Graco 332564B Operation Using a Programmable Logic Controller PLC, Discrete I/O, Efcm

Page 24

Operation Using a Programmable Logic Controller (PLC)

Operation Using a Programmable Logic Controller (PLC)

Network Communications and Discrete I/O

The ProMix PD2K Automatic system does not use a Booth Control module. Instead, it uses Network Communications and has optional Discrete I/O features to drive the system remotely.

Some automation control elements of the ProMix PD2K can be driven by a discrete input or network communications. These options need to be configured at the ADM (see System Screen 5, page 71). The following features can be set to ‘Discrete’ or ‘Network’:

Flow Control – Means of adjusting the control set point (see Flow Control Set Point below).

Gun Trigger – Means of signaling the ProMix PD2K when the spray device is triggered.

NOTE: The Manual Override check box enables a user to operate the system before the automation (PLC) is available. Manual Override can be used to run all functions of the system if a proper gun trigger signal is provided. It is not intended to be the main mode of control. Graco recommends that Manual Override be disabled during normal operation to avoid driving the system in a way that conflicts with the automation sequence.

Discrete I/O

The ProMix PD2K does not supply power for Discrete I/O. A clear understanding of these inputs is necessary to properly integrate the ProMix PD2K with the PLC or networking device. Input and output connections are made at the Discrete I/O terminal strips on the Enhanced Fluid Control Module (EFCM) inside the control box.

Table 3 and Figure 2 show where discrete I/O connections are made on the ProMix PD2K.

Table 3 PD2K Discrete I/O Connections

I/O

EFCM

Pins

Type

Description

Connector

 

 

 

 

 

 

Gun Trigger

6

1,2

Normally Open

Input

 

 

Contact

Control Set

7

1,2

4-20 mA Input

Point

 

 

 

Safety

7

11,12

Normally Open

Interlock

 

 

Contact

Input

 

 

 

24

332564B

Image 24
Contents Important Safety Instructions ProMix PD2K Proportioner for Automatic Spray ApplicationsContents Related Manuals Manual No DescriptionManual No Models ECB Labels0359 Model AC2000 High Pressure Identification Label Fire and Explosion Hazard Intrinsic Safety Personal Protective Equipment Important Isocyanate ISO Information Isocyanate ConditionsKeep Components a and B Separate Moisture Sensitivity of IsocyanatesGeneral Information USB Download Procedure Advanced Display Module ADMADM Display USB Upload Procedure ADM Keys and Indicators ADM Keys and Indicators FunctionSoft Key Icons Soft Key FunctionsKey Function Key Function Navigating the Screens Screen IconsPre-operation Checklist Power OnPre-Operation Tasks Initial System Setup Flush Before Using EquipmentValve Settings Without Color Change With Color ChangeOperation Using Automatic Display Module ADM Prime and Fill the SystemSpraying Purging Flush Mixed MaterialShutdown Flush the SystemSingle Color System Color Change SystemOperation Using a Programmable Logic Controller PLC Network Communications and Discrete I/ODiscrete I/O PD2K Discrete I/O ConnectionsDigital Inputs Analog InputsDiscrete I/O Connections on Efcm KEYCommunication Gateway Module CGM Details CGM OverviewCGM Kits Output Register 00 Current System Mode Number Operation Mode DescriptionNetwork Communication I/O Data Map ProMix PD2K Network OutputsOutput Registers 01, 02, 03, and 04 Pump Status Pump States for Output Registers Description BerOutput Register 05 Actual Mix Flow Output Register 06 Actual Mix RatioOutput Register 14 Active Recipe Potlife Timeout Set Point Output Register 27 Safety Interlock Input StatusOutput Registers 28 36 DCS Command Structure Output Register 12 Active Recipe Material B Flush SequenceOutput Register 37 Time Output Register 38 40 Software VersionOperation Using a Programmable Logic Controller PLC Network Output Data Map Read Only NonePSI = Busy = ACK= NAK = ERRInput Register 00 System Mode Command ProMix PD2K Network InputsInput Register 02 Flush/Prime Pump Command Input Register 03 Mix Pump 1 Control Set PointInput Register 07 Go to Recipe Number Input Register 08 Clear Active Alarm Input Registers 14 21 DCS Command StructureInput Register 09 Job Complete Input Register 10 Gun 1 TriggerOperation Using a Programmable Logic Controller PLC Network Input Data Map Write/Read 40180 Gun 3 Trigger Uint32 Operation Flow Charts Purge Mode SequenceFlush Pump Command Inactive Pump Flush and Prime SequencesColor Change Sequence ChangeMixing Sequence Standby Mix Ready? noAlarm Clearing Sequence Clear Active AlarmNetwork Communication Dynamic Command Structure DCS Dynamic Command DescriptionList of DCS Commands Dynamic Commands with Command IDWrite User ID DCSWrite Recipe Write Flush Sequence Write Fluid Control Mode Read User IDRead Recipe Read Flush SequenceRead Fluid Control Mode Read Job Info YymmddRead Alarm Info YymmdddwExample Ascii Character String Decode Algorithm Read Event Info Flow Control System Run Mode Screens Opening ScreenHome Screen Home Screen Key Description Details See Advanced Screen 1, page 82, to setKey Description Key Description Spray Screen, in Standby Mode Spray ScreenFill Screen Fill Screen, Color a SelectedUsage Screen Usage ScreenErrors Screen Jobs ScreenEvents Screen Setup Mode Screens Password ScreenSystem Screen Mix Idle Timeout Mix No Flow TimeoutLow Flow Timeout Mix Pressure ToleranceGun Hose Length Gun Hose DiameterMix At Wall Hose Length and DiameterEnable Gateway IDGun Trigger Signal Flow Control Setpoint SignalFluid Control Manual OverrideRecipe Screen Flush Screen Pump Screen Default Settings Selected Default Settings Not SelectedPressure Alarm and Deviation Limits Pump Screen 3, Pressure Monitoring DisabledCalibration Screens Calibrate ScreenVolume Check Screen Enter Measured Volume of Solvent Maintenance Screens Maintenance ScreenMaintenance Screen 4, Color Valve Resets Advanced Screen Enable USB Downloads/Uploads Log 90% Full Advisory EnabledDisplay Units Download DepthCalibration Checks Pump Pressure CheckPerform the pressure check Pump Volume Check Solvent Meter Calibration Scroll to Calibrate Screen 3,Color Change Single Color SystemsMultiple Color Systems System Errors To Clear Error and RestartGun Trigger Input Function Error Codes Purge Errors Code Type Description Problem Cause SolutionMix Errors Code Type Description Problem Cause Solution Pumping Errors Code Type Description Problem Cause Solution Code Type Description Problem Cause Solution EBH#SAD1 Pressure Errors Code Type Description Problem Cause Solution Qadx QbdxSystem Errors Code Type Description Problem Cause Solution EmixCA0X CAC#Cagx CDC#Cddx USB Errors Code Type Description Problem Cause Solution Wxud USBWxuu B9AX B9BXB9SX Calibration Errors Code Type Name Description END#ENS0 ENT#Maintenance Errors Code Type Name DescriptionMaintenance Preventive Maintenance ScheduleCleaning the ADM FlushingTechnical Data Positive Displacement Metric ProportionerGraco Standard Warranty Graco InformationFor Graco Canada Customers