Ingersoll-Rand IRN37-160K-CC, IRN250-300H-2S, IRN50-200H-CC, IRN75-160K-2S Alarms, Alarm Main Menu

Page 80

9.0 OPERATING INSTRUCTIONS

9.15 ALARMS

When an Alarm occurs, a large exclamation mark in a triangle will flash on the display screen. The display message will indicate what caused the Alarm.

The compressor will stop and cannot be re−started again until the alarm condition no longer exists and the alarm message reset.

Pressing the STATUS button will display the STATUS screen. The presence of the ALARM button indicates that an Alarm condition still exists. Alarm Status is the list of machine operating conditions that existed at the time of the Alarm.

The name and value of each of the items listed can be seen by moving the list up and down using the arrow buttons. Pressing the ALARM button will return the display to the Alarm screen and the RESET button.

The Alarm needs to be reset by the operator by pressing the RESET button twice. Any exceptions to this are explained in the alarm descriptions.

 

 

 

 

 

 

 

 

100

 

PSI

 

 

 

 

 

 

 

 

−ALARM STATUS−

 

STOPPED BY

 

 

 

PACKAGE DISCH

 

ALARM

 

 

PRESSURE

 

 

 

 

 

100 psi

 

 

 

 

 

PACKAGE DISCHARGE

 

 

 

 

 

 

TEMP

 

 

 

 

 

103° F

 

 

 

 

 

 

 

ALARM

 

 

MAIN MENU

 

The possible Alarm messages are as follows;

EMERGENCY STOP− This will occur if the Emergency Stop button is engaged. The button must be disengaged before the alarm can be cleared.

BLOWER FAULT− This will occur if a blower fault is sensed.

HIGH AIREND DISCH TEMP− This will occur if the airend discharge temperature is greater than 109° C (228° F).

REMOTE START FAILURE− This will occur if the Remote Start button is pressed after the machine is running or if the Remote Start button remains closed.

REMOTE STOP FAILURE− This will occur if the Remote Stop button remains open and either Start button is pressed.

SENSOR FAILURE − This will occur if a sensor is recognized as missing or broken.

VSD FAULT − The VSD fault is read from the drive. The Intellisys will read the status menu of the variable speed drive. If a fault condition is returned in the status information, the Intellisys will issue a VSD FAULT alarm and display the number of the fault condition.

CONTROL POWER LOSS − This will occur if the control circuit is broken by a bad connection or safety switch (e.g. HAT Switch/ Phase Monitor). Any fall of voltage below 100VAC for more than 2 seconds will cause this alarm trip.

STOP FAILURE − This will occur if the compressor should be stopped but the motor is still running above minimum speed 4 seconds after the stop signal is given.

HIGH START PRESSURE − If the sump pressure is above 100 psi (6.9 bar) when the compressor starts, the Intellisys will open the blowdown valve during the first few seconds of starting (3 to 7 seconds). If the sump pressure does not fall to 100 psi (6.9 bar) during that time period, this shutdown will occur.

CHECK MOTOR ROTATION − This will occur if the Intellisys reads a negative speed from the VSD when starting .

VSD COMMUNICATION FAILURE − This will occur if the Intellisys does not receive a response from the VSD when requesting information. This alarm will take about 8 seconds to occur.

VSD INITIALIZATION FAULT − Will occur if the Intellisys is unable to establish communications with the VSD after a power up.

LOW SUMP PRESSURE − Will occur if the compressor is operating at or above the minimum speed and the sump pressure drops below 15psi (1.03 bar) for 15 seconds.

REPLACE COOLANT FILTER − This will occur if the coolant filter is blocked and requires changing.

INCORRECT VSD TYPE − Will occur at power up if the VSD type does not match the size of the compressor

125HP (90kW) machines and above also have the following alarm messages;

CONTROL POWER LOSS − This will occur if the compressor should be running and the AC input voltage, as read from the VSD, falls below 100 VAC. There is a delay of 2 seconds on this alarm in case the power quickly returns. An open HAT switch or phase monitor are two things that can cause this alarm.

STOP FAILURE − This will occur if the compressor should be stopped, but the motor speed has not dropped below the minimum motor speed setpoint. The Intellisys will wait 4 seconds for the compressor to stop before issuing this alarm.

HIGH INTERSTAGE PRESSURE − If the interstage pressure is over 100psi while the unit is running and the unit is a 2−stage.

