CommandsWrite User ID DCSWrite Recipe Write Flush Sequence Read User ID Write Fluid Control ModeRead Flush Sequence Read RecipeRead Fluid Control Mode Yymmdd Read Job InfoYymmdddw Read Alarm InfoExample Ascii Character String Decode Algorithm Read Event Info Flow Control System Opening Screen Run Mode ScreensHome Screen See Advanced Screen 1, page 82, to set Home Screen Key Description DetailsKey Description Key Description Spray Screen Spray Screen, in Standby ModeFill Screen, Color a Selected Fill ScreenUsage Screen Usage ScreenJobs Screen Errors ScreenEvents Screen Password Screen Setup Mode ScreensSystem Screen Mix No Flow Timeout Mix Idle TimeoutLow Flow Timeout Mix Pressure ToleranceGun Hose Diameter Gun Hose LengthMix At Wall Hose Length and DiameterGateway ID EnableFlow Control Setpoint Signal Gun Trigger SignalFluid Control Manual OverrideRecipe Screen Flush Screen Pump Screen Default Settings Not Selected Default Settings SelectedPump Screen 3, Pressure Monitoring Disabled Pressure Alarm and Deviation LimitsCalibrate Screen Calibration ScreensVolume Check Screen Enter Measured Volume of Solvent Maintenance Screen Maintenance ScreensMaintenance Screen 4, Color Valve Resets Advanced Screen Log 90% Full Advisory Enabled Enable USB Downloads/UploadsDisplay Units Download DepthPump Pressure Check Calibration ChecksPerform the pressure check Pump Volume Check Scroll to Calibrate Screen 3, Solvent Meter CalibrationSingle Color Systems Color ChangeMultiple Color Systems To Clear Error and Restart System ErrorsGun Trigger Input Function Purge Errors Code Type Description Problem Cause Solution Error CodesMix Errors Code Type Description Problem Cause Solution Pumping Errors Code Type Description Problem Cause Solution EBH# Code Type Description Problem Cause SolutionSAD1 Pressure Errors Code Type Description Problem Cause Solution Qbdx QadxEmix System Errors Code Type Description Problem Cause SolutionCA0X CAC#CDC# CagxCddx USB Errors Code Type Description Problem Cause Solution USB WxudWxuu B9BX B9AXB9SX END# Calibration Errors Code Type Name DescriptionENS0 ENT#Code Type Name Description Maintenance ErrorsPreventive Maintenance Schedule MaintenanceCleaning the ADM FlushingPositive Displacement Metric Proportioner Technical DataGraco Information Graco Standard WarrantyFor Graco Canada Customers