Ingersoll-Rand IRN250-300H-2S, IRN37-160K-CC manual Separator tank scavenge check valve/orifice

Page 91

10.0 MAINTENANCE

Watercooled machines

Shut off the cooling water.

The machine should trip at 109° C (228° F).

caution

Under no circumstances should these discharge temperatures be exceeded. If the machine fails to trip A FAULT EXISTS. Investigate immediately.

Separator tank scavenge check valve/orifice

Disconnect tubing at each end of check valve/ screen/ orifice assembly.

Check orifice and clean if required. Use suitable tool and remove orifice from its housing. Be careful not to damage flared end of fitting or O−ring.Wash housing in safety solvent and blow dry.

Press the check valve/orifice into fitting block.

Assemble the check valve/orifice assembly to the

tubing lines.The fitting must be re−installed with the check valve on the upstream side of the orifice as indicated by the flow arrow.

Blower / fan Motor Bearing Maintenance (Stored units)

Prior to placing a unit in storage for extended intervals, rotate the blower motor several revolutions by hand in the direction of rotation.

On N75 − 160, N250 − 300H aircooled units, whilst rotating the motor, pump grease into the bearing until grease is seen at the relief port.

Thereafter rotate the motor as described above every three months until such time as the unit is placed in service.

If the storage time is to exceed a total of nine (9) months duration, the compressor must be ordered for long term storage.

Motor cowl cleaning N75−160 units only

Ensure compressor is electrically isolated for at least 15 minutes before commencing any maintenance work.

Remove panels from the compressor.

Using a clean dry cloth, remove dust from the surface of the motor cowl and ensure all ventilation slots are free of obstructions.

Replace panels to the compressor.

Drive Box Filter Removal / Replacement

Ensure compressor is electrically isolated for at least 15 minutes before commencing any maintenance work.

Unclip the front grill of the drive box filter.

Remove the filter pad from the housing and replace with a new filter pad from Ingersoll Rand.

Replace front grill to the drive box filter.

Moisture Separator Check / Cleaning

Ensure compressor is electrically isolated for at least 15 minutes, before commencing any maintenance work.

Isolate the compressor from the system and fully discharge the compressed air within the unit.

Remove plastic tube from the fitting located on the bottom of the moisture separator.

Remove the bowl of the moisture trap, clean and replace.

Condensate (Moisture) Drain Valve / Trap

Ensure compressor is electrically isolated for 15 minutes and all pressure is relieved from system.

Remove all pipes going to and from the valve (or trap).

Disconnect any electrical cables to the valve (or trap).

Determine the type of condensate drain device and continue in the appropriate section below:−

Timed Solenoid Drain Valves (where fitted) Check / Cleaning

Remove the central nut and then the electrical coil.

Remove screws holding bonnet of valve and carefully split the valve. Clean and inspect all internal parts.

Similarly check and clean the ball valve and needle valve.

Replace any defective parts as identified in parts manual.

Re−assemble and later, with machine running, check that condensate and air is expelled at frequency and duration set into the INTELLISYS controller (see section 9.6).

IRN37 - 160K - CC & IRN50 - 200H & IRN75 - 160K - 2S & IRN - 100 - 200H - 2S & IRN 250 - 300H - 2S

89

http://air.irco.com

 

Image 91
Contents Operation and Maintenance Manual AIR Compressor Group Bonded Warranty & Registered Start UP Contents If in Doubt Consult Supervision ForewordSomer FOREWORD F.C Abbreviations & SymbolsEnergy recovery system ERSRotary Screw AIR Compressor Purchase Order DetailsThis unit was purchased from General Information SafetyCompressed air Electrical MaterialsAvoid INGESTION, Skin Contact Inhalation of Fumes TransportCoolant disposal Condensate disposalDischarge air Text DecalsLift here 39540257 Rev RotationCondensate Drain Electrical power inlet Prohibition / Mandatory Information / Instructions Safety Graphic Form and Meaning of ISO SymbolsDo not stand on any service valve or Safety Coolant Separator Pressure AIR Discharge Belt Tension Filter Motor Lubrication Unpacking and Handling Receipt / HandlingReceipt Ingersoll Rand CompanyEnsure that the correct tie down points are used InstallationLocation in Plant For technical information see sectionInstallation Discharge and Condensate Piping Installation Electrical Fuse Type Installation Very ImportantExample of voltage imbalance calculation 50F 70F Adjusting the Aftercooler Trim ValveCooling Water Piping Model Minimum cooling water requirement vs RangeWater quality recommendations Orifice diameter in mm Installation SEA Watercooled Units Selected Units onlyPsi Outdoor Sheltered Installation Technical INFORMATION-SINGLE Stage General InformationFlow at 7.5 Barg m3/min Minimum ambient temperature C F Weight Kg lbsCooling clean water flow l/min US 51/38 95/46 Sound pressure level dBAMax fuse size @ 550V − 575V a Cooling clean water flow l/min US 84/65 95/72Max fuse size @ 380V − 415V a Max fuse size @ 440V − 480V aN132K N160K N200H General Information Technical Information − TWO Stage 1527 5933Flow at 100 psig cfm 1100 1690KEY Installation DRAWING−N37/45K−CC & N50/60H−CC − Air CooledInstallation DRAWING− N37/45K−CC & N50/60H−CC − Water Cooled Installation Drawing − N55/75K−CC & N75/100H−CC − Air Cooled Installation DRAWING−N55/75K−CC & N75/100H−CC−Water Cooled General Information General Information General Information General Information KEY 22381206 Revision B Equipment downstream of compressor Stage only 23128994 Revision aAir/coolant Coolant Condensate Cooling water W.C. only 22099006 Revision C General Information 22402135 Revision C Process and Instrumentation Diagram N250−300H TWO StagePiping legend Stop FD Wiring Schematic N37K − N45K-CC / N50-60h−cc a/c blower vfdNumbers Function Wire color WiresLabel Description Wiring schematic n55-75k-cc / n75-100h-cc a/c Blower vfdSS1-3 Wires Numbers Function Wire colorSgne Wiring schematic n37/45k-cc/n50/60h-cc w/cColor 23131345 Revision a Wiring schematic n55-75k-cc / n75-100h-cc W/c4ATT SENSOR, Package AIR Discharge Temperature 4CTT 22093058 Wiring schematic n75-160k-cc / n125-200h-cc A/cRevision M SGNe F10Revision E Wiring schematic n75-160k-cc / n125-200h-cc W/c4SV VALVE, Water Stop 6APT 380-480V SG-Ne Wiring schematic n250-300H4ATT SENSOR, Package AIR Discharge Temperature 6APT General Information General Description Basic Operation Operating InstructionsStopping the machine in an emergency Arrows Intellisys ControlsMain Menu Display ScreenCurrent Status items Current Status ScreenReady to Start Main MenuOperator Setpoints Operator Setpoints Default MIN MAX Step UnitCondensate Interval Selection MIN MAX OptionsScheduled start Sensor CalibrationClock Functions Alarm HistoryEnergy Status Messages Initial Check Alarms Service WarningsAlarm Main Menu AlarmsMaintenance Ultra Coolant Maintenance Procedures Prior to attempting any maintenance work, ensure that− Adding coolant Prior to starting Coolant level checking procedureDrain sequence for N250/300H−2S Coolant filter change procedureSeparator element checking procedure Separator element change procedureSeparator tank / Pressure system Separator element change procedure for N250/ 300H−2SScavenge screen clean/check procedure Start the compressor and check for leaks and coolant levelBlower motor Re−Grease Air filter change procedureAir filter change procedure N250/300H−2S Aircooled Cooler CleaningN50/100H N37/75K Aftercooler Watercooled Cooler CleaningHigh Airend Temperature Sensor checking procedure Coolant CoolersMoisture Separator Check / Cleaning Blower / fan Motor Bearing Maintenance Stored unitsMotor cowl cleaning N75−160 units only Drive Box Filter Removal / ReplacementCoolant Sampling Procedure No Loss Drain Trap where fitted Check / CleaningFluid and Vibration Monitoring Compressor will not No power supply to package Fault FindingGeneral Faults Symptom Fault RemedyCheck and modify settings With correct coolant Or not sealing correctlyWith coolant’ See aboveRemove blockage, repair or replace damaged Pressure transducer Fault Cause RemedyFault Cause Action Drive FaultsIndicated on the INTELhYS Controller