78IRN37 - 160K - CC & IRN50 - 200H -CC & IRN75 - 160K - 2S & IRN100 - 200H - 2S & IRN 250 - 300H - 2S

http://air.irco.com

Image 80
Contents Operation and Maintenance Manual AIR Compressor Group Bonded Warranty & Registered Start UP Contents Somer ForewordIf in Doubt Consult Supervision FOREWORD Abbreviations & Symbols Energy recovery systemERS F.CThis unit was purchased from Purchase Order DetailsRotary Screw AIR Compressor Compressed air SafetyGeneral Information Materials Avoid INGESTION, Skin Contact Inhalation of FumesTransport ElectricalCondensate disposal Coolant disposalText Decals Discharge airLift here Rotation 39540257 RevCondensate Drain Electrical power inlet Safety Graphic Form and Meaning of ISO Symbols Prohibition / Mandatory Information / InstructionsDo not stand on any service valve or Safety Coolant Separator Pressure AIR Discharge Belt Tension Filter Motor Lubrication Receipt / Handling ReceiptIngersoll Rand Company Unpacking and HandlingInstallation Location in PlantFor technical information see section Ensure that the correct tie down points are usedInstallation Discharge and Condensate Piping Installation Electrical Example of voltage imbalance calculation Installation Very ImportantFuse Type Adjusting the Aftercooler Trim Valve Cooling Water PipingModel Minimum cooling water requirement vs Range 50F 70FWater quality recommendations Psi Installation SEA Watercooled Units Selected Units onlyOrifice diameter in mm Outdoor Sheltered Installation General Information Technical INFORMATION-SINGLE StageMinimum ambient temperature C F Weight Kg lbs Cooling clean water flow l/min US 51/38 95/46Sound pressure level dBA Flow at 7.5 Barg m3/minCooling clean water flow l/min US 84/65 95/72 Max fuse size @ 380V − 415V aMax fuse size @ 440V − 480V a Max fuse size @ 550V − 575V aN132K N160K N200H General Information Technical Information − TWO Stage 5933 Flow at 100 psig cfm 11001690 1527Installation DRAWING−N37/45K−CC & N50/60H−CC − Air Cooled KEYInstallation DRAWING− N37/45K−CC & N50/60H−CC − Water Cooled Installation Drawing − N55/75K−CC & N75/100H−CC − Air Cooled Installation DRAWING−N55/75K−CC & N75/100H−CC−Water Cooled General Information General Information General Information General Information KEY 22381206 Revision B Equipment downstream of compressor 23128994 Revision a Stage onlyAir/coolant Coolant Condensate Cooling water W.C. only 22099006 Revision C General Information Process and Instrumentation Diagram N250−300H TWO Stage 22402135 Revision CPiping legend Wiring Schematic N37K − N45K-CC / N50-60h−cc a/c blower vfd Stop FDWires Numbers Function Wire colorWiring schematic n55-75k-cc / n75-100h-cc a/c Blower vfd Label DescriptionWires Numbers Function Wire color SS1-3Wiring schematic n37/45k-cc/n50/60h-cc w/c SgneColor Wiring schematic n55-75k-cc / n75-100h-cc W/c 23131345 Revision a4ATT SENSOR, Package AIR Discharge Temperature 4CTT Revision M Wiring schematic n75-160k-cc / n125-200h-cc A/c22093058 F10 SGNeWiring schematic n75-160k-cc / n125-200h-cc W/c Revision E4SV VALVE, Water Stop 6APT Wiring schematic n250-300H 380-480V SG-Ne4ATT SENSOR, Package AIR Discharge Temperature 6APT General Information General Description Operating Instructions Basic OperationStopping the machine in an emergency Intellisys Controls ArrowsDisplay Screen Main MenuCurrent Status Screen Current Status itemsMain Menu Ready to StartOperator Setpoints Default MIN MAX Step Unit Operator SetpointsCondensate Interval Options Selection MIN MAXSensor Calibration Scheduled startAlarm History Clock FunctionsEnergy Status Messages Service Warnings Initial Check AlarmsAlarms Alarm Main MenuMaintenance Ultra Coolant Maintenance Procedures Prior to attempting any maintenance work, ensure that− Prior to starting Coolant level checking procedure Adding coolantCoolant filter change procedure Separator element checking procedureSeparator element change procedure Drain sequence for N250/300H−2SSeparator element change procedure for N250/ 300H−2S Scavenge screen clean/check procedureStart the compressor and check for leaks and coolant level Separator tank / Pressure systemAir filter change procedure Air filter change procedure N250/300H−2SAircooled Cooler Cleaning Blower motor Re−GreaseN50/100H N37/75K Watercooled Cooler Cleaning High Airend Temperature Sensor checking procedureCoolant Coolers AftercoolerBlower / fan Motor Bearing Maintenance Stored units Motor cowl cleaning N75−160 units onlyDrive Box Filter Removal / Replacement Moisture Separator Check / CleaningFluid and Vibration Monitoring No Loss Drain Trap where fitted Check / CleaningCoolant Sampling Procedure Fault Finding General FaultsSymptom Fault Remedy Compressor will not No power supply to packageCheck and modify settings Or not sealing correctly With correct coolantRemove blockage, repair or replace damaged See aboveWith coolant’ Fault Cause Remedy Pressure transducerIndicated on the INTELhYS Controller Drive FaultsFault Cause Action