Operation Using a Programmable Logic Controller (PLC)
OUTPUT REGISTER 12: Active Recipe Material B Flush Sequence
The Active Recipe Material B Flush Sequence register contains the number of the Flush Sequence (1 – 5) that is associated with the Catalyst pump of the current recipe.
•If the current recipe is invalid this value reflects the Flush Sequence associated with Material B pump of recipe 0.
•This value is 0 if the current recipe ratio is 0:1 (1K recipe)
OUTPUT REGISTER 13: Active Recipe Ratio Set Point
The Active Recipe Ratio Set Point data register contains the ratio set point associated with the current recipe.
•The value reported is the ratio antecedent multiplied by 100. The ratio consequent is always 1.
Example: Value = 250 >> A mix ratio of 2.5:1 (Material A to Material B)
•This value is 0 if the current recipe ratio is 0:1 (1K recipe)
OUTPUT REGISTER 14: Active Recipe Potlife Timeout Set Point
The Active Recipe Potlife Timeout Set Point register contains the set point for the potlife time associated with the current recipe in minutes.
•This value is 0 if the potlife time is disabled for the current recipe.
OUTPUT REGISTER 15: Actual Pump 1 Flow Rate
OUTPUT REGISTER 16: Actual Pump 2 Flow Rate
OUTPUT REGISTER 17: Actual Pump 3 Flow Rate
OUTPUT REGISTER 18: Actual Pump 4 Flow Rate
These registers contain the instantaneous flow rate of Pumps
This is NOT the mix flow rate. For mix flow rate see Actual Mix Flow.
OUTPUT REGISTER 19: Actual Pump 1 Fluid
Pressure
OUTPUT REGISTER 20: Actual Pump 2 Fluid
Pressure
OUTPUT REGISTER 21: Actual Pump 3 Fluid
Pressure
OUTPUT REGISTER 22: Actual Pump 4 Fluid
Pressure
These registers contain the instantaneous fluid pressure on the outlet of pumps
OUTPUT REGISTER 23: Gun 1 Trigger Input Status
The Gun 1 Trigger Input Status register contains the status of the Gun Trigger Discrete Input.
•The value is 0 if the input is OPEN (gun not triggered).
•The value is 1 if the input is CLOSED (gun triggered).
This data register is valid only for systems configured to use the discrete input for the Gun Trigger. See Gun Trigger Signal, page 71.
OUTPUT REGISTER 24: Gun 2 Trigger Input Status
OUTPUT REGISTER 25: Gun 3 Trigger Input Status
OUTPUT REGISTER 26: Gun 4 Trigger Input Status
These registers are not used.
OUTPUT REGISTER 27: Safety Interlock Input Status
The Safety Interlock Input Status register contains the status of the Safety Interlock Discrete Input.
•The value will be 0 if the input is OPEN (Normal).
•The value will be 1 if the input is CLOSED (Safety Stop).
See Safety Interlock in Digital Inputs, page 25.
OUTPUT REGISTERS 28 – 36: DCS Command Structure
See Dynamic Command Description, page 47.
30 | 332564B